Plan Review Details - Permit 17021061
Plan Review Stops For Permit 17021061
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-04-17 Cont ID  
Sent By jgomez Date 2017-04-17 Time 14:26 Rev Time 0.00
Received By jgomez Date 2017-04-17 Time 12:49 Sent To  
Notes
2017-04-17 14:26:11BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- PROVIDE HURRICANE SHUTTERS COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-31 Cont ID  
Sent By jgomez Date 2017-03-31 Time 10:35 Rev Time 0.00
Received By jgomez Date 2017-03-30 Time 17:23 Sent To  
Notes
2017-03-31 10:44:09RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) NEW ENTRY DOOR AS SHOWN ON PLANS. PROVIDE THE
 FLORIDA PRODUCT APPROVAL COVER PAGE FOR DRAWINGS
 SUBMITED. IF THERE IS NOT FLORIDA PRODUCT APPROVAL,
 THEN DOOR MANUFACTURER MAY SUBMITT COMPLETE ORIGINAL
 ENGINEERING PACKAGE FOR LOCAL PRODUCT APPROVAL BY
 BUILDING OFFICIAL.
  
 B) NEW SINGLE HUNG WINDOWS AS SHOWN ON PLANS.
  
 C) HURRICANE SHUTTERS IF WINDOWS DON'T HAVE IMPACT
 GLAZING. AND PROVIDE COMPLETE INSTALLATION SCHEDULE.
 SEE CITY SAMPLE.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- PRODUCT APPROVALS INFORMATION SHOWN ON SHEET S-1 AND
 S-3 DON'T MATCH PRODUCT APPROVALS SUBMITTED. ENGINEER
 OF RECORD TO REVISE AS REQUIRED TO MATCH.. SEC. 107.2.1
 CITY AMENDMENTS.
  
 4- ENGINEER OF RECORD TO CLARIFY SCOPE OF WORK NOTE # 2
 ON SHEET D-1. THERE IS NOT BATHROOM #4. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-13 Cont ID  
Sent By jleahy Date 2017-03-13 Time 13:54 Rev Time 0.00
Received By jleahy Date 2017-03-13 Time 11:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-17 Cont ID  
Sent By jgomez Date 2017-04-17 Time 15:17 Rev Time 0.00
Received By jgomez Date 2017-04-10 Time 14:26 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-31 Cont ID  
Sent By jgomez Date 2017-03-31 Time 11:51 Rev Time 0.00
Received By jgomez Date 2017-02-24 Time 14:10 Sent To  
Notes
2017-02-27 14:10:37R12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2017-04-17 Cont ID  
Sent By jgomez Date 2017-04-17 Time 15:00 Rev Time 0.00
Received By jgomez Date 2017-04-17 Time 15:00 Sent To  
Notes
2017-04-17 15:02:08PER CONVERSATION WITH VINCENT LAWSON (CONTRACTOR)
 CORRECT A/C PLAN AND EQUIPMENT SIZING CALCULATIONS TO
 BE SUBMITTED UNDER A SEPARATE.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-31 Cont ID  
Sent By jgomez Date 2017-03-31 Time 11:28 Rev Time 0.00
Received By jgomez Date 2017-03-31 Time 07:54 Sent To  
Notes
2017-03-31 11:41:39RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS (2
 COPIES) ALONG WITH THE MANUFACTURER AND MODEL NUMBER AS
 REQUIRED BY SEC. R403.6 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 2- ENGINEER OF RECORD TO SPECIFY ON THE A/C PLAN THE
 EQUIPMENT MANUFACTURER AND MODEL NUMBER SPECIFIED ON
 THE EQUIPMENT SIZING CALCULATIONS. SEC. 107.3.5.3(10)
 CITY AMENDMENTS.
  
 3- ENGINEER OF RECORD TO SPECIFY THE CFM'S ON THE A/C
 PLAN. SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 4- ENGINEER OF RECORD TO SHOW ON THE A/C PLAN
 COMPLIANCE WITH THE BALANCED RETURN AIR AS REQUIRED BY
 SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-04-17 Cont ID  
Sent By gjohnson Date 2017-04-17 Time 14:42 Rev Time 0.00
Received By gjohnson Date 2017-04-17 Time 14:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-03-14 Cont ID  
Sent By gjohnson Date 2017-03-14 Time 15:24 Rev Time 0.00
Received By gjohnson Date 2017-03-14 Time 15:24 Sent To  
Notes
***NONE***