Plan Review Details - Permit 17021205
Plan Review Stops For Permit 17021205
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-09 Cont ID  
Sent By jgomez Date 2017-03-09 Time 15:20 Rev Time 0.00
Received By jgomez Date 2017-03-09 Time 14:27 Sent To  
Notes
2017-03-09 14:47:00BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PER MEETING WITH FERNANDO GOMES (CONTRACTOR):
 CONTRACTOR WILL COORDINATE PRE-INSPECTION WITH THE
 BUILDING INSPECTOR TO VERIFY ROOF TO WALL CONNECTIONS
 ON ONE CORNER. ACTION ON THE ROOF TO WALL CONNECTIONS
 WILL BE DETERMINED BASED ON THE FINDINGS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-03 Cont ID  
Sent By jgomez Date 2017-03-03 Time 11:15 Rev Time 0.00
Received By jgomez Date 2017-03-03 Time 08:34 Sent To  
Notes
2017-03-03 11:27:20RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE; FBC 5TH EDITION (2014).
  
 1- ACCORDING TO PALM BEACH COUNTY PROPERTY APPRAISER
 THE VALUE OF THE STRUCTURE IS MORE THAN $300.000. NEED
 TO COMPLY WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED
 BY SEC. 708.8 FBC-EXISTING BUILDING, 5TH EDITION
 (2014).
 EXCEPTION: "ROOF-TO-WALL CONNECTIONS SHALL NOT BE
 REQUIRED UNLESS EVALUATION AND INSTALLATION OF
 CONNECTIONS AT GABLE ENDS OR ALL CORNERS CAN BE
 COMPLETED FOR 15 PERCENT OF THE COST OF ROOF
 REPLACEMENT.".
 NOTE: A COMPLETE ITEMIZED EVALUATION AND COST ESTIMATE
 DONE BY QUALIFIED PEOPLE WILL BE REQUIRED WHEN THE
 EXCEPTION OPTION IS TAKEN.
  
 2- RAS 117 CALCULATIONS SUBMITTED:
 A) NAIL SPACING SPECIFIED FOR THE CORNER AREAS NEEDS TO
 BE REVISED. ACCORDING TO CALCULATIONS SUBMITTED THE
 NAIL SPACING FOR TWO ROWS IS 3.64 INCHES. SEC. 8.1 RAS
 117 DOESN'T ALLOW NAIL SPACING LESS THAN 4 INCHES.
 REVISE AS REQUIRED.
  
 B) FASTENER SPACING CONCLUSIONS/RECOMMENDATIONS ON PAGE
 3 OF 3 IS VERY CONFUSING. FASTENER SPACING FOR CORNER
 AREA IS IN THE SAME PARAGRAPH OF THE FASTENER SPACING
 FOR PERIMETER AREA. SAME THING APPLIES TO FASTENER
 SPACING FOR FIELD AREA. CLEARLY PLACE THE FASTENER
 SPACING FOR EACH ROOF ZONE IN THE SAME PARAGRAPH TO
 AVOID CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2017-03-02 Cont ID  
Sent By destabro Date 2017-03-02 Time 08:57 Rev Time 0.00
Received By destabro Date 2017-03-02 Time 08:57 Sent To B
Notes
2017-03-02 08:59:503/2/2017 - FLAT ROOF REPLACEMENT IN-KIND. DLE
2017-03-01 15:51:27ROUTED TO DESIREE ESTABROOK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-09 Cont ID  
Sent By jgomez Date 2017-03-09 Time 15:26 Rev Time 0.00
Received By jgomez Date 2017-03-09 Time 14:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-03 Cont ID  
Sent By jgomez Date 2017-03-03 Time 12:22 Rev Time 0.00
Received By jgomez Date 2017-02-28 Time 14:58 Sent To  
Notes
2017-02-28 14:58:51ROUTED TO HISTORIC VIA ZONING INBOX