Plan Review Stops For Permit 17030007 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2017-11-17 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-11-17 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-11-15 |
Time |
17:18 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2017-09-26 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-09-26 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-09-26 |
Time |
07:38 |
Sent To |
P |
|
Notes |
2017-09-26 15:09:29 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 2ND REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. PROVISO ISSUED FOR ELEVATION CERTIFICATE. SEE | | COMMENTS UNDER NFIP REVIEW. | | 2. OWNER/AGENT TO SIGN ENERGY SUBMITTALS. | | 3. DIGITAL SIGNATURE ON STRUCTURAL PLANS - NOT VALID. | | PROVIDE SIGNATURE AND SEAL OF STRUCTURAL ENGINEER. | | | | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. | | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 | | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE | | COMPLIANCE BY SECTION 405. | | | | ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN | | ACCORDANCE WITH THE PROVISIONS OF FLORIDA STATUTES | | 471.025, AND RULE 61G15-23.001, F.A.C. MAY BE | | PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN | | BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE. | | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE | | LICENSEES SIGNATURE ON EACH PAGE REQUIRED TO BE SEALED. | | A SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE | | OF THE LICENSEES SIGNATURE SHALL NOT BE USED. | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2017-04-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-04-10 |
Time |
14:10 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-04-10 |
Time |
09:51 |
Sent To |
|
|
Notes |
2017-04-10 14:27:23 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 1ST REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1. SEPERATE PERMIT REQUIRED FOR ACCESSORY STRUCTURE | | (CABANA). STATED VALUE MAY BE PRORATED BETWEEN | | STRUCTURES. | | | | 2. THIS REVIEW IS ONLY FOR THE MAIN RESIDENCE. A REVIEW | | OF THE CABANA MAY GENERATE ADDITIONAL COMMENTS. | | | | 3. PALM BEACH COUNTY IMPACT FEES REQUIRED. | | | | 4. ROOFING PERMIT REQUIRED. PROVIDE PRODUCT APPROVALS | | FOR NEW ROOFING SYSTEM COMPONENTS. | | | | 5. THIS PROPERTY LIES IN FLOOD ZONE A5. BASE FLOOD | | ELEVATION IS 7.5 FT. CORRECT FLOOD ZONE NOTE ON SURVEY. | | FBC 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) & | | R322.2.1 ELEVATION REQUIREMENTS. BUILDINGS AND | | STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS | | COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED | | TO 6 INCHES ABOVE THE DESIGN FLOOD ELEVATION. PROVIDE | | FLOOD DESIGN INFORMATION ON THE PROPOSED SURVEY AND | | PROVIDE FLOOD ELEVATION CERTIFICATE. | | | | G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION. | | FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION | | SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO | | THE FOLLOWING: | | | | 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY | | WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS | | TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF | | FLOODWATERS. | | | | SECTION R322 FLOOD-RESISTANT CONSTRUCTION | | R322.1 GENERAL. | | BUILDINGS AND STRUCTURES CONSTRUCTED IN WHOLE OR IN | | PART IN FLOOD HAZARD AREAS (INCLUDING A OR V ZONES) AS | | ESTABLISHED IN TABLE R301.2(1) SHALL BE DESIGNED AND | | CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS CONTAINED | | IN THIS SECTION. BUILDINGS AND STRUCTURES LOCATED IN | | WHOLE OR IN PART IN IDENTIFIED FLOODWAYS SHALL BE | | DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ASCE 24. | | | | FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS | | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE | | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE | | AND LOCATION OF NEW CONSTRUCTION AND EXISTING | | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE | | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED | | GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS, | | FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE | | DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE | | SURVEY. | | | | 6. ELEVATION CERTIFICATE REQUIRED AT PERMITTING AND | | PRIOR TO C.O. | | | | 1612.5 FLOOD HAZARD DOCUMENTATION. | | THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND | | SEALED BY A REGISTERED DESIGN PROFESSIONAL AND | | SUBMITTED TO THE BUILDING OFFICIAL: | | | | 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN | | COASTAL HIGH HAZARD AREAS: | | | | 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING | | BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND | | THE FINAL INSPECTION IN SECTION 110.3. | | | | 7. GEOTECHNICAL REPORT BY ALLTERRA PROVIDES TWO | | FOUNDATION ALTERNATIVES. PLANS SPECIFY DEEP FOUNDATION | | ALTERNATIVE SHALL BE USED. PROVIDE CERTIFICATION LETTER | | FROM ALLTERRA UPON COMPLETION OF DEEP FOUNDATION. | | | | 8. PROVIDE SHOP DRAWINGS FOR ELEVATOR. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2017-11-14 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-11-14 |
Time |
13:35 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-11-14 |
Time |
13:35 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2017-09-20 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2017-09-20 |
Time |
15:47 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2017-09-20 |
Time |
15:46 |
Sent To |
|
|
Notes |
2017-09-20 15:47:31 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, | | PART VIII ELECTRICAL | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. RISER DIAGRAM SHOWS 2 PANELS, THERE IS NO PANEL | | INDICATED FOR CABANA, AND I SEE NO CIRCUIT DESIGNATED | | FOR CABANA. BE ADVISED THAT A SEPARATE STRUCTURE IS | | PERMITTED TO BE FED BY ONLY ONE CIRCUIT, WHICH IN THIS | | CASE WOULD TYPICALLY BE A SUB-PANEL. "A BUILDING OR | | OTHER STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR | | FEEDER ON THE LOAD SIDE OF A SERVICE DISCONNECTING | | MEANS SHALL BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH | | CIRCUIT. NEC 225.30". PROVIDE CORRECTION. | | 2. PROVIDE CORRECTED RISER DIAGRAM SHOWING THE | | GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A BUILDING | | OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH CIRCUIT. | | NEC 250.32; FBC RE3607.3 | | 3. IF A SUB-PANEL IS INSTALLED IN CABANA, PROVIDE PANEL | | SCHEDULE FOR THIS PANEL, INDICATING ANY NEW OR ALTERED | | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, | | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY | | WITH CODE. ADDITIONALLY, SHOW LOCATION OF PANEL ON | | PLAN. FBC 107.2.1; NEC 210.8, 210.12, 215.5, 408.4; FBC | | RE3706.2, RE3902 | | 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A | | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE | | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR | | MAIN BREAKER AT THE PANEL FOR CABANA PANEL. NEC 225.31, | | 225.32 | | 5. NO HVAC EQUIPMENT IS SHOWN ON THE ELECTRICAL PLAN | | FOR CABANA. PROVIDE DETAILS ON PLAN, SHOW REQUIRED GFCI | | PROTECTED OUTLET FOR SERVICING THE EQUIPMENT. NEC | | 210.63; FBC RE3901.12; FBC 107.2.1 | | 6. RISER SHOWS PVC SCHEDULE 40 FOR THE CONDUIT | | SUPPLYING THE FPL FEED. THIS CONDUIT IS REQUIRED TO BE | | SCHEDULE 80 PVC, OR ANOTHER APPROVED TYPE. PROVIDE | | CORRECTION. NEC 300.5(D)(4); FBC RE 3802.3.2 | | 7. RISER SHOWS THE GROUNDING ELECTRODE CONDUCTOR SIZED | | AS #4. THE MINIMUM SIZE REQUIRED PER CODE IS 1/0 | | COPPER. PROVIDE CORRECTION. FBC RE TABLE T3603.1 | | 8. PROVIDE ONE ACCURATE LOAD CALCULATION FOR ENTIRE | | SERVICE. IT APPEARS THAT THERE ARE LOAD CALCULATIONS | | FOR THE 2 PANELS, BUT NOT ALL LOADS ARE INCLUDED. | | PROVIDE CORRECTION. NEC 220.82; FBC RE 3602.2 | | 9. INDICATE GFCI PROTECTION FOR ALL OUTSIDE WP OUTLETS | | PER PREVIOUS COMMENT. NOTHING IN THE LEGEND STATES THAT | | A WP RECEPTACLE IS ALSO GFCI PROTECTED. PROVIDE | | CORRECTION. NEC 210.8; FBC RE 3902.3 | | 10. THERE ARE NO OUTLETS SHOWN FOR GARAGE DOOR OPENERS. | | WILL THESE BE INSTALLED? IF SO, SHOW GFCI PROTECTED | | OUTLETS. NEC 210.8; FBC RE 3902.2 | | 11. THERE IS A ROOM ADJACENT TO THE MASTER BATH THAT | | APPEARS TO BE A CLOSET, ALTHOUGH IT IS NOT LABELED ON | | PLAN. IN THIS AREA, A LIGHT IS SHOWN DIRECTLY ABOVE THE | | SHELVING. PROVIDE CORRECTION. ALSO, PROVIDE NOTE THAT | | ALL CLOSET LIGHTING WILL COMPLY WITH NEC 410.16. NEC | | 410.16; FBC RE4003.12 | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-03-22 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2017-03-22 |
Time |
10:11 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2017-03-20 |
Time |
11:41 |
Sent To |
B |
|
Notes |
2017-03-21 08:58:13 | INITIAL PLAN REVIEW ELECTRICAL 3/20/2017 | | | | 2814 N FLAGLER DR | | PERMIT 17030007 | | | | | | CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70 2011 EDITION | | | | | | COMMENTS: | | | | 1) PAGE A-6 SEPARATE STRUCTURE SHALL COMPLY WITH | | 225.30, 225.31, 225.32, E3607.3 FBC RESIDENTIAL | | 2) PAGE E-1 GENERAL OUTLET SPACING TO MEET E-3901.2, | | E3901.2.1 FBC RESIDENTIAL | | 3) GARAGE SHOWS NO OUTLETS E3901.9 FBC RESIDENTIAL | | 4) LOAD NOT SHOWN FOR ELEVATOR | | 5) DRYER LOAD IS 5000W MINIMUM | | 6) NO CIRCUITS SHOWN FOR WASHER AND DRYER | | 7) RISER DIAGRAM SHOS ONLY ONE PANEL | | 8) OUTLETS IN THE OPEN AREA ON GROUND FLOOR SHALL BE | | GFCI PROTECTED | | 9) A SEPARATE PLAN AND PERMIT WILL BE REQUIRED FOR LV | | SYSTEMS IF NOT SHOWN ON PLANS. | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | BN1165, BU1753, PX163 | | 561-805-6713 | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2017-11-20 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2017-11-20 |
Time |
15:08 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-11-08 |
Time |
13:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-10-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-10-06 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-08-29 |
Time |
13:07 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-04-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-04-10 |
Time |
14:09 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-03-01 |
Time |
14:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
P |
Date |
2017-09-26 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-09-26 |
Time |
07:51 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-09-26 |
Time |
07:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2017-04-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-04-10 |
Time |
14:07 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-04-10 |
Time |
10:08 |
Sent To |
|
|
Notes |
2017-04-10 14:08:03 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 1ST REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES | | MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE | | SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM | | BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH | | THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT | | MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE | | THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2017-10-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-10-06 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-10-06 |
Time |
14:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-03-07 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2017-03-07 |
Time |
17:52 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2017-03-07 |
Time |
17:39 |
Sent To |
|
|
Notes |
2017-03-07 17:52:34 | PLAN DENIED | | 1) NEED DUCT SIZE ON 2ND FLOOR RETURN AIR DUCT 107 FBC | | 2014 | | 2) SHOW DRYER EXHAUST ON PLAN. PER SECTION M1502.3 FBC | | 2014 | | 3) PROVIDE TOTAL CFM FOR EACH UNIT ON PLANS. PER 107 | | FBC | | 4) PROVIDE MORE INFORMATION ON RETURN AIR PLENUM'S | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|
|
Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
Rev No |
1 |
Status |
P |
Date |
2017-09-26 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-09-26 |
Time |
14:22 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-09-26 |
Time |
08:51 |
Sent To |
|
|
Notes |
2017-09-26 14:28:47 | PROVISO | | BASE FLOOD ELEVATION FOR ZONE A5 IS 7.0 FEET. REQUIRED | | FREEBOARD IS 12 INCHES. DESIGN FLOOD ELEVATION OF 8.0 | | FEET IS CORRECT. | | SEPERATE ELEVATION CERTIFICATES HAVE BEEN PROVIDED FOR | | MAIN HOUSE AND CABANA. | | | | NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS | | SITE ARE REQUIRED TO BE AT OR ABOVE 8.0 FEET NGVD. | | | | GARAGE FINISHED FLOOR ELEVATION IS SET AT 7.7 FEET. | | FLOOD OPENINGS REQUIRED. PROVIDE COPY OF PRE-ENGINEERED | | FLOOD VENTS AT TIME OF INSPECTION. | | | | AN UNDER CONSTRUCTION ELEVATION CERTIFICATE IS | | RECOMMENDED. | | | | A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS | | REQUIRED FOR BOTH STRUCTURES AND SHALL BE SUBMITTED FOR | | REVIEW AND APPROVAL PRIOR TO THE ISSUANCE OF THE | | CERTIFICATE OF OCCUPANCY. | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2017-09-27 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-09-27 |
Time |
11:40 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-09-27 |
Time |
11:40 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2017-03-16 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-03-16 |
Time |
13:15 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-03-16 |
Time |
11:45 |
Sent To |
|
|
Notes |
2017-03-16 13:14:50 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. ON THE TOP FLOOR IT SHOWS A LAUNDRY ROOM BUT IT DOES | | NOT SHOW A WASHING MACHINE IS THIS CORRECT PLEASE | | CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | 2. PLEASE PROVIDE WATER RISER DIAGRAM . PER WPB AMEND | | TO FBC 107.3.5.3(13) | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
2 |
Status |
P |
Date |
2017-09-26 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-09-26 |
Time |
14:46 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-09-26 |
Time |
07:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
R |
ROOF PLAN REVIEW |
Rev No |
1 |
Status |
F |
Date |
2017-04-10 |
|
|
Cont ID |
|
Sent By |
cthroop |
Date |
2017-04-10 |
Time |
14:08 |
Rev Time |
0.00 |
Received By |
cthroop |
Date |
2017-04-10 |
Time |
10:07 |
Sent To |
|
|
Notes |
2017-04-10 14:09:52 | BUILDING PLAN REVIEW | | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 | | ADMINISTRATION | | | | CHRISTOPHER S. THROOP, C.B.O. | | PLANS EXAMINER, PX3169 | | CONSTRUCTION SERVICES DIVISION | | TEL: 561-805-6726 | | FAX: 561-805-6676 | | | | 1ST REVIEW | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. ROOFING PERMIT REQUIRED. | | 2. PROVIDE PRODUCT APPROVALS FOR ROOF SYSTEM | | COMPONENETS. | | | | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE | | PRODUCTS WHICH ARE REGULATED BY | | FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING | | SUBMITTALS. | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-11-20 |
Time |
|
Rev Time |
0.00 |
Received By |
pgreilic |
Date |
2017-11-20 |
Time |
11:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2017-09-14 |
Time |
|
Rev Time |
0.00 |
Received By |
pgreilic |
Date |
2017-09-13 |
Time |
15:59 |
Sent To |
|
|
Notes |
2017-09-14 09:15:10 | 1.) PROVIDE OVERALL SITE PLAN INDICATING SETBACKS OF | | BOTH PROPOSED STRUCTURES | | | | PAUL GREILICH, SENIOR PLANNER | | 561-822-1443 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2017-03-15 |
|
|
Cont ID |
|
Sent By |
|
Date |
2017-07-13 |
Time |
|
Rev Time |
0.00 |
Received By |
pgreilic |
Date |
2017-07-13 |
Time |
14:48 |
Sent To |
|
|
Notes |
2017-03-15 09:26:15 | MAXIMUM BUILDING HEIGHT: 30 FEET. | | | | HEIGHT OF STRUCTURE MEANS THE VERTICAL DISTANCE FROM | | THE AVERAGE ELEVATION OF THE FINISHED GRADE OF THE | | STRUCTURE TO THE HIGHEST PORTION OF THE STRUCTURE, | | SUBJECT TO SPECIFIED HEIGHT REQUIREMENTS OF THIS | | CHAPTER. FOR BUILDINGS, THE HEIGHT SHALL BE MEASURED AS | | THE VERTICAL DISTANCE FROM THE AVERAGE ELEVATION OF THE | | FINISHED GRADE OF THE BUILDING TO THE HIGHEST POINT OF | | THE TOP OF THE STRUCTURE OF A FLAT ROOF, OR TO THE DECK | | LINE OF A MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL | | BETWEEN EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL | | ROOFS. | | | | THE ELEVATION DRAWINGS NEED TO SHOW THE BUILDING HEIGHT | | MEASURED FROM THE FINISHED GRADE, NOT THE GARAGE FLOOR | | OR THE FINISHED FLOOR. | | | | PAUL GREILICH, SENIOR PLANNER | | 561-822-1443 | | [email protected] |
|
|