Plan Review Details - Permit 17030022
Plan Review Stops For Permit 17030022
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-16 Cont ID  
Sent By jleahy Date 2017-03-16 Time 07:29 Rev Time  
Received By jwitmer Date 2017-03-16 Time 06:29 Sent To  
Notes
2017-03-16 07:28:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17030022
 ADD: 2300 PRESIDENTIAL WAY
 CONT: HEDRICK BROTHERS
 TEL: 561-689-0880
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 16/ 2017
 ACTION: DENIED
  
 1) SITE PLAN:
 1A) THE SITE PLAN IS BLOWN UP SO LARGE THE LOCATION
 CANNOT BE VERIFIED AS TO THE LOCATION AND ADDRESS. SITE
 PLAN INDICATES BANYAN CAY RESORT BUT THE PERMIT
 APPLICATION INDICATES 2300 PRESIDENTIAL WAY. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED.
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES AND, AS APPLICABLE,
 FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN FLOOD
 ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE WITH AN
 ACCURATE BOUNDARY LINE SURVEY.
  
 1B) THE SITE PLAN SHOWS (3) ACCESSIBLE PARKING SPACES
 AND ACCESS AISLES BUT THERE ARE NO DETAILS SHOWING
 COMPLIANCE WITH ANY ACCESSIBLE ELEMENTS OF EITHER THE
 ACCESSIBLE PARKING SPACE NOR THE ACCESS AISLE.
 2014 FBC-ACCESS. CODE PARKING SECTION 502.1-502.7.
  
 2) THE SUBMITTED PLANS AND MODULAR UNIT WERE DESIGNED
 TO THE 1997 SBBCI WITH A WIND SPEED OF 110 MPH FASTEST
 MILE. OUR CURRENT CODE IS DESIGNED TO 170 VULT 3 SECOND
 GUST. PLEASE SHOW THE RELATIONSHIP IN WIND SPEEDS AND
 HOW COMPLIANCE WITH THE 2014 EXISTING BUILD. CODE
 SECTION 1302.3 WIND LOADS MAKE COMPLIANCE. [B] 1302.3
 WIND LOADS. BUILDINGS SHALL COMPLY WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 EXCEPTIONS:
 2. STRUCTURAL ELEMENTS WHOSE STRESS IS NOT INCREASED BY
 MORE THAN 10 PERCENT.
 3. MANUFACTURED BUILDINGS AS APPROVED BY THE
 MANUFACTURED BUILDINGS PROGRAM, FLORIDA DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION.
 YOU CAN INTERPOLATE BETWEEN CONTROL LINES.
  
 3) SHEET A1 SHOW EACH MANUFACTURED BUILDING WILL HAVE 2
 EXITS. THE SITE PLAN ONLY SHOWS RAMPS AT THE MAIN EXIT,
 THERE HAS BEEN NO CONSIDERATION HOW THE SECONDARY EXIT
 WILL BE ACHIEVED? FBC-B 2027.1.
 EXITS SHALL DISCHARGE DIRECTLY TO THE EXTERIOR OF THE
 BUILDING. THE EXIT DISCHARGE SHALL BE AT GRADE OR SHALL
 PROVIDE DIRECT ACCESS TO GRADE. SHEET RS-1 SHOWS
 DETAILS FOR AN ACCESSIBLE RAMP BUT NO STAIR NOR LANDING
 DETAILS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
2017-03-10 15:14:51RESULTED BY MISTAKE JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-10 Cont ID  
Sent By jleahy Date 2017-03-10 Time 15:14 Rev Time 0.00
Received By jleahy Date 2017-03-10 Time 12:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-09 Cont ID  
Sent By wjolin Date 2017-03-09 Time 15:10 Rev Time 0.00
Received By wjolin Date 2017-03-09 Time 14:44 Sent To  
Notes
2017-03-09 15:10:342300 PRESIDENTIAL WAY - CONSTRUCTION TRAILER COMPOUND
 PERMIT #17030022
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED ON THE PLANS.
  
 PROVIDE A LEGIBLE AND DETAILED SITE PLAN. THE CURRENT
 PLAN IS OVERLAID AND IS VERY DIFFICULT TO READ AND
 UNDERSTAND EXACT TRAILER LOCATIONS.
  
 THE PLANS INDICATE ONE TYPICAL FLOOR PLAN WILL BE USED
 FOR ALL THREE TRAILER COMPOUNDS. CONFIRM THIS IS
 ACCURATE.
  
 NO PORTABLE FIRE EXTINGUISHERS PROVIDED. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 NO STAIR, HANDRAIL, OR GUARDRAIL DETAILS SUBMITTED.
  
 EACH TRAILER INDICATES A PRIMARY AND SECONDARY EXIT;
 HOWEVER, NO EXIST DISCHARGE INFORMATION IS PROVIDED.
  
 PLANS INDICATE AN ADA RAMP; HOWEVER, THESE RAMPS CANNOT
 BE LOCATED ON THE SITE PLAN.
  
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 THE CITY OF WEST PALM BEACH REQUIRES CONSTRUCTION
 TRAILERS LARGER THAN A SINGLE "DOUBLE WIDE" (OR TWO
 "SINGLE WIDE") TO EITHER BE PROTECTED BY AN AUTOMATIC
 SPRINKLER SYSTEM OR COMPLY WITH THE SEPARATION
 REQUIREMENTS OF NFPA 241. TEMPORARY CONSTRUCTION
 TRAILERS OR MODULAR BUILDINGS WILL REQUIRE A PERMIT AND
 COMPLIANCE WITH THE FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 DEAD-END FIRE DEPARTMENT ACCESS ROADS IN EXCESS OF 150
 FEET IN LENGTH SHALL BE PROVIDED WITH APPROVED
 PROVISIONS FOR THE FIRE APPARATUS TO TURN AROUND. PER
 SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT ACCESS
 ROADS SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE
 APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL
 HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND
 AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES.
  
 PLANS DO NOT INDICATE ANY NEW OR EXISTING FIRE HYDRANTS
 TO PROTECT THE TRAILER COMPOUND.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-11 Cont ID  
Sent By jroach Date 2017-04-11 Time 11:21 Rev Time 0.00
Received By jroach Date 2017-03-01 Time 10:19 Sent To  
Notes
2017-03-03 10:19:16B04

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2017-03-09 Cont ID  
Sent By ccole Date 2017-03-09 Time 06:58 Rev Time 0.00
Received By ccole Date 2017-03-08 Time 17:52 Sent To  
Notes
2017-03-09 06:59:25 
 SEPARATE PERMIT REQUIRED FROR HVAC ALTERATIONS.
 CCOLE

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-03-13 Cont ID  
Sent By gjohnson Date 2017-03-13 Time 14:57 Rev Time 0.00
Received By gjohnson Date 2017-03-13 Time 13:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-04-11 Cont ID  
Sent By jroach Date 2017-04-11 Time 11:21 Rev Time 0.00
Received By jroach Date 2017-04-11 Time 11:21 Sent To  
Notes
2017-04-11 11:21:55PROVISO
  
 ALL CONSTRUCTION TRAILERS SHALL BE REMOVED WITHIN SEVEN
 DAYS OF THE FINAL CONSTRUCTION INSPECTION BY THE CITY
 AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY.
  