Plan Review Details - Permit 17020950
Plan Review Stops For Permit 17020950
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-01-04 Cont ID  
Sent By cthroop Date 2018-01-04 Time 09:57 Rev Time 0.00
Received By cthroop Date 2018-01-03 Time 15:37 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-10-24 Cont ID  
Sent By cthroop Date 2017-10-24 Time 16:55 Rev Time 0.00
Received By cthroop Date 2017-10-24 Time 13:19 Sent To  
Notes
2017-10-24 16:59:09BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROPERTY IS LOCATED IN A FLOOD ZONE. ELEVATION
 CERTIFICATE REQUIRED.
 2. THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS
 SITE IS A5 WITH A BASE FLOOD ELEVATION (BFE) OF 7FT.
 THE CITY OF WEST PALM BEACH (THROUGH ORDINANCE)
 REQUIRES AN ADDITIONAL 12 INCHES OF FREEBOARD REQUIRING
 THE DESIGN FLOOD ELEVATION (DFE) TO BE 8. 0 FEET.
 PLEASE NOTE THIS INFORMATION ON YOUR PLANS.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-01-22 Cont ID  
Sent By jpearson Date 2018-01-22 Time 10:00 Rev Time 0.00
Received By jpearson Date 2018-01-22 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-12-11 Cont ID  
Sent By jpearson Date 2017-12-11 Time 09:14 Rev Time 0.00
Received By jpearson Date 2017-12-11 Time 08:47 Sent To  
Notes
2017-12-11 09:14:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 2ND ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS
 BELOW.
  
 COMMENTS CORRECTED HAVE BEEN NOTED, REMAINING COMMENTS
 ARE NOT ADDRESSED SATISFACTORILY. SEE ADDITIONAL
 COMMENTARY IN PARENTHESES.
  
 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL, INDICATING
 THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI
 OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH
 CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE3706.2,
 RE3902 (THERE IS NO PANEL SCHEDULE FOR THE FUTURE
 PANEL. ANY FUTURE PANEL WOULD LIKELY OVERLOAD THE
 SERVICE, SINCE THE PROVIDED LOAD CALCULATION IS AT 182
 AMPS ON A 200 AMP SERVICE. PROVIDE PANEL SCHEDULE WITH
 LOAD, OR REMOVE FROM PLAN. NEC 220; FBC 107.2.1)
 2. CORRECTED.
 3. RISER DIAGRAM SHOWS TWO 100 AMP SUB-PANELS, BUT ONLY
 ONE IS SHOWN ON POWER PLAN. PROVIDE LOCATION OF ALL
 SUB-PANELS. FBC 107.2.1 (PLAN NOW SHOWS AN ATS ADJACENT
 TO METER AND A 200 AMP PANEL INSIDE THE GARAGE, BUT
 THIS PANEL IS NOT LABELED. IS THE ATS ALSO A PANEL, OR
 JUST AN ATS WITH MAIN BREAKER AS SHOWN? WHERE IS PANEL
 A AND PANEL B? RISER SHOWS ITEMS BEING FED FROM PANEL B
 THAT ARE LOCATED IN THE PANEL SCHEDULE FOR PANEL A.
 PLAN IS REQUIRED TO BE ACCURATE. PROVIDE CORRECTIONS.
 FBC 107.2.1)
 4. CORRECTED.
 5. CORRECTED.
 6.CORRECTED.
 7.CORRECTED.
 8. CORRECTED.
 9. CORRECTED.
 10. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC
 107.2.1, FS 471, 481 (A LETTER STATING THAT SOMEONE
 DESIGNED THE PLAN IS NOT SUFFICIENT. THE PLAN MUST BE
 SIGNED BY THE PERSON RESPONSIBLE FOR THE DESIGN, WITH
 THAT PERSON'S INFORMATION SHOWN ON PLAN.)
 11. NEW COMMENT: RISER SHOWS THE FEED TO PANEL B AS TWO
 2/0 AND ONE 1/0 COPPER WIRE. THIS CONDUIT REQUIRES AN
 EQUIPMENT GROUNDING CONDUCTOR. PROVIDE CORRECTIONS. NEC
 310.15, 250.120, 122
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-10-05 Cont ID  
Sent By jpearson Date 2017-10-05 Time 13:02 Rev Time 0.00
Received By jpearson Date 2017-10-05 Time 13:02 Sent To  
Notes
2017-10-05 13:02:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE PANEL SCHEDULE FOR EACH PANEL, INDICATING
 THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, AND AFCI
 OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY WITH
 CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC RE3706.2,
 RE3902
 2. RISER DIAGRAM SHOWS TWO 100 AMP SUB-PANELS FED WITH
 #8 WIRE. #8 WIRE IS NOT RATED FOR 100 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16); FBC RE TABLE E3705.1
 3. RISER DIAGRAM SHOWS TWO 100 AMP SUB-PANELS, BUT ONLY
 ONE IS SHOWN ON POWER PLAN. PROVIDE LOCATION OF ALL
 SUB-PANELS. FBC 107.2.1
 4. GARAGE DOOR OPENER OUTLET REQUIRES GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE3902.2
 5. PLAN SHOWS 2 DISHWASHERS, BUT I ONLY SEE ONE
 INCLUDED IN THE LOAD CALCULATION. PROVIDE ACCURATE LOAD
 CALCULATION. NEC 220; FBC RE3902.3
 6. KITCHEN ISLAND RECEPTACLES REQUIRE GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8; FBC RE 3902.6
 7. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC R315.1
 8. LIGHTING IN CLOSETS IS SHOWN AS STANDARD RECESS
 LIGHTS. PER CODE: "LIGHTING WITH OPEN OR PARTIALLY
 ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS
 SHALL NOT BE PERMITTED IN CLOTHES CLOSETS". PROVIDE
 CORRECTION. ALSO, CORRECT NOTE THAT STATES LIGHTING IN
 CLOSETS TO COMPLY WITH SECTION 4108, THIS SECTION DOES
 NOT EXIST IN THE NEC . NEC 410.16; FBC RE4003.12; FBC
 107.2.1
 9. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC CE R404.1
 10. PER THE WPB AMENDMENTS TO THE FBC, PLAN IS REQUIRED
 TO BEAR THE NAME AND BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FBC
 107.2.1, FS 471, 481
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2018-01-05 Cont ID  
Sent By tklarge Date 2018-01-05 Time 04:32 Rev Time 0.00
Received By tklarge Date 2018-01-05 Time 04:32 Sent To  
Notes
2018-01-05 04:32:34A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A GAS PERMIT IS REQUIRED FOR A CONTRACTOR TO
 PERFORM THE RELATED WORK. PROVIDE COMPLETE PLANS THAT
 REFLECT THE ENTIRE SCOPE OF GAS WORK TO BE DONE. WPB
 AMEND. TO FBC SEC.107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2017-10-11 Cont ID  
Sent By gjohnson Date 2017-10-11 Time 07:16 Rev Time 0.00
Received By gjohnson Date 2017-10-11 Time 07:16 Sent To  
Notes
2017-10-11 07:17:34GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-01-22 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-18 Time 13:38 Sent To  
Notes
2018-01-19 13:38:15RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-01-05 Cont ID  
Sent By tklarge Date 2018-01-05 Time 04:32 Rev Time 0.00
Received By tklarge Date 2017-12-07 Time 10:18 Sent To I
Notes
2017-12-08 10:19:09R11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-11-02 Cont ID  
Sent By hmoser Date 2017-11-02 Time 14:25 Rev Time 0.00
Received By hmoser Date 2017-09-29 Time 13:49 Sent To  
Notes
2017-10-02 13:49:44R26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-01-04 Cont ID  
Sent By cthroop Date 2018-01-04 Time 08:04 Rev Time 0.00
Received By cthroop Date 2018-01-03 Time 15:37 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-10-24 Cont ID  
Sent By cthroop Date 2017-10-24 Time 13:20 Rev Time 0.00
Received By cthroop Date 2017-10-24 Time 13:20 Sent To  
Notes
2017-10-24 13:21:14BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES, REQUIRED BY PALM BEACH COUNTY, SHALL BE PAID.
 UPON FINAL APPROVAL OF PLANS, ONE SET OF PLANS SHALL BE
 SIGNED OUT AND SUBMITTED TO PALM BEACH COUNTY FOR AN
 IMPACT FEE REVIEW. THE PLANS WITH THE IMPACT FEE STAMP
 AND A COPY OF THE PAID RECEIPT MUST BE RETURNED TO THE
 CITY BUILDING DEPARTMENT BEFORE THE BUILDING PERMIT CAN
 BE ISSUED. FOR INFORMATION CALL PALM BEACH COUNTY
 IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-12-20 Cont ID  
Sent By hmoser Date 2017-12-20 Time 13:47 Rev Time 0.00
Received By hmoser Date 2017-12-19 Time 10:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-11-02 Cont ID  
Sent By hmoser Date 2017-11-02 Time 14:24 Rev Time 0.00
Received By hmoser Date 2017-11-02 Time 13:04 Sent To  
Notes
2017-11-02 14:24:40PLAN DENIED
 PROVIDE DUCT SIZE ON A/C # 2 TWO SUPPLY LINES COMING
 OFF SUPPLY PLENUM.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2018-01-04 Cont ID  
Sent By cthroop Date 2018-01-04 Time 09:56 Rev Time 0.00
Received By cthroop Date 2018-01-03 Time 15:37 Sent To  
Notes
2018-01-04 09:56:58PROPERLY COMPLETED EC REQUIRED PRIOR TO CO

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2017-10-24 Cont ID  
Sent By cthroop Date 2017-10-24 Time 16:59 Rev Time 0.00
Received By cthroop Date 2017-10-24 Time 16:51 Sent To  
Notes
2017-10-24 17:03:36BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). THE SPECIFIC ZONE DESIGNATION FOR THIS SITE IS
 A5 WITH A BASE FLOOD ELEVATION (BFE) OF 7FT. THE CITY
 OF WEST PALM BEACH (THROUGH ORDINANCE) REQUIRES AN
 ADDITIONAL 12 INCHES OF FREEBOARD REQUIRING THE DESIGN
 FLOOD ELEVATION (DFE) TO BE 8. 0 FEET. PLEASE NOTE THIS
 INFORMATION ON YOUR PLANS.
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ON THIS
 SITE ARE REQUIRED TO BE AT OR ABOVE 8.0 FEET NGVD.
  
 AN UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 RECOMMENDED.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
  
 1612.1 GENERAL.
 WITHIN FLOOD HAZARD AREAS AS ESTABLISHED IN SECTION
 1612.3, ALL NEW CONSTRUCTION OF BUILDINGS, STRUCTURES
 AND PORTIONS OF BUILDINGS AND STRUCTURES, INCLUDING
 SUBSTANTIAL IMPROVEMENT AND RESTORATION OF SUBSTANTIAL
 DAMAGE TO BUILDINGS AND STRUCTURES, SHALL BE DESIGNED
 AND CONSTRUCTED TO RESIST THE EFFECTS OF FLOOD HAZARDS
 AND FLOOD LOADS. FOR BUILDINGS THAT ARE LOCATED IN MORE
 THAN ONE FLOOD HAZARD AREA, THE PROVISIONS ASSOCIATED
 WITH THE MOST RESTRICTIVE FLOOD HAZARD AREA SHALL
 APPLY.
  
 1612.4 DESIGN AND CONSTRUCTION.
 THE DESIGN AND CONSTRUCTION OF BUILDINGS AND STRUCTURES
 LOCATED IN FLOOD HAZARD AREAS, INCLUDING COASTAL HIGH
 HAZARD AREAS, SHALL BE IN ACCORDANCE WITH CHAPTER 5 OF
 ASCE 7 AND WITH ASCE 24.
  
 FBC 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY) &
 R322.2.1 ELEVATION REQUIREMENTS. BUILDINGS AND
 STRUCTURES IN FLOOD HAZARD AREAS NOT DESIGNATED AS
 COASTAL A ZONES SHALL HAVE THE LOWEST FLOORS ELEVATED
 TO OR ABOVE THE DESIGN FLOOD ELEVATION. PROVIDE FLOOD
 DESIGN INFORMATION ON THE PROPOSED SURVEY AND PROVIDE
 FLOOD ELEVATION CERTIFICATE.
  
 G1001.4 ENCLOSURES BELOW DESIGN FLOOD ELEVATION.
 FULLY ENCLOSED AREAS BELOW THE DESIGN FLOOD ELEVATION
 SHALL BE AT OR ABOVE GRADE ON ALL SIDES AND CONFORM TO
 THE FOLLOWING:
  
 1. IN FLOOD HAZARD AREAS NOT SUBJECT TO HIGH-VELOCITY
 WAVE ACTION, ENCLOSED AREAS SHALL HAVE FLOOD OPENINGS
 TO ALLOW FOR THE AUTOMATIC INFLOW AND OUTFLOW OF
 FLOODWATERS.
  
  
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-01-22 Cont ID  
Sent By tklarge Date 2018-01-22 Time 10:02 Rev Time 0.00
Received By tklarge Date 2018-01-22 Time 08:39 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-01-05 Cont ID  
Sent By tklarge Date 2018-01-05 Time 04:29 Rev Time 0.00
Received By tklarge Date 2017-12-29 Time 10:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-12-29 Cont ID  
Sent By gjohnson Date 2017-10-11 Time 07:11 Rev Time 0.00
Received By tklarge Date 2017-10-11 Time 07:01 Sent To  
Notes
2017-10-11 07:16:011ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. THE LAUNDRY SINK AND WASHING MACHINE SHALL CONNECT
 TO THE BUILDING DRAIN DOWN STREAM OF THE BATHROOM
 GROUP. PER FBC RES P3108.1
  
 2. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK. PER FBC RES P3005.2.6
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2017-10-24 Cont ID  
Sent By cthroop Date 2017-10-24 Time 16:01 Rev Time 0.00
Received By cthroop Date 2017-10-24 Time 13:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2017-12-22 Time   Rev Time 0.00
Received By pgreilic Date 2017-12-21 Time 15:19 Sent To  
Notes
2017-12-22 12:19:28LANDSCAPE PERMIT REQUIRED
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By PG Date 2017-11-01 Time   Rev Time 0.00
Received By pgreilic Date 2017-11-01 Time 14:27 Sent To  
Notes
2017-11-01 14:34:021.) LANDSCAPE PERMIT REQUIRED
 2.) LABEL OVERAL HEIGHT OF PROPOSED RESIDENCE
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]