Plan Review Details - Permit 17021226
Plan Review Stops For Permit 17021226
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-17 Cont ID  
Sent By tklarge Date 2017-03-17 Time 05:56 Rev Time 0.00
Received By tklarge Date 2017-03-14 Time 10:21 Sent To  
Notes
2017-03-15 10:21:47RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-08 Cont ID  
Sent By tklarge Date 2017-03-08 Time 12:51 Rev Time 0.00
Received By tklarge Date 2017-02-28 Time 10:08 Sent To  
Notes
2017-03-01 10:08:17ROUTED TO PLUMBING INBOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-03-17 Cont ID  
Sent By tklarge Date 2017-03-17 Time 05:56 Rev Time 0.00
Received By tklarge Date 2017-03-17 Time 05:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-08 Cont ID  
Sent By tklarge Date 2017-03-08 Time 12:51 Rev Time 0.00
Received By tklarge Date 2017-03-08 Time 12:41 Sent To  
Notes
2017-03-08 12:51:361) THE DESCRIPTION OF WORK ON THE PERRMIT APPLICATION
 NOTES TWO SEPARATE SYSTEMS: ONE FOR THE GROUND FLOOR
 AND ONEE FOR THE THE 7TH FLOOR. THERE IS ONLY ONE PLAN
 WHICH IS FOR THE POOL TERRACE WHICH APPEARS TO BE
 LOCATED ON THE 7TH FLOOR. CLARIFY. SUBMIT TWO COMPLETE
 SETS OF PLANS FOR BOTH SYSTEMS. WPB AMEND. TO FBC SEC.
 107.1.
 2) IDENTIFY ALL THE PIPING AND HEADS THAT WILL BE
 INSTALLED BY HILITING. WPB AMEND. TO FBC SEC. 107.2.1.
 THE PLANS SHOW SOME AREAS OF HEADS AND PIPING HILITED
 AND SOME AREAS NOT. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  