Plan Review Details - Permit 17030176
Plan Review Stops For Permit 17030176
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-10 Cont ID  
Sent By tklarge Date 2017-03-10 Time 09:49 Rev Time 0.00
Received By tklarge Date 2017-03-07 Time 11:33 Sent To  
Notes
2017-03-08 11:33:20IN PLUMBING BACKFLOW INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-06 Cont ID  
Sent By tklarge Date 2017-03-06 Time 05:49 Rev Time 0.00
Received By tklarge Date 2017-03-06 Time 05:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-03-10 Cont ID  
Sent By tklarge Date 2017-03-10 Time 09:49 Rev Time 0.00
Received By tklarge Date 2017-03-08 Time 13:02 Sent To  
Notes
2017-03-08 13:11:37APPROVED BY PLUMBING. SENT TO UTILITIES FOR REVIEW.

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-06 Cont ID  
Sent By tklarge Date 2017-03-06 Time 05:49 Rev Time 0.00
Received By tklarge Date 2017-03-06 Time 05:40 Sent To  
Notes
2017-03-06 05:49:21ALL BACKFLOW DEVICES MUST BELISTED ON THE UNIVERSITY OF
 SOUTHERN CALIFORNIA?S ( USC ) LIST OF APPROVED DEVICES.
 THE SUBMITTED DOCUMENT IS THE INSTALLATION, TESTING AND
 MAINTENANCE INSTRUCTION BOOKLET AND THERE IS NOTHING IN
 THE BOOKLET THAT STATES THE DEVICE IS ON THE USC'S LIST
 OF APPROVED DEVICES. THIS INFORMATION IS FOUND IN THE
 MANUFACTURER'S SPECIFICATION SHEETS, NOT IN THE
 INSTALLATION MANUAL. PLEASE SUBMIT TWO COPIES OF THE
 MANUFACTURER'S SPECIFICATION SHEETS THAT STATE THE
 DEVICE IS ON THE USC LIST OF APPROVED DEVICES PER THE
 CITY WPB CROSS- CONNECTION CONTROL MANUAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  