Plan Review Details - Permit 17020912
Plan Review Stops For Permit 17020912
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-04-19 Cont ID  
Sent By shill Date 2017-04-19 Time 17:55 Rev Time 0.00
Received By shill Date 2017-04-19 Time 17:55 Sent To  
Notes
2017-04-19 17:56:08PROVISO - TAS105 REQUIRED FOR GYPSUM INSULATED DECK
 PRIOR TO INSPECTION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-30 Cont ID  
Sent By shill Date 2017-03-30 Time 07:46 Rev Time 0.00
Received By shill Date 2017-03-30 Time 07:46 Sent To  
Notes
2017-03-30 07:46:55****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, DESIGNER OF RECORD IS TO REVIEW PRODUCT
 APPROVALS AND DELEGATED ENGINEERING PRIOR TO SUBMITTAL.
  
 2ND REVIEW, NOT ADDRESSED. THE DESIGNER OF RECORD IS TO
 REVIEW THE PRODUCT APPROVALS, EITHER WITH A SHOP
 DRAWING REVIEW STAMP OR A LETTER. A REFERENCE TO A TYPE
 OF PRODUCT ON THE PLAN, UNLESS IT SPECIFICALLY
 REFERENCES THE MANUFACTURER AND PRODUCT, DOES NOT
 DEMONSTRATE THAT DOR HAS REVIEWED THE SPECIFIC PRODUCT
 AND METHOD OF INSTALLATION PROPOSED.
  
 2.OK
  
 3. FBC 107, WHEN RESUBMITTING APPLICANT IS TO PREPARE
 TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS FOR
 PERMIT ISSUANCE.
  
 OLD SHEETS ARE TO BE RETAINED IN THE SUBMITTAL, REMOVED
 FROM THE TWO PERMIT ISSUE SETS, AND THOSE DOCUMENTS
 SHOULD BE MARKED "VOID" OR "OLD SHEETS".
  
 THE TWO COLLATED PERMIT SETS ARE TO INCLUDE ANY
 DOCUMENTS PREVIOUSLY SUBMITTED AND REVIEWED AS WELL AS
 THE NEW DOCUMENTS WHICH SHOULD ADDRESS ALL COMMENTS.
  
 2ND REVIEW, NOT CLEAR WHAT SHOULD BE REVIEWED, NOT
 CLEAR WHAT IS PROPOSED TO BE ISSUED. NOTHING WAS MARKED
 VOID.
  
 4. THIS PERMIT WILL NOT BE ISSUED UNTIL THE MASTER IS
 ISSUED.
  
 5. I WAS UNABLE TO LOCATE ASSEMBLY PROPSED IN THE NEW
 SUBMITTAL. SEE COMMENT #3; IF THIS INFORMATION IS IN
 THE FIRST SUBMITTAL DOCUMENTS, THE DOCUMENTS NEEDED FOR
 REVIEW SHOULD BE PUT WITH THE CURRENT SUBMITTAL. A
 LARGE STACK OF PAPERS WAS SUBMITTED. THE SECOND PAPER
 CLIPPED PORTION STARTS WITH THE MIDDLE OF A PRODUCT
 APPROVAL. EITHER SUBMIT COMPLETE PRODUCT APPROVALS, OR
 SUBMIT ALL SHEETS NEEDED FOR REVIEW (COVER SHEET
 SHOWING PRODUCT APPROVAL NUMBER, STATUS, CODE VERSION,
 ETC.), FIRST PAGES WHICH ARE APPLICABLE TO ALL
 ASSEMBLIES (INCLUDES LIMITATIONS AND PRODUCTS), AND THE
 SHEET(S) WHICH INCLUDE INFORMATION REGARDING THE
 SPECIFIC PROPOSED ASSEMLY. IF YOU ARE UNSURE AS TO WHAT
 IS REQUIRED, SUBMIT THE COMPLETE PRODUCT APPROVAL WITH
 THE PROPOSED ASSEMBLY MARKED AND UNNEEDED SHEETS WILL
 BE REMOVED FOR YOU.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-07 Cont ID  
Sent By shill Date 2017-03-07 Time 10:57 Rev Time 0.00
Received By shill Date 2017-03-07 Time 10:57 Sent To  
Notes
2017-03-07 10:59:19****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, DESIGNER OF RECORD IS TO REVIEW PRODUCT
 APPROVALS AND DELEGATED ENGINEERING PRIOR TO SUBMITTAL.
  
 2. PROVIDE ALL PAGES OF THE PRODUCT APPROVALS WHICH ARE
 RELEVANT TO THE ASSEMBLY SELECTED. THIS SHOULD INCLUDE
 THE FLORIDA STATE PRODUCT APPROVAL COVER SHEET,
 EVALUATION REPORT (PAGES RELEVANT TO ALL ASSEMBLIES),
 AND INSTALLATION INSTRUCTIONS (PAGES RELEVANT TO ALL
 ASSEMBLIES).
  
 3. FBC 107, WHEN RESUBMITTING APPLICANT IS TO PREPARE
 TWO IDENTICAL COLLATED SETS OF PERMIT DOCUMENTS FOR
 PERMIT ISSUANCE.
  
 OLD SHEETS ARE TO BE RETAINED IN THE SUBMITTAL, REMOVED
 FROM THE TWO PERMIT ISSUE SETS, AND THOSE DOCUMENTS
 SHOULD BE MARKED "VOID" OR "OLD SHEETS".
  
 THE TWO COLLATED PERMIT SETS ARE TO INCLUDE ANY
 DOCUMENTS PREVIOUSLY SUBMITTED AND REVIEWED AS WELL AS
 THE NEW DOCUMENTS WHICH SHOULD ADDRESS ALL COMMENTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-19 Cont ID  
Sent By shill Date 2017-04-19 Time 17:56 Rev Time 0.00
Received By shill Date 2017-04-06 Time 10:16 Sent To  
Notes
2017-04-07 10:16:36RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-30 Cont ID  
Sent By shill Date 2017-03-30 Time 07:52 Rev Time 0.00
Received By shill Date 2017-03-10 Time 14:25 Sent To  
Notes
2017-03-10 14:25:46SHILL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-07 Cont ID  
Sent By shill Date 2017-03-07 Time 11:00 Rev Time 0.00
Received By shill Date 2017-02-21 Time 14:32 Sent To  
Notes
2017-02-22 14:32:46ROUTED TO SHILL