Plan Review Details - Permit 17030007
Plan Review Stops For Permit 17030007
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-11-17 Cont ID  
Sent By cthroop Date 2017-11-17 Time 16:52 Rev Time 0.00
Received By cthroop Date 2017-11-15 Time 17:18 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-09-26 Cont ID  
Sent By cthroop Date 2017-09-26 Time 14:59 Rev Time 0.00
Received By cthroop Date 2017-09-26 Time 07:38 Sent To P
Notes
2017-09-26 15:09:29BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVISO ISSUED FOR ELEVATION CERTIFICATE. SEE
 COMMENTS UNDER NFIP REVIEW.
 2. OWNER/AGENT TO SIGN ENERGY SUBMITTALS.
 3. DIGITAL SIGNATURE ON STRUCTURAL PLANS - NOT VALID.
 PROVIDE SIGNATURE AND SEAL OF STRUCTURAL ENGINEER.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF FLORIDA STATUTES
 471.025, AND RULE 61G15-23.001, F.A.C. MAY BE
 PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN
 BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEES SIGNATURE ON EACH PAGE REQUIRED TO BE SEALED.
 A SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEES SIGNATURE SHALL NOT BE USED.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-10 Cont ID  
Sent By cthroop Date 2017-04-10 Time 14:10 Rev Time 0.00
Received By cthroop Date 2017-04-10 Time 09:51 Sent To  
Notes
2017-04-10 14:27:23BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1. SEPERATE PERMIT REQUIRED FOR ACCESSORY STRUCTURE
 (CABANA). STATED VALUE MAY BE PRORATED BETWEEN
 STRUCTURES.
  
 2. THIS REVIEW IS ONLY FOR THE MAIN RESIDENCE. A REVIEW
 OF THE CABANA MAY GENERATE ADDITIONAL COMMENTS.
  
 3. PALM BEACH COUNTY IMPACT FEES REQUIRED.
  
 4. ROOFING PERMIT REQUIRED. PROVIDE PRODUCT APPROVALS
 FOR NEW ROOFING SYSTEM COMPONENTS.
  
 5. THIS PROPERTY LIES IN FLOOD ZONE A5. BASE FLOOD
 ELEVATION IS 7.5 FT. CORRECT FLOOD ZONE NOTE ON SURVEY.
 FBC 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) &
 R322.2.1 ELEVATION REQUIREMENTS. BUILDINGS AND
 STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS
 COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED
 TO 6 INCHES ABOVE THE DESIGN FLOOD ELEVATION. PROVIDE
 FLOOD DESIGN INFORMATION ON THE PROPOSED SURVEY AND
 PROVIDE FLOOD ELEVATION CERTIFICATE.
  
 G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION.
 FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION
 SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO
 THE FOLLOWING:
  
 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY
 WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS
 TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF
 FLOODWATERS.
  
 SECTION R322 FLOOD-RESISTANT CONSTRUCTION
 R322.1 GENERAL.
 BUILDINGS AND STRUCTURES CONSTRUCTED IN WHOLE OR IN
 PART IN FLOOD HAZARD AREAS (INCLUDING A OR V ZONES) AS
 ESTABLISHED IN TABLE R301.2(1) SHALL BE DESIGNED AND
 CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS CONTAINED
 IN THIS SECTION. BUILDINGS AND STRUCTURES LOCATED IN
 WHOLE OR IN PART IN IDENTIFIED FLOODWAYS SHALL BE
 DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ASCE 24.
  
 FBC 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS
 SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE
 ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE
 AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES AND, AS APPLICABLE, FLOOD HAZARD AREAS,
 FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT SHALL BE
 DRAWN IN ACCORDANCE WITH AN ACCURATE BOUNDARY LINE
 SURVEY.
  
 6. ELEVATION CERTIFICATE REQUIRED AT PERMITTING AND
 PRIOR TO C.O.
  
 1612.5 FLOOD HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS:
  
 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING
 BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND
 THE FINAL INSPECTION IN SECTION 110.3.
  
 7. GEOTECHNICAL REPORT BY ALLTERRA PROVIDES TWO
 FOUNDATION ALTERNATIVES. PLANS SPECIFY DEEP FOUNDATION
 ALTERNATIVE SHALL BE USED. PROVIDE CERTIFICATION LETTER
 FROM ALLTERRA UPON COMPLETION OF DEEP FOUNDATION.
  
 8. PROVIDE SHOP DRAWINGS FOR ELEVATOR.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-11-14 Cont ID  
Sent By jleahy Date 2017-11-14 Time 13:35 Rev Time 0.00
Received By jleahy Date 2017-11-14 Time 13:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-09-20 Cont ID  
Sent By jpearson Date 2017-09-20 Time 15:47 Rev Time 0.00
Received By jpearson Date 2017-09-20 Time 15:46 Sent To  
Notes
2017-09-20 15:47:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM SHOWS 2 PANELS, THERE IS NO PANEL
 INDICATED FOR CABANA, AND I SEE NO CIRCUIT DESIGNATED
 FOR CABANA. BE ADVISED THAT A SEPARATE STRUCTURE IS
 PERMITTED TO BE FED BY ONLY ONE CIRCUIT, WHICH IN THIS
 CASE WOULD TYPICALLY BE A SUB-PANEL. "A BUILDING OR
 OTHER STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR
 FEEDER ON THE LOAD SIDE OF A SERVICE DISCONNECTING
 MEANS SHALL BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH
 CIRCUIT. NEC 225.30". PROVIDE CORRECTION.
 2. PROVIDE CORRECTED RISER DIAGRAM SHOWING THE
 GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A BUILDING
 OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH CIRCUIT.
 NEC 250.32; FBC RE3607.3
 3. IF A SUB-PANEL IS INSTALLED IN CABANA, PROVIDE PANEL
 SCHEDULE FOR THIS PANEL, INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. ADDITIONALLY, SHOW LOCATION OF PANEL ON
 PLAN. FBC 107.2.1; NEC 210.8, 210.12, 215.5, 408.4; FBC
 RE3706.2, RE3902
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR CABANA PANEL. NEC 225.31,
 225.32
 5. NO HVAC EQUIPMENT IS SHOWN ON THE ELECTRICAL PLAN
 FOR CABANA. PROVIDE DETAILS ON PLAN, SHOW REQUIRED GFCI
 PROTECTED OUTLET FOR SERVICING THE EQUIPMENT. NEC
 210.63; FBC RE3901.12; FBC 107.2.1
 6. RISER SHOWS PVC SCHEDULE 40 FOR THE CONDUIT
 SUPPLYING THE FPL FEED. THIS CONDUIT IS REQUIRED TO BE
 SCHEDULE 80 PVC, OR ANOTHER APPROVED TYPE. PROVIDE
 CORRECTION. NEC 300.5(D)(4); FBC RE 3802.3.2
 7. RISER SHOWS THE GROUNDING ELECTRODE CONDUCTOR SIZED
 AS #4. THE MINIMUM SIZE REQUIRED PER CODE IS 1/0
 COPPER. PROVIDE CORRECTION. FBC RE TABLE T3603.1
 8. PROVIDE ONE ACCURATE LOAD CALCULATION FOR ENTIRE
 SERVICE. IT APPEARS THAT THERE ARE LOAD CALCULATIONS
 FOR THE 2 PANELS, BUT NOT ALL LOADS ARE INCLUDED.
 PROVIDE CORRECTION. NEC 220.82; FBC RE 3602.2
 9. INDICATE GFCI PROTECTION FOR ALL OUTSIDE WP OUTLETS
 PER PREVIOUS COMMENT. NOTHING IN THE LEGEND STATES THAT
 A WP RECEPTACLE IS ALSO GFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.8; FBC RE 3902.3
 10. THERE ARE NO OUTLETS SHOWN FOR GARAGE DOOR OPENERS.
 WILL THESE BE INSTALLED? IF SO, SHOW GFCI PROTECTED
 OUTLETS. NEC 210.8; FBC RE 3902.2
 11. THERE IS A ROOM ADJACENT TO THE MASTER BATH THAT
 APPEARS TO BE A CLOSET, ALTHOUGH IT IS NOT LABELED ON
 PLAN. IN THIS AREA, A LIGHT IS SHOWN DIRECTLY ABOVE THE
 SHELVING. PROVIDE CORRECTION. ALSO, PROVIDE NOTE THAT
 ALL CLOSET LIGHTING WILL COMPLY WITH NEC 410.16. NEC
 410.16; FBC RE4003.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-22 Cont ID  
Sent By jleahy Date 2017-03-22 Time 10:11 Rev Time 0.00
Received By jleahy Date 2017-03-20 Time 11:41 Sent To B
Notes
2017-03-21 08:58:13INITIAL PLAN REVIEW ELECTRICAL 3/20/2017
  
 2814 N FLAGLER DR
 PERMIT 17030007
  
  
 CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
  
 COMMENTS:
  
 1) PAGE A-6 SEPARATE STRUCTURE SHALL COMPLY WITH
 225.30, 225.31, 225.32, E3607.3 FBC RESIDENTIAL
 2) PAGE E-1 GENERAL OUTLET SPACING TO MEET E-3901.2,
 E3901.2.1 FBC RESIDENTIAL
 3) GARAGE SHOWS NO OUTLETS E3901.9 FBC RESIDENTIAL
 4) LOAD NOT SHOWN FOR ELEVATOR
 5) DRYER LOAD IS 5000W MINIMUM
 6) NO CIRCUITS SHOWN FOR WASHER AND DRYER
 7) RISER DIAGRAM SHOS ONLY ONE PANEL
 8) OUTLETS IN THE OPEN AREA ON GROUND FLOOR SHALL BE
 GFCI PROTECTED
 9) A SEPARATE PLAN AND PERMIT WILL BE REQUIRED FOR LV
 SYSTEMS IF NOT SHOWN ON PLANS.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 BN1165, BU1753, PX163
 561-805-6713
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-11-20 Cont ID  
Sent By lmarchan Date 2017-11-20 Time 15:08 Rev Time 0.00
Received By lmarchan Date 2017-11-08 Time 13:27 Sent To  
Notes
2017-11-09 13:27:27R30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-10-06 Cont ID  
Sent By hmoser Date 2017-10-06 Time 14:28 Rev Time 0.00
Received By hmoser Date 2017-08-29 Time 13:07 Sent To  
Notes
2017-08-30 13:08:04R32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-10 Cont ID  
Sent By cthroop Date 2017-04-10 Time 14:09 Rev Time 0.00
Received By cthroop Date 2017-03-01 Time 14:42 Sent To  
Notes
2017-03-02 14:42:22R31

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-09-26 Cont ID  
Sent By cthroop Date 2017-09-26 Time 07:51 Rev Time 0.00
Received By cthroop Date 2017-09-26 Time 07:38 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-04-10 Cont ID  
Sent By cthroop Date 2017-04-10 Time 14:07 Rev Time 0.00
Received By cthroop Date 2017-04-10 Time 10:08 Sent To  
Notes
2017-04-10 14:08:03BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-10-06 Cont ID  
Sent By hmoser Date 2017-10-06 Time 14:28 Rev Time 0.00
Received By hmoser Date 2017-10-06 Time 14:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-07 Cont ID  
Sent By hmoser Date 2017-03-07 Time 17:52 Rev Time 0.00
Received By hmoser Date 2017-03-07 Time 17:39 Sent To  
Notes
2017-03-07 17:52:34PLAN DENIED
 1) NEED DUCT SIZE ON 2ND FLOOR RETURN AIR DUCT 107 FBC
 2014
 2) SHOW DRYER EXHAUST ON PLAN. PER SECTION M1502.3 FBC
 2014
 3) PROVIDE TOTAL CFM FOR EACH UNIT ON PLANS. PER 107
 FBC
 4) PROVIDE MORE INFORMATION ON RETURN AIR PLENUM'S
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2017-09-26 Cont ID  
Sent By cthroop Date 2017-09-26 Time 14:22 Rev Time 0.00
Received By cthroop Date 2017-09-26 Time 08:51 Sent To  
Notes
2017-09-26 14:28:47PROVISO
 BASE FLOOD ELEVATION FOR ZONE A5 IS 7.0 FEET. REQUIRED
 FREEBOARD IS 12 INCHES. DESIGN FLOOD ELEVATION OF 8.0
 FEET IS CORRECT.
 SEPERATE ELEVATION CERTIFICATES HAVE BEEN PROVIDED FOR
 MAIN HOUSE AND CABANA.
  
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS
 SITE ARE REQUIRED TO BE AT OR ABOVE 8.0 FEET NGVD.
  
 GARAGE FINISHED FLOOR ELEVATION IS SET AT 7.7 FEET.
 FLOOD OPENINGS REQUIRED. PROVIDE COPY OF PRE-ENGINEERED
 FLOOD VENTS AT TIME OF INSPECTION.
  
 AN UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 RECOMMENDED.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED FOR BOTH STRUCTURES AND SHALL BE SUBMITTED FOR
 REVIEW AND APPROVAL PRIOR TO THE ISSUANCE OF THE
 CERTIFICATE OF OCCUPANCY.
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-09-27 Cont ID  
Sent By gjohnson Date 2017-09-27 Time 11:40 Rev Time 0.00
Received By gjohnson Date 2017-09-27 Time 11:40 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-16 Cont ID  
Sent By gjohnson Date 2017-03-16 Time 13:15 Rev Time 0.00
Received By gjohnson Date 2017-03-16 Time 11:45 Sent To  
Notes
2017-03-16 13:14:501ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. ON THE TOP FLOOR IT SHOWS A LAUNDRY ROOM BUT IT DOES
 NOT SHOW A WASHING MACHINE IS THIS CORRECT PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
 2. PLEASE PROVIDE WATER RISER DIAGRAM . PER WPB AMEND
 TO FBC 107.3.5.3(13)
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2017-09-26 Cont ID  
Sent By cthroop Date 2017-09-26 Time 14:46 Rev Time 0.00
Received By cthroop Date 2017-09-26 Time 07:38 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-04-10 Cont ID  
Sent By cthroop Date 2017-04-10 Time 14:08 Rev Time 0.00
Received By cthroop Date 2017-04-10 Time 10:07 Sent To  
Notes
2017-04-10 14:09:52BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
 2. PROVIDE PRODUCT APPROVALS FOR ROOF SYSTEM
 COMPONENETS.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING
 SUBMITTALS.
  

Review Stop Z ZONING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2017-11-20 Time   Rev Time 0.00
Received By pgreilic Date 2017-11-20 Time 11:31 Sent To  
Notes
2017-11-20 11:32:49 
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2017-09-14 Time   Rev Time 0.00
Received By pgreilic Date 2017-09-13 Time 15:59 Sent To  
Notes
2017-09-14 09:15:101.) PROVIDE OVERALL SITE PLAN INDICATING SETBACKS OF
 BOTH PROPOSED STRUCTURES
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2017-03-15 Cont ID  
Sent By   Date 2017-07-13 Time   Rev Time 0.00
Received By pgreilic Date 2017-07-13 Time 14:48 Sent To  
Notes
2017-03-15 09:26:15MAXIMUM BUILDING HEIGHT: 30 FEET.
  
 HEIGHT OF STRUCTURE MEANS THE VERTICAL DISTANCE FROM
 THE AVERAGE ELEVATION OF THE FINISHED GRADE OF THE
 STRUCTURE TO THE HIGHEST PORTION OF THE STRUCTURE,
 SUBJECT TO SPECIFIED HEIGHT REQUIREMENTS OF THIS
 CHAPTER. FOR BUILDINGS, THE HEIGHT SHALL BE MEASURED AS
 THE VERTICAL DISTANCE FROM THE AVERAGE ELEVATION OF THE
 FINISHED GRADE OF THE BUILDING TO THE HIGHEST POINT OF
 THE TOP OF THE STRUCTURE OF A FLAT ROOF, OR TO THE DECK
 LINE OF A MANSARD ROOF, OR TO THE MEAN HEIGHT LEVEL
 BETWEEN EAVES AND RIDGE FOR GABLE, HIP, AND GAMBREL
 ROOFS.
  
 THE ELEVATION DRAWINGS NEED TO SHOW THE BUILDING HEIGHT
 MEASURED FROM THE FINISHED GRADE, NOT THE GARAGE FLOOR
 OR THE FINISHED FLOOR.
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]