Plan Review Details - Permit 17021070
Plan Review Stops For Permit 17021070
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-02-28 Cont ID  
Sent By vperez Date 2017-02-28 Time 08:05 Rev Time 0.00
Received By vperez Date 2017-02-28 Time 08:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-08 Cont ID  
Sent By ccole Date 2017-03-08 Time 12:46 Rev Time 0.00
Received By ccole Date 2017-03-03 Time 11:31 Sent To  
Notes
2017-03-06 11:32:04RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-02 Cont ID  
Sent By ccole Date 2017-03-02 Time 07:16 Rev Time 0.00
Received By ccole Date 2017-02-24 Time 15:01 Sent To  
Notes
2017-02-27 15:01:37REVISION ROUTED TO VPEREZ

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-08 Cont ID  
Sent By ccole Date 2017-03-08 Time 12:46 Rev Time 0.00
Received By ccole Date 2017-03-08 Time 12:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-02 Cont ID  
Sent By ccole Date 2017-03-02 Time 07:28 Rev Time 0.00
Received By ccole Date 2017-03-01 Time 17:51 Sent To  
Notes
2017-03-02 07:38:301ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17021070
 3/2/17
  
 1) SHEET M-2: THE DIFFUSER TAGS AND CFMS ARE MISSING IN
 THE BREAKROOM AND THE TECH ROOM.
  
 2) M-2: THE ORIGINAL APPROVED PLAN INDICATES 1140 CFMS
 OF SUPPLY AIR PROVIDED TO THE TECH ROOM WHICH WOULD
 INDICATE THE TWO 10X10 TA GRILLES ARE UNDERSIZED- SEE
 SECTION 601.5 (2) AND PROVIDE TRANSFER GRILLS SIZED AT
 50 SQ. INCHES PER 100 CFM OF SUPPLY AIR.
  
 3) PLEASE BIND THE PLANS TOGETHER- SECTION 107.2.1 WPB
 AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  