Plan Review Details - Permit 17021025
Plan Review Stops For Permit 17021025
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-05-16 Cont ID  
Sent By shill Date 2017-05-16 Time 07:28 Rev Time 0.00
Received By shill Date 2017-05-16 Time 07:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-20 Cont ID  
Sent By shill Date 2017-04-20 Time 14:07 Rev Time 0.00
Received By shill Date 2017-04-20 Time 14:07 Sent To  
Notes
2017-04-20 14:07:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. REGARDING THE ALTERNATING STAIRS, THE BUILDING
 OFFICIAL HAS THE FOLLOWING REQUIREMENTS:
  
 THE LETTER DOES NOT INCLUDE A PROJECT NAME, ADDRESS, OR
 PERMIT NUMBER. INCORPORATE THIS INFORMATION INTO THE
 LETTER.
  
 THE LETTER STATES THAT ALL ACCESS IS FROM EXTERIOR.
 REVISE THE PLAN (BOTH PERMIT DRAWINGS AND PLAN INCLUDED
 IN THE LETTER) AT THE RAILING (WHERE IT STATES OPEN TO
 BELOW) TO STATE THAT THERE WILL BE NO ACCESS FROM THE
 STORAGE LOFT TO THE INTERIOR.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-27 Cont ID  
Sent By shill Date 2017-03-27 Time 09:46 Rev Time 0.00
Received By shill Date 2017-03-24 Time 18:26 Sent To  
Notes
2017-03-23 17:57:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. ALS1.1 LIFE SAFETY REQUIREMENTS STATES THAT SF AREA
 IS 2367, BUT IT APPEARS THAT AN ADDITION IS PROPOSED.
 REVISE PLAN TO SHOW EXISTING SF AREA, PROPOSED NEW, NEW
 TOTAL; AREA SUMMARY SHOULD INCLUDE BOTH UNDER AIR AND
 OUTDOOR CALCS SEPARATELY, AREA SUMMARY SHOULD INCLUDE
 MEZZANINE, FBC 107, FBC EB CHAPTER 11.
  
 2. ALS1.1 STATES THIS IS A CHANGE OF OCCUPANCY. OUR
 RECORDS APPEAR TO SHOW THE HISTORY OF THIS STRUCTURE AS
 CONSTRUCTED AS A RESTAURANT WITH CONTINUED USE AS A
 RESTAURANT. EITHER REVISE TO REMOVE CHANGE OF OCCUPANCY
 DESIGNATION, OR CLARIFY BY INCLUDING EXISTING OCCUPANCY
 AND SHOW COMPLIANCE WITH THE REQUIREMENTS OF FBC EB
 CHAPTER 10 AS APPLICABLE.
  
 3. THIS APPEARS TO INCLUDE AN ADDITION; REVISE TO
 INCLUDE THIS INFORMATION, FBC EB CHAPTER 11. AN
 ACCURATE PLAN REVIEW WITH CORRECT CODE REFERENCES
 CANNOT BE DONE AT THIS TIME. THEREFORE, A GENERAL PLAN
 REVIEW WILL BE PERFORMED.
  
 4. PROVIDE A COPY OF THE SURVEY FOR THIS PROPERTY, FBC
 107, FBC B TABLE 602, TABLE 705.8.
  
 5. FBC B 1008.2, 1008.1.10, OCCUPANT LOAD THAT THE GATE
 SERVES IS NOT CLEAR. EXIT STRATEGY NOT CLEAR. IT
 APPEARS THAT TWO EXITS ARE REQUIRED, BUT THE REAR EXIT
 DOOR APPEARS TO ROUTE THE OCCUPANT TO THE FRONT EXIT.
  
 REVISE PLAN TO SHOW THE TWO EXITS REQUIRED, CONTINUOUS
 TO THE PUBLIC WAY. IF THE PLAN IS NOT REVISED TO
 INCLUDE THE PATIO GATE AS HAVING PANIC BARS AND
 UTILIZED AS THE SECOND EXIT, SEND THE PROPOSED LIFE
 SAFETY PLAN VIA EMAIL FOR PRELIMINARY REVIEW.
  
 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109. PROVIDE A COPY OF THE COST BREAKDOWN FOR THIS JOB.
 VALUE IS TO INCLUDE LABOR, MATERIALS, OVERHEAD, PROFIT,
 DESIGN FEES, EVEN IF PROVIDED BY OTHERS. VALUE APPEARS
 TOO LOW.
  
 7. FBC A 220.1.1, IT APPEARS THAT INTENT IS THAT
 VERTICAL ACCESSIBILITY WILL NOT BE PROVIDED TO THE
 MEZZANINE. REVISE PLAN TO CLARIFY UNDER WHICH EXEMPTION
 THIS FALLS. REVISE PLAN TO CLARIFY THAT THE PROPOSED
 SPACE MEETS ALL OF THE REQUIREMENTS OF SELECTED
 EXEMPTION(S).
  
 8. NO EXIT SIGNS ARE SHOWN IN THE PATIO; REVISE TO ADD,
 FBC 1011.1.
  
 9. FBC 1003.6, SOFT SEATING 101 TO PATIO, FBC B 1003.6,
 IT IS NOT CLEAR IF THE FOLDING DOOR COMPLIES WITH THE
 REQUIREMENTS OF CHAPTER 10. FBC B 1004.5, B 1027.1, IT
 APPEARS THAT THE OCCUPANT, AFTER BEING DIRECTED TO THE
 REAR EXIT DOOR, IS FORCED TO REENTER THE BUILDING.
  
 10. FBC B CHAPTER 2, 505, THE PROPOSED MEZZANINE DOES
 NOT APPEAR TO MEET THE DEFINITION OF A MEZZANINE;
 REVISE.
  
 11. FBC 107, ACCESS TO PROPOSED MEZZANINE, REVISE PLAN
 TO INCORPORATE EXCEPTIONS.
  
 12. FBC A 902, 904, REVISE PLAN TO SHOW COMPLIANCE WITH
 DINING SURFACE REQUIREMENTS.
  
 13. PRODUCT APPROVAL REQUIRED FOR COMPONENTS AND
 CLADDING, INCLUDING THE ROOF HATCH, FBC B 1609. THIS
 MAY BE SUBMITTED AS A REVISION AFTER PERMIT ISSUANCE,
 PRIOR TO INSTALLATION. PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL, FBC
 107.
  
 14. ACCESSIBLE ROUTE FROM THE PARKING SPACE TO THE
 ALTERED AREA NOT CLEAR; REVISE PLAN TO CLARIFY, FBC A
 202.3, CHAPTER 4.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-25 Cont ID  
Sent By rlecky Date 2017-04-25 Time 12:30 Rev Time 0.00
Received By rlecky Date 2017-04-25 Time 12:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-09 Cont ID  
Sent By rlecky Date 2017-03-09 Time 13:15 Rev Time 0.00
Received By rlecky Date 2017-03-09 Time 12:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-05-24 Cont ID  
Sent By wjolin Date 2017-05-24 Time 11:58 Rev Time 0.00
Received By wjolin Date 2017-05-24 Time 11:58 Sent To  
Notes
2017-05-24 12:00:22WOOD GRILL NEEDS TO BE FIELD TESTED AND OBTAIN A UL
 LISTING.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-19 Cont ID  
Sent By wjolin Date 2017-04-19 Time 16:44 Rev Time 0.00
Received By wjolin Date 2017-04-19 Time 16:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-09 Cont ID  
Sent By wjolin Date 2017-03-09 Time 14:29 Rev Time 0.00
Received By wjolin Date 2017-03-09 Time 13:59 Sent To  
Notes
2017-03-09 14:29:263815 SOUTH DIXIE HIGHWAY
 PERMIT #17021025
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE UL LISTING (OR EQUAL), APPLIANCE SPECIFICATIONS
 AND INSTALLATION DATA FOR THE SOLID FUEL COOKING
 EQUIPMENT. DATA SHALL INDICATE IF A SUPPRESSION SYSTEM
 IS REQUIRED FOR THIS APPLIANCE.
  
 INDICATE THE LOCATION, FUEL TYPE AND QUANTITY OF SOLID
 FUEL TO BE STORED FOR THE COOKING OPERATIONS.
  
 SOLID COOKING OPERATIONS AND DESIGN SHALL COMPLY WITH
 NFPA 96. FOR EXAMPLE: PER SECTION 14.9.2.1. FUEL
 STORAGE SHALL NOT EXCEED A ONE-DAY SUPPLY WHERE STORAGE
 IS LOCATED IN THE SAME ROOM AS THE SOLID FUELED
 APPLIANCE, OR IN THE SAME ROOMS AS THE FUEL-LOADING OR
 CLEAN-OUT DOORS.
  
 ***SECTION14.9.3.7.3 APPLIANCES WITH FIREBOXES OVER 5
 CUBIC FEET THE WATER SOURCE SHALL BE A FIXED PIPE WATER
 SYSTEM WITH A HOSE OF ADEQUATE LENGTH TO REACH THE
 COMBUSTION AND COOKING CHAMBERS OF THE APPLIANCE.
  
 ALL OVEN ASH SHALL BE REMOVED FROM THE ASH COMPARTMENT
 AT LEAST ONCE PER DAY. THE ASH SHALL BE SPRAYED
 ADEQUATELY WITH WATER BEFORE REMOVAL TO EXTINGUISH ANY
 HOT ASH OR CINDERS AND TO CONTROL THE DUST WHEN THE ASH
 IS MOVED. SECTION 14.9.3.8.1 A HEAVY METAL CONTAINER OR
 CART (MINIMUM 16 GAUGE) WITH A COVER SHALL BE PROVIDED
 FOR THE REMOVAL OF ASH. THE ASH REMOVAL CONTAINER OR
 CART SHALL NOT EXCEED A MAXIMUM OF 20 GAL CAPACITY,
 SHALL BE ASSIGNED FOR THIS ONE PURPOSE, SHALL BE ABLE
 TO BE HANDLED EASILY BY ANY EMPLOYEE ASSIGNED THE TASK,
 AND SHALL PASS EASILY THROUGH ANY PASSAGEWAY TO THE
 OUTSIDE OF THE BUILDING. THE CONTAINER OR CART SHALL
 ALWAYS BE COVERED WHEN IT IS BEING MOVED THROUGH THE
 PREMISES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-05-26 Cont ID  
Sent By tklarge Date 2017-05-26 Time 11:20 Rev Time 0.00
Received By tklarge Date 2017-05-26 Time 11:18 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-05-09 Cont ID  
Sent By tklarge Date 2017-05-09 Time 06:28 Rev Time 0.00
Received By tklarge Date 2017-05-09 Time 04:35 Sent To  
Notes
2017-05-09 06:00:291) THE COMBUSTION AIR CALCULATIONS FOR THE GAS
 APPLIANCES SHALL BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL OF RECORD FOR THE GAS SYSTEM PER THE FL.
 ADMIN. CODE RULES 61G15-23.001 & 61G15-30.003.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT. SINCE THE GAS WILL BE A SEPARATE PERMIT, THE
 SPECIFICATIONS FOR ALL THE GAS EQUIPMENT / APPLIANCES
 CAN BE SUBMITTED AT THE TIME OF THE GAS APPLICATION
 SUBMITTAL. THIS WILL BE NOTED AS A PROVISO ON THE GAS
 PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-03-29 Cont ID  
Sent By tklarge Date 2017-03-29 Time 14:14 Rev Time 0.00
Received By tklarge Date 2017-03-29 Time 14:02 Sent To  
Notes
2017-03-29 14:14:28PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL GAS
 APPLIANCES IN ACCORDANCE WITH THE 2014 FBC-FUEL GAS
 SEC. 304.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-26 Cont ID  
Sent By tklarge Date 2017-05-26 Time 11:18 Rev Time 0.00
Received By tklarge Date 2017-05-12 Time 13:30 Sent To  
Notes
2017-05-15 13:30:56C04

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-09 Cont ID  
Sent By tklarge Date 2017-05-09 Time 06:28 Rev Time 0.00
Received By tklarge Date 2017-04-17 Time 13:29 Sent To  
Notes
2017-04-18 13:29:23C16

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-29 Cont ID  
Sent By tklarge Date 2017-03-29 Time 14:14 Rev Time 0.00
Received By tklarge Date 2017-02-23 Time 16:13 Sent To  
Notes
2017-02-23 16:13:54C14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2017-04-20 Cont ID  
Sent By shill Date 2017-04-20 Time 14:09 Rev Time 0.00
Received By shill Date 2017-04-20 Time 14:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-03-24 Cont ID  
Sent By shill Date 2017-03-24 Time 18:34 Rev Time 0.00
Received By shill Date 2017-03-24 Time 18:31 Sent To  
Notes
2017-03-24 18:35:04IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT SHOWING
 THAT FEES WERE PAID, IF APPLICABLE, IS TO BE PROVIDED.
  
 561-233-5025 FOR MORE INFORMATION
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-05-22 Cont ID  
Sent By ccole Date 2017-05-22 Time 15:59 Rev Time 0.00
Received By ccole Date 2017-05-22 Time 15:59 Sent To  
Notes
2017-05-22 16:10:20MECHANICAL PROVISO:
 5/2/17
  
 THE GRILLWORKS WOOD FIRED GRILL ASSEMBLY SHALL BE FIELD
 TESTED IN ACCORDANCE WITH THE UL 2162 STANDARD.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-04-20 Cont ID  
Sent By ccole Date 2017-04-20 Time 17:45 Rev Time 0.00
Received By ccole Date 2017-04-20 Time 17:44 Sent To  
Notes
2017-05-04 09:49:34MECHANICA PROVISO:
  
 1) THE WOOD-FIRED GRILL SHALL BE LISTED AND LABELED IN
 ACCORDANCE WITH UL 2162.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-01 Cont ID  
Sent By ccole Date 2017-03-01 Time 08:56 Rev Time 0.00
Received By ccole Date 2017-03-01 Time 07:43 Sent To  
Notes
2017-03-01 09:58:391ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17021025
 3/1/17
  
 1) THE PROPOSED PROJECT IS CLASSIFIED AS A RENOVATION
 PER SECTION 202 FBC-14 ENERGY CONSERVATION. REFER TO
 SECTIONS C101.4.3 AND C401.2 AND SUBMIT A COMPLIANCE
 REPORT.
  
 2) PLEASE PLACE A NOTE ON THE PLAN INDICATING SEPARATE
 PERMITS ARE REQUIRED FOR THE HOODS, THE HOOD FIRE
 SUPPRESSION SYSTEMS, AND THE WALK-IN COOLERS AND
 FREEZERS. PLEASE NOTE THAT A FLORIDA PRODUCT APPROVAL
 OR MANUFACTURED BUILDING CERTIFICATION IS REQUIRED FOR
 THE EXTERIOR WALK-IN BOX.
  
 3) SHEET M1.1: PLEASE LABEL THE RTU'S 1, 2, & 3.
  
 4) M1.1: IT APPEARS THAT THE AMOUNT OF CFMS BEING
 SUPPLIED ON THE PLAN BY RTU-1 (4110 CFMS) MAY BE
 EXCEEDING THE UNIT'S DESIGN AIRFLOW SHOWN IN THE
 SCHEDULE. THIS IS ALSO TRUE OF RTU-3 AT 3900 CFMS
  
 5) MR1.1: PLEASE VERIFY THAT NO MECHANICAL EQUIPMENT
 REQUIRING SERVICING IS WITHIN 10' OF THE ROOF EDGE
 UNLESS THE PARAPET WALL AT THAT LOCATION IS MINIMUM 42"
 HIGH. OTHERWISE A GUARDRAIL WILL BE REQUIRED- SECTION
 304.11.
  
 6) INDICATE HOW ACCESS TO THE EQUIPMENT ON THE ROOF IS
 BEING PROVIDED- SEE SECTION 306.5.
  
 7) THE OUTDOOR AIR SUPPLY FOR THE RTU'S MUST BE
 EQUIPPED WITH DAMPERS THAT WILL AUTOMATICALLY SHUT WHEN
 THE SYSTEMS OR SPACES ARE NOT IN USE- SECTION
 C403.2.4.4 FBC-14 ENERGY CONSERVATION.
  
 8) DEMAND CONTROLLED VENTILATION IS REQUIRED IN THE
 DINING ROOM PER SECTION C403.2.5.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-05-26 Cont ID  
Sent By tklarge Date 2017-05-26 Time 11:17 Rev Time 0.00
Received By tklarge Date 2017-05-26 Time 05:57 Sent To  
Notes
2017-05-26 11:18:04SEPARATE PERMIT REQD. FOR BACKFLOW PREVENTER.TKL.

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-05-09 Cont ID  
Sent By tklarge Date 2017-05-09 Time 05:41 Rev Time 0.00
Received By tklarge Date 2017-05-09 Time 03:49 Sent To  
Notes
2017-05-09 04:53:041) AS A NOTE OF INFORMATION, A SEPARATE PERMIT WILL BE
 REQUIRED FOR THE NEW BACKFLOW PREVENTER LOCATED AT THE
 NEW WATER METER. THE DEVICE SHALL BE LEAD- FREE AND
 COMPLY WITH THE CITY OF WPB CROSS-CONNECTION CONTROL
 MANUAL AND MUST ALSO BE ON THE UNIVERSITY OF SOUTHERN
 CALIFORNIA'S (USC) LIST OF APPROVED DEVICES. TWO COPIES
 OF THE MANUFACTURER'S SPECIFICATIONS SHALL BE SUBMITTED
 AT THE TIME OF PERMIT APPLICATION. 2014 FBC-PLUMBING
 SEC.605.2.1. THE CITY OF WPB CROSS-CONNECTION MANUAL
 CAN BE VIEWED AT HTTP://WPB.ORG/UTILITIES/BACKFLOW.
 2) SHT. A 8.02 - DETAIL #3 - THE SIDE WALL GRAB BAR
 NEXT TO THE WATER CLOSET SHALL BE LOCATED PER 2014
 FBC-ACCESS.SEC. 604.5.1 & FIGURE 604.5.1. THE GRAB BAR
 SHALL EXTEND A MINIMUM OF 54 INCHES FROM THE REAR
 WALL.THE DETAIL SHOWS THE GRAB BAR 10 1/2 INCHES FROM
 THE REAR WALL WHICH WILL PRODUCE 52 1/2 INCHES FROM THE
 REAR WALL USING A 42 INCH BAR AND A MINIMUM OF 54
 INCHES IS REQUIRED. 2ND REQUEST.
 3) SHT. A 8.02 - DETAILS #3 & #4 - THE TOILET PAPER
 DISPENSER SHALL BE LOCATED 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM TO THE CENTER OF THE FIRST TOILET PAPER
 ROLL, NOT TO THE CENTER OF THE DOUBLE ROLL DISPENSER AS
 SHOWN ON THE PLANS.FBC-ACCESS SEC.604.7. 2ND REQUEST.
 4) THE DETAIL OF THE HOT WATER RECIRCULATING SYSTEM ON
 DETAIL #1 ON SHT.P0.1 DOES NOT APPEAR TO COMPLY WITH
 2014 FBC-PLUMBING SEC.607.2.2. I DO NOT SEE A HOT WATER
 RETURN LINE COMING FROM THE FIXTURES BACK TO THE WATER
 HEATERS. PLEASE REFER TO THE FOLLOWING TEXT FROM THE
 PLUMBING CODE:
 607.2.2 RECIRCULATING PUMP.
 WHERE A THERMOSTATIC MIXING VALVE IS USED IN A SYSTEM
 WITH A HOT WATER RECIRCULATING PUMP, THE HOT WATER OR
 TEMPERED WATER RETURN LINE SHALL BE ROUTED TO THE COLD
 WATER INLET PIPE OF THE WATER HEATER AND THE COLD WATER
 INLET PIPE OR THE HOT WATER RETURN CONNECTION OF THE
 THERMOSTATIC MIXING VALVE.
 5) THE DESIGN OF THE GREASE INTERCEPTOR SHALL COMPLY
 WITH THE CITY OF WEST PALM BEACH STANDARD DRAWING GS-7
 FOR CONCRETE TANKS AND DRAWING GS-7.1 FOR
 HYDR-MECHANICAL TANKS. I HAVE INCLUDED COPIES OF THESE
 STANDARD DRAWINGS IN THE PERMIT APPLICATION SUBMITTAL
 PACKAGE FOR YOUR PERUSAL. AS A NOTE OF INFORMATION, THE
 INTERCEPTOR SHALL BE PERMITTED UNDER A SEPARATE PERMIT.
 ENSURE THE SIZE AND LOCATION OF THE FLOW THROUGH HOLE
 IN THE BAFFLE COMPLIES WITH THE CITY'S STANDARD
 DRAWING.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-29 Cont ID  
Sent By tklarge Date 2017-03-29 Time 14:02 Rev Time 0.00
Received By tklarge Date 2017-03-27 Time 11:11 Sent To  
Notes
2017-03-29 13:45:051) SHT. ALS.1.1 - WHAT TABLE AND WHAT CODE ARE YOU
 DERIVING YOUR SANITARY FIXTURE REQUIREMENTS FROM? TABLE
 403.1 IN THE 2014 FBC-PLUMBING REQUIRES ONE WATER
 CLOSET FOR EVERY 75 MALES AND ONE WATER CLOSET FOR
 EVERY 75 FEMALES, NOT ONE PER 500. THERE IS ALSO AN
 ISSUE WITH THE TABLE ON THE PLANS FOR THE LAVATORIES.
 THE RATIO IS ONE LAVATORY FOR EVERY 200 MALES AND ONE
 LAVATORY FOR EVERY 200 FEMALES. ALSO, THE SPLIT HAS TO
 BE EQUAL, NOT 48 & 49. THE CORRECT NUMBER OF FIXTURES
 HAVE BEEN SUPPLIED BUT CORRECT THE TABLE.WPB AMEND. TO
 FBC SEC. 107.2.1, FBC-PLUMBING SEC. 403.1.
 2) SHT. ALS.1.1 - THE DOORS IN THE TOILET ROOMS SWING
 INTO THE REQUIRED CLEAR FLOOR SPACE FOR THE LAVATORIES
 WHICH IS PROHIBITED BY 2014 FBC-ACCESS SEC.603.2.3. SEE
 EXCEPTION #2 AND SHOW COMPLIANCE ON THE PLAN.
 3) SHT. A2.01 SHOWS GUTTERS. PROVIDE THE GUTTER SIZES
 AND THE SQUARE FOOT AREA DRAINED BY EACH GUTTER.
 GUTTERS AND DOWNSPOUTS SHALL BE SIZED PER 2014
 FBC-PLUMBING TABLE 1106.6.
 4) SUBMIT A STORM DRAINAGE RISER FOR REVIEW. THE
 RAINFALL RATE SHALL BE BASED ON A 5 INCH PER HOUR
 RAINFALL, NOT 4.5 INCHES.
 5) SHT. A8.02 - DETAIL #2 & #5 - THE MINIMUM VERTICAL
 DISTANCE FOR KNEE CLEARANCE UNDER AN ELEMENT SHALL BE
 27 INCHES PER 2014 FBC-ACCESSIBILITY SEC.306.3.1.
 6) SHT. A8.02 - DETAIL #2 - THE GRAB BAR BEHIND THE
 WATER CLOSET SHALL BE LOCATED PER 2014
 FBC-ACCESSIBILITY SEC.604.5.2 & FIG. 604.5.2.
 7) SHT. A8.02 - DETAIL #3 - THE SIDE WALL GRAB BAR NEXT
 TO THE WATER CLOSET SHALL BE LOCATED PER 2014
 FBC-ACCESS. SEC.604.5.1 & FIG. 604.5.1.
 8) SHT. A8.02 - DETAILS #3 & #4 - THE TOILET PAPER
 DISPENSER SHALL BE LOCATED 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM TO THE CENTERLINE OF THE FIRST TOILET
 PAPER DISPENSER. 2014 FBC-ACCESS SEC.604.7.
 9) SHT. A8.02 - THE HEIGHT OF THE TOILET PAPER
 DISPENSER IS SHOWN AT 1'-7" MAXIMUM AND 2'-0" MINIMUM.
 THIS IS OBVIOUSLY A TYPO ERROR. PLEASE CORRECT.
 10) SUBMIT A CLEAR DETAIL FOR THE HOT WATER
 RECIRCULATING SYSTEM. COMPLY WITH 2014 FBC-PLUMBING
 SEC.607.2.2.
 11) SHT. P0.2 - DETAIL #4 - THE GENERAL NOTES ON THE
 DETAIL REFER TO THE UNIFORM PLUMBING CODE. THE CODE IN
 EFFECT IS THE 2014 FLORIDA BUILDING CODE-PLUMBING.
 PLEASE REVISE THE NOTE.
 12) SHT. P0.2 - DETAIL #1 - PROVIDE INFORMATION AS TO
 HOW THE CONDENSATE STANDS WILL BE ANCHORED TO THE ROOF
 MEMBRANE. WPB AMEND. TO FBC SEC. 107.2.1.
 13) SHT. P0.2 - THE GENERAL NOTES STATE THAT THE GREASE
 INTERCEPTOR IS 1250 GALLON CAPACITY AND THERE IS A NOTE
 IN THE UPPER LEFT CORNER OF THE DETAIL STATING THE IT
 IS 750 GALON. CLARIFY.
 14) SHT. P1.1 - THE GREASE TRAP SIZING FORMULA NOTES 40
 SEATS BUT SHT A1.14 SHOWS MORE THAN 40 SEATS. THE BAR
 AREA SEATS, PATIO AREA AND BANQUET AREAS MUST BE
 INCLUDED IN THE CALCULATIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2017-08-15 Cont ID  
Sent By shill Date 2017-08-15 Time 09:13 Rev Time 0.00
Received By shill Date 2017-08-15 Time 09:13 Sent To  
Notes
2017-08-15 09:43:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PRODUCT APPROVALS NOT SUBMITTED. PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD REQUIRED TO BE
 SUBMITTED. INDICATE WHICH ASSEMBLY IS PROPOSED AND
 PROVIDE ENGINEERING IF REQUIRED.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-04-28 Cont ID  
Sent By ajones Date 2017-04-28 Time 16:33 Rev Time 0.00
Received By ajones Date 2017-04-27 Time 10:32 Sent To  
Notes
2017-04-28 16:36:114/28/17- PASSED WITH THE PROVISO THAT ALL EXISTING
 COLUMNS ALONG THE FRONT OF THE BUILDING ALONG DIXIE
 MUST REMAIN.
  
 ANGELLA VANN, AICP
 PLANNING AND ZONING ADMINISTRATOR
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2017-03-23 Cont ID  
Sent By ajones Date 2017-03-23 Time 15:38 Rev Time 0.00
Received By ajones Date 2017-03-23 Time 15:38 Sent To  
Notes
2017-03-23 15:46:133/23/17- FAILED FOR THE FOLLOWING REASONS:
  
 1. A SURVEY OF THE SITE NEEDS TO BE PROVIDED.
 2. IT APPEARS THAT ADDITIONAL SQUARE FOOTAGE IS BEING
 ADDED TO THE BUILDING. IF SO, 2 ADDITIONAL PARKING
 SPACES NEED TO BE PROVIDED.
 3. IN PRELEMINARY DISCUSSIONS WITH THE APPLICANT IT WAS
 STATED THAT ALL EXISTING WALLS OF THE BUILDING HAD TO
 REMAIN. IT APPEARS THAT ONLY CERTAIN SECTIONS OF THE
 NORTH, WEST AND SOUTH WALLS ARE REMAINING. THEREFORE,
 THE PROJECT HAS TO COMPLY WITH THE CURRENT PARKING
 SPACE REQUIREMENTS.
  
 ANGELLA VANN
 561-8221441
 [email protected]
  
  