Plan Review Details - Permit 17021161
Plan Review Stops For Permit 17021161
Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-04-05 Cont ID  
Sent By ccole Date 2017-04-05 Time 17:26 Rev Time 0.00
Received By ccole Date 2017-04-04 Time 10:18 Sent To  
Notes
2017-04-05 10:19:00RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-17 Cont ID  
Sent By ccole Date 2017-03-17 Time 16:56 Rev Time 0.00
Received By ccole Date 2017-03-15 Time 13:03 Sent To  
Notes
2017-03-16 13:04:08RESUB OF REVISION ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-10 Cont ID  
Sent By ccole Date 2017-03-10 Time 12:11 Rev Time 0.00
Received By ccole Date 2017-03-07 Time 11:41 Sent To  
Notes
2017-03-08 11:42:09REVISION ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-28 Cont ID  
Sent By ccole Date 2017-02-28 Time 12:34 Rev Time 0.00
Received By ccole Date 2017-02-27 Time 09:01 Sent To  
Notes
2017-02-28 09:01:39MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-04-05 Cont ID  
Sent By ccole Date 2017-04-05 Time 17:27 Rev Time 0.00
Received By ccole Date 2017-04-05 Time 17:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-03-17 Cont ID  
Sent By ccole Date 2017-03-17 Time 16:28 Rev Time 0.00
Received By ccole Date 2017-03-17 Time 16:28 Sent To  
Notes
2017-03-17 16:31:133RD REVIEW FBC-2014 MECHANICAL
 PERMIT #17021161
 3/17/17
  
 COMMENTS # 4, 5, 6, & 7 FROM THE 2ND REVIEW STILL
 EXIST. THE COMMENTS ARE PRINTED AGAIN BELOW- PLEASE
 COMPLY.
  
 4) AS PREVIOSUSLY REQUESTED IN THE 1ST REVIEW SUBMIT
 ENERGY CALCULATIONS- SEE SECTION R101.2 AND R101.5,1.1
 FBC-14 ENERGY CONSERVATION
  
 5) AS PREVIOUSLY REQUESTED PROVIDE CONDENSATE DISPOSAL
 PLANS FOR THE AIR HANDLERS- SECTION M1411.3 & M1411.3.1
 FBC-14 RESIDENTIAL.
  
 6) THE NEW 2ND FLOOR AC PLAN APPEARS TO INDICATE AHU-2
 IS IN THE ATTIC. PLEASE REFER TO SECTION R403.2.4 FBC-1
 ENERGY CONSERVATION AND SHOW COMPLIAINCE WITH ITEMS
 #1-4, AND BY SUBMITTING DOCUMENTATION OF
 PERFORMANCE-BASED ENERGY CONSERVATION COMPLIANCE IN
 ACCORDANCE WITH SECTION R405.
  
 7) REFER TO SECTION 607.6.2.1 AND PROVIDE CEILING
 RADIATION DAMPERS FOR THE DUCTS PENETRATING THE
 FIRE-RATED FLOOR/CEILING ASSEMBLY. THE DAMPER SPECS
 SUBMITTED INDICATE THAT THE PRODUCT IS FOR USE IN
 MASONRY OR STUD WALLS, AND CONCRETE FLOORS. THE FLOOR
 ASSEMBLY IS WOOD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-03-10 Cont ID  
Sent By ccole Date 2017-03-10 Time 11:36 Rev Time 0.00
Received By ccole Date 2017-03-10 Time 11:36 Sent To  
Notes
2017-03-10 12:00:112ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17021161
 3/10/17
  
 1) THE PLAN SHEETS FOR THE 1ST AND 2ND FLOOR ARE BOTH
 LABELED M.1. PLEASE LABEL THE 2ND FLOOR PLAN SHEET M.2-
 SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 2) BOTH AC SYSTEMS FOR THE 1ST AND 2ND FLOOR ARE
 DESIGNATED AS SYSTEM #1 IN THE SCHEDULE. PLEASE LABEL
 THE 2ND FLOOR SYSTEM AS SYSTEM #2.
  
 3) PLEASE INDICATE WHICH SETS OF AC CALCULATIONS ARE
 FOR SYSTEM #1 AND FOR AC #2.
  
 4) AS PREVIOSUSLY REQUESTED IN THE 1ST REVIEW SUBMIT
 ENERGY CALCULATIONS- SEE SECTION R101.2 AND R101.5,1.1
 FBC-14 ENERGY CONSERVATION
  
 5) AS PREVIOUSLY REQUESTED PROVIDE CONDENSATE DISPOSAL
 PLANS FOR THE AIR HANDLERS- SECTION M1411.3 & M1411.3.1
 FBC-14 RESIDENTIAL.
  
 6) THE NEW 2ND FLOOR AC PLAN APPEARS TO INDICATE AHU-2
 IS IN THE ATTIC. PLEASE REFER TO SECTION R403.2.4 FBC-1
 ENERGY CONSERVATION AND SHOW COMPLIAINCE WITH ITEMS
 #1-4, AND BY SUBMITTING DOCUMENTATION OF
 PERFORMANCE-BASED ENERGY CONSERVATION COMPLIANCE IN
 ACCORDANCE WITH SECTION R405.
  
 7) REFER TO SECTION 607.6.2.1 AND PROVIDE CEILING
 RADIATION DAMPERS FOR THE DUCTS PENETRATING THE
 FIRE-RATED FLOOR/CEILING ASSEMBLY. THE DAMPER SPECS
 SUBMITTED INDICATE THAT THE PRODUCT IS FOR USE IN
 MASONRY OR STUD WALLS, AND CONCRETE FLOORS. THE FLOOR
 ASSEMBLY IS WOOD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-28 Cont ID  
Sent By ccole Date 2017-02-28 Time 12:34 Rev Time 0.00
Received By ccole Date 2017-02-28 Time 12:34 Sent To  
Notes
2017-02-28 12:56:361ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17021161
 2/28/17
  
 1) PROVIDE COMPLETE AC EQUIPMENT SCHEDULES FOR SYSTEMS
 1 & 2.
  
 2) LABEL SYSTEM THE LOCATION OF SYSTEM #2 ON THE PLANS.
  
 3) PROVIDE AN AC LAYOUT PLAN FOR THE SECOND FLOOR.
  
 4) PROVIDE A RETURN GRILL FOR THE AC SYSTEM IN THE
 BEDROOM 1 CLOSET.
  
 5) THE SUBMITTED AC CALCULATIONS APPEAR TO BE FOR THE
 FIRST FLOOR ONLY. PLEASE PROVIDE CALCULATIONS FOR THE
 SECOND FLOOR- SECTION R403.6.1 FBC-14 ENERGY
 CONSERVATION.
  
 6) FULL COMPLIANCE WITH THE FBC-14 ENERGY CONSERVATION
 CODE IS REQUIRED PER SECTION R101.4.5. PLEASE SUBMIT
 EITHER FORM R402 FOR PRESCRIPTIVE COMPLIANCE OR FORM
 R405 USING APPROVED SOFTWARE SUCH AS ENERGYGAUGE FOR
 PERFORMANCE BASED COMPLIANCE.
  
 7) PROVIDE A CONDENSATE DISPOSAL PLAN FOR EACH AIR
 HANDLER.
  
 8) PROVIDE A DETAIL FOR INSTALLATION OF THE FIRE DAMPER
 AT THE DUCT PENETRATIONS OF THE FLOOR/CEILING
 ASSEMBLIES. PLEASE INCLUDE A DETAIL OF THE ACTUAL
 FLOOR/CEILING ASSEMBLY INCLUDING THE HOURLY
 FIRE-RATING.
  
 9) AN APPLICATION FOR BUSINESS LICENSING MUST BE
 SUBMITTED. PLEASE CONTACT RACHELSKLAREW- LICENSE &
 PERMIT SPECIALIST SUPERVISOR- 561-805-6688.
  
 10) PLEASE NOTE THAT AN INCREASE IN VALUE WILL BE
 REQUIRED FOR THE ENTIRE SCOPE OF WORK FOR THE PROJECT-
 SEE SECTION 109.3 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  