Plan Review Details - Permit 17020796
Plan Review Stops For Permit 17020796
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2018-11-13 Cont ID  
Sent By shill Date 2018-11-13 Time 08:08 Rev Time 0.00
Received By shill Date 2018-11-13 Time 08:08 Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2018-05-12 Cont ID  
Sent By shill Date 2018-05-12 Time 10:33 Rev Time 0.00
Received By shill Date 2018-05-12 Time 10:33 Sent To  
Notes
2018-05-12 10:34:50****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PLEASE ADVISE; DO YOU HAVE PARCEL ID NUMBERS AND
 ADDRESSES ASSIGNED FROM PROPERTY APPRAISER?
  
 WHEN WILL THE REPLAT BE FINALIZED? IF FILED, PROVIDE
 BOOK/PAGE.
  
 PLEASE PROVIDE THIS INFORMATION VIA EMAIL, SUBJECT LINE
 TO REFERENCE THIS PERMIT NUMBER 17020796.
  
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2017-04-24 Cont ID  
Sent By shill Date 2017-04-24 Time 17:36 Rev Time 0.00
Received By shill Date 2017-04-24 Time 17:36 Sent To  
Notes
2017-04-24 17:51:09CONTACT MICHAEL ORIO
 [email protected]
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 2022-08-15 Cont ID  
Sent By scwelter Date 2022-08-15 Time 16:21 Rev Time 0.00
Received By scwelter Date 2022-08-15 Time 16:23 Sent To  
Notes
2022-08-15 16:23:37SUBJECT TO PUBLIC ART REQUIREMENT. CONTACT
 [email protected] FOR AN ART ASSESSMENT APPLICATION.
 MUST CONTRIBUTE TO THE PUBLIC ART ACCOUNT.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-10-16 Cont ID  
Sent By dbattles Date 2018-10-16 Time 08:07 Rev Time 0.00
Received By dbattles Date 2018-10-16 Time 08:06 Sent To  
Notes
2018-10-16 08:05:17PROVISO: DERFERED SUBMITTALS
 1. ROOFING (SUBMIT WITH SUB-PERMIT)
 2. GUARDS AND HANDRAILS
 3. STEEL PAN STAIRS
 4. TRASH CHUTE
 5. FENESTRATION
 6. FLOORING SUBMITTAL WITH REPORTS FOR ICC, STC AND
 FLAME SPREAD/SMOKE DEVELOPED INDEX.
 7. ART IN PUBLIC PLACES (AIPP)
 8. SHORING/RE-SHORING
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-09-07 Cont ID  
Sent By dbattles Date 2018-09-07 Time 14:24 Rev Time 0.00
Received By dbattles Date 2018-09-05 Time 11:34 Sent To  
Notes
2018-09-07 14:27:42****CORRECTIONS****
 W.P.B. PERMIT: 17020796
 3RD REVIEW: SEPTEMBER 6, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. OK
  
 2. COMMENT FROM FIRST REVIEW: A1.2.01 EXIT DISCHARGE
 NOT CLEAR; REVISE PLAN TO SHOW COMPLIANCE WITH FBC B
 1027.
  
 ON THE ELECTRICAL PAGES, I WAS NOT ABLE TO LOCATE VOICE
 EVAC. SHEET E2.1.01 SHOWS A FIRE ALARM CONTROL PANEL,
 DETAILS ON E3.1.02, BUT I WAS UNABLE TO LOCATE THE
 LABEL "EVAC" ON THE FLOOR PLANS (PER ELECTRICAL LEGEND)
 AND E3.1.02 WAS NOT CLEAR. PLEASE DIRECT WHERE THIS
 INFORMATION CAN BE FOUND OR CLARIFY INTENT. NOTE THAT
 FBC B 1005.3.1 REQUIRES .3" PER OCCUPANT, BUT .2" WAS
 USED PER EXCEPTION.
  
 2- 3RD REVIEW
 MOST OF THIS IS WAS ADDRESSED IN COMMENT RESPONSE, BUT
 NOT THE VOICE EVAC PORTION. THE FACP ON SHEET E-3.1.02
 DOESN'T SHOW AS A VOICE EVAC SYSTEM.
  
 (SEE NEW COMMENTS FROM LIFE SAFETY SHEETS PROVIDED AT
 BOTTOM STARTING COMMENT #35)
  
 3-6. OK
  
 7-11. OK
  
 12. 2ND REVIEW, NOT ADDRESSED. ENGINEER OF RECORD IS TO
 REVIEW THE SOILS, EITHER WITH A SHOP DRAWING REVIEW
 STAMP OR BY INCORPORATING A REFERENCE INTO THE PLAN.
 THE SOILS REPORT WAS PROVIDED FOR THE FOUNDATION PERMIT
 APPLICATION (17010911). AFTER THE FOUNDATION PERMIT IS
 ISSUED, THE SOILS WILL BE PUBLIC RECORD AND IS NOT
 NEEDED FOR THIS PERMIT. IF YOU RESUBMIT PRIOR TO
 ISSUANCE OF FOUNDATION PERMIT, PLEASE INCLUDE IN YOUR
 RESUBMITTAL.
  
 12- 3RD REVIEW THE NOTES ADDED WILL REFER TO SOILS
 REPORT FOR BEARING CAPACITY, BUT STRUCTURAL SHEETS
 S-2.00, S-2.00A AND S-2.00B SHOW THE TOP OF FOOTERS AT
 12" BELOW GRADE. THE GEO TECHNICAL REPORT STATES THAT
 TOP OF FOOTERS SHOULD BE PLACED 18" BELOW GRADE. PLEASE
 REVIEW AND REVISE AS APPLICABLE.
  
 13-37. OK (26-28 MOVED TO PROVISO)
  
 38. (MOVED TO PROVISO)
  
 39-40. OK
  
 41. (MOVED TO PROVISO)
  
 42. THIS PERMIT WILL BE ISSUED WITH PROVISOS:
  
 A. COMPLIANCE WITH ART IN PUBLIC PLACES ORDINANCE
 78-123 REQUIRED: MS. SYBILLE WELTER, 561-822-1515,
 [email protected]. MS. WELTER WILL ADVISE VIA EMAIL WHEN
 THIS IS COMPLETE.
  
 B. SEPARATE PERMITS REQUIRED. SUB PERMITS FOR
 MECHANICAL, ELECTRICAL, PLUMBING ARE REQUIRED. SEPARATE
 PERMITS (APPLICATION, FEES, PLANS, REVIEWS) REQUIRED
 FOR ALL OTHER ITEMS SUCH AS PARKING, SIGNAGE, ETC.
  
 C. COMPLIANCE WITH FBC B 1006, MEANS OF EGRESS
 ILLUMINATION, INCLUDING EXIT DISCHARGE, REQUIRED.
  
 D. VOICE EVAC REQUIRED (NOTE 35, SHEET E3.1.02).
  
 E. ADVISORY ONLY; THE LANDSCAPE PLANS APPEAR TO
 CONFLICT WITH THE EXIT DISCHARGE. LANDSCAPE PERMIT
 REQUIRES A SEPARATE SUBMITTAL; PERMIT APPLICATION,
 FEES, AND PLANS AND ARE NOT REVIEWED BY BUILDING.
  
 F. PRODUCT APPROVALS FOR ALL COMPONENTS AND CLADDING
 ARE TO BE SUBMITTED, REVIEWED BY DESIGNER OF RECORD,
 REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 G. SHORING/RESHORE ENGINEERING ARE REQUIRED TO BE
 SUBMITTED, REVIEWED, AND ISSUED PRIOR TO INSTALLATION.
 FAILURE TO DO SO WILL RESULT IN A STOP WORK ORDER.
  
 H. AN ENGINEERED CONSTRUCTION GUARD RAIL DETAIL IS
 REQUIRED PRIOR TO INSTALLATION. THIS MAY BE SUBMITTED
 AS A SUBMITTAL ALONG WITH THE SHORING/RESHORE, BUT MAY
 BE PROVIDED IN THE FIELD TO KEN CONRAD, SUBJECT TO HIS
 APPROVAL.
  
 I. RECORDED REPLAT REQUIRED PRIOR TO C.O.; PROVIDE
 BOOK/PAGE VIA EMAIL.
  
 J. BUILT IN BENCHES TO COMPLY WITH FBC A 903.
  
 K. DRESSING, FITTING AND LOCKER ROOMS TO COMPLY WITH
 FBC A 222, REVISE PLAN TO SHOW COMPLIANCE.
  
 L. SPA RECEPTION/ RETAIL DESK, ANY OTHER CHECK OUT
 AREAS, SEE FBC A 904 NOTE ON PLAN AND PROVIDE A DETAIL
 2ND REVIEW: RESPONSE TO 26, 27, 28 REFERS TO D SHEETS;
 THESE PAGES ARE NOT SIGNED AND SEALED AND IT IS NOT
 CLEAR WHO IS TAKING RESPONSIBILITY FOR THE PAGES.
 PLEASE REMOVE THE SHEETS AS IT APPEARS MOST OF THE
 INFORMATION IS NOT REQUIRED. ITEMS 26, 27, AND 28 CAN
 BE A PROVISO ITEM.
  
 M. FBC B 603.1, A4.4.02 DETAIL 12 SHOWS POLYSTYRENE
 OUTRIGGER AT METAL ROOFS AND POSSIBLY OTHER LOCATIONS,
 OTHER DETAILS. PLEASE PROVIDE MORE INFORMATION VIA
 EMAIL REGARDING HEIGHT OF LOCATIONS PROPOSED (OVER
 30'?), OVER EXITS. A4.4.03 SHOWS EXTERIOR FOAM; PROVIDE
 INFORMATION VIA EMAIL. ARE THESE PRODUCTS
 NONCOMBUSTIBLE?
  
 N. ADVISORY ONLY; SHEET D0.0.00 SHOWS A PLATFORM BED.
 IT IS NOT CLEAR IF THIS BED COMPLIES WITH FBC A
 806.4(II), OPEN-FRAME TYPE BEDS REQUIRED. THIS WILL BE
 A PROVISO ITEM.
  
 ADDITIONAL COMMENTS:
  
 43. [FBC 1011.1]SHEET A-1.2.01 EXIT SIGNS. EXIT SIGNS
 ARE ONLY LOCATED AT THE EGRESS DOORS AND NO
 INTERMEDIATE SIGNS ARE PROVIDED WHEN THE EGRESS DOOR
 ISN'T VISABLE. FLOORS 2-4 DO A GOOD JOB OF THIS, BUT
 FIRST FLOOR NEEDS REVIEW OF EXIT SIGN PLACEMENT.
  
 44. [FBC 1011.2]FLOOR-LEVEL EXIT SIGNS IN GROUP R-1.
 WHERE EXIT SIGNS ARE REQUIRED IN GROUP R-1 OCCUPANCIES
 BY SECTION 1011.1, ADDITIONAL LOW-LEVEL EXIT SIGNS
 SHALL BE PROVIDED IN ALL AREAS SERVING GUESTROOMS IN
 GROUP R-1 OCCUPANCIES AND SHALL COMPLY WITH SECTION
 1011.5.
  
 45. [FBC 701]GENERAL COMMENT-CHECK THAT LIFE SAFETY
 SHEET FOR 1ST FLOOR SHOWS DESIGNATED LINES TO CORESPOND
 WITH FIRE RATED WALLS AND THAT FLOORS PLAN WALL TYPES
 MATCH THE REQ?D FIRE RATINGS. MAINLY ON SHEET A-1.2.01
 THE CORRIDORS DON?T SHOW THE 1 HOUR RATED DASHED LINES
 (SEE BELOW FOR EXAMPLES ON THE FLOOR PLANS)
  
 46. [FBC 701]SHEET A-1.4.01B WALLS IN WOMENS LOUNGE AND
 SPA THAT DEFINE COORIDOR ARE LABLED TYPE C4 WHICH IS
 NON-RATED, BUT LIFE SAFETY STATES ALL CORRIDORS ARE TO
 BE 1 HR WHICH WOULD BE TYPE C1 ACCORDING TO SHEET
 A-6.6.02.
  
 47. [FBC 701]SHEET A-1.4.01A MECH RM 116 SHOWS C1 ON
 CORRIDOR WALL, BUT THE REST OF ROOM IS 2 HR.
 SAME FOR RM 1112C. ALSO, MECH ROOM 1103A BACK WALL IS
 NOT LABELED WITH WALL TYPE.
  
 48. [FBC 701]SHEET A-1.4.01A WHY ARE FIRE RATED WALLS
 IN RM 1107 & 1108 CALLED OUT FOR THE BATHROOM
 PARTITIONS? ARE THEY SUPPOSED TO BE C4 FOR SOUND ONLY?
 ALSO, FOR RESTROOMS 1149 & 1150 NO WALL TYPES ARE
 SHOWN.
 IN GENERAL PLEASE LOOK AT RESTROOMS AND PROVIDE
 INTENDED WALL TYPES.
  
 49. WHAT IS THE RATING, ASSEMBLY AND GLASS TYPE FOR
 WALLS/WINDOWS ATDINING BOOTHS THAT LOOK INTO CORRIDOR
 1122?
  
 50. [NO CODE REF]CHECK SHEET A-1.3.01 1ST FLOOR PLAN.
 THE PERIMETER HAS A LIGHTER OFF-SET LAYER THAT SHOWS
 ITEMS ON A LAYER THAT I THINK SHOULD BE TURNED OFF.
  
 51. [FBC ACCESSIBILITY 233.3.1]MINIMUM NUMBER: NEW
 CONSTRUCTION.
 IN FACILITIES WITH RESIDENTIAL DWELLING UNITS, AT LEAST
 5 PERCENT, BUT NO FEWER THAN ONE UNIT, OF THE TOTAL
 NUMBER OF RESIDENTIAL DWELLING UNITS SHALL PROVIDE
 MOBILITY FEATURES COMPLYING WITH 809.2 THROUGH 809.4
 AND SHALL BE ON AN ACCESSIBLE ROUTE AS REQUIRED BY 206.
 I SEE 5 ROOMS PROVIDED, BUT 5% OF 150 ROOMS WOULD BE 8
 ROOMS NEEDED TO COMPLY WITH REQUIRED AMOUNT.
  
 52. [FBC ACCESSIBILITY 233.3.1.2]RESIDENTIAL DWELLING
 UNITS WITH COMMUNICATION FEATURES.
 IN FACILITIES WITH RESIDENTIAL DWELLING UNITS, AT LEAST
 2 PERCENT, BUT NO FEWER THAN ONE UNIT, OF THE TOTAL
 NUMBER OF RESIDENTIAL DWELLING UNITS SHALL PROVIDE
 COMMUNICATION FEATURES COMPLYING WITH 809.5.
 I SEE 11 ROOMS PROVIDED WHICH EXCEEDS THE RE'D 2% (3
 ROOMS). THIS EXCEEDS CODE AND I ONLY MENTION BECAUSE I
 WONDER IF SOME OF THESE WERE INTENED TO PROVIDE
 MOBILITY FEATURES INSTEAD OF COMMUNICATION FEATURES.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-05-12 Cont ID  
Sent By shill Date 2018-05-12 Time 17:57 Rev Time 0.00
Received By shill Date 2018-04-30 Time 18:54 Sent To  
Notes
2018-05-07 06:24:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 BANYAN CAY FOUR STORY HOTEL
 ***THRESHOLD BUILDING***, POST TENSION 6"-8" SLABS, FRT
 TRUSSES, TYPE IIA
 ARCHITECT - ADACHE GROUP ARCHITECTS, DANIEL E. ADACHE
 AR7073
 ENGINEER - MUE ENGINEERS, INC (29348), MARCUS O.
 UNTERWEGER, PE63860
 MEP - TLC ENGINEERING
 MECHANICAL - JORGE E. REYES, PE54904
 ELECTRICAL - RALPH BAEZA, PE42641
 PLUMBING - JORGE E. REYES, PE54904
  
  
 1. OK
  
 2. COMMENT FROM FIRST REVIEW: A1.2.01 EXIT DISCHARGE
 NOT CLEAR; REVISE PLAN TO SHOW COMPLIANCE WITH FBC B
 1027.
  
 2ND REVIEW, RESPONSE LETTER STATES THAT FBC B 1027
 REFERENCES "EXTERIOR EXIT STARIWAYS AND RAMPS" AND
 GIVES SOME EXPLANATION ABOUT ALL STAIRS BEING INTERIOR
 STAIRS.
  
 THE FBC 2014 BUILDING, SECTION 1027, IS TITLED "EXIT
 DISCHARGE". SECTION 1022 IS INTERIOR STAIRS AND RAMPS.
 SEE PREVIOUS COMMENT; REFERENCE WAS TO FBC B 1027, NOT
 FBC B 1022, AND SPECIFICALLY REFERENCES "EXIT
 DISCHARGE". IT IS NOT CLEAR WHY RESPONSE LETTER
 EXPLAINS SOMETHING UNRELATED.
  
 SEE FBC 1027.5, EXIT DISCHARGE SHALL PROVIDE A DIRECT
 AND UNOBSTRUCTED ACCESS TO A PUBLIC WAY, SEE ALSO
 EXCEPTIONS. ALSO SEE COMMENT #3. SHEET A1.2.00 APPEARS
 TO SHOW COMPLIANCE EXCEPT AS NOTED IN OTHER COMMENTS,
 BUT INFORMATION REGARDING ACCESSIBILITY AND SLOPES NOT
 PROVIDED.
  
 COMPLIANCE WITH REQUIREMENTS FOR EXIT DISCHARGE
 ILLUMINATION NOT CLEAR; THIS PERMIT WILL BE ISSUED WITH
 PROVISO, COMPLIANCE WITH FBC B 1006 REQUIRED.
  
 FIRST FLOOR LIFE SAFETY PLAN A1.2.01 IS NOT CLEAR ON
 NUMBER OF OCCUPANTS IN EACH ROOM AS A SUMMARY WAS
 PROVIDED. IT APPEARS THAT EXIT CAPACITY IS ADEQUATE FOR
 EACH AREA, BUT COMPLIANCE WITH REQUIREMENT FOR EXIT
 DISCHARGE IS NOT CLEAR.
  
 FOR INSTANCE: THE PATH AT THE LEFT OF THE SITE LIFE
 SAFETY PLAN INDICATES "146 OCCUPANTS". FIRST FLOOR
 SHOWS 146 OCCUPANTS EXITING FROM THE STAIR AND EXIT
 CORRIDOR. BUT NO OCCUPANT LOAD WAS PROVIDED FOR MEETING
 ROOM #1, BALLROOM #1, ETC. WHICH ALSO TRAVEL ALONG THE
 SAME PATH IN THE EXIT DISCHARGE. A SUMMARY FOR EACH
 OCCUPANCY WAS PROVIDED, BUT AS THE OCCUPANCIES ARE IN
 DIFFERENT AREAS OF THE BUILDING, THE NUMBER USING THE
 GRAPHICALLY DEPICTED EXIT DISCHARGE IS NOT CLEAR.
  
 THE CIVIL PAGES INCLUDE ELEMENTS IN THE EXIT DISCHARGE
 WHICH ARE NOT SHOWN ON THE LIFE SAFETY SHEETS (APPEARS
 TO BE FENCES, GATES). PLEASE CORRELATE. FOR INSTANCE,
 CIVIL PAGE 2 OF 9 MASTER PLAN) WHICH SHOWS GATES IN THE
 MEANS OF EGRESS, AND THE SITE LIFE SAFETY PLAN A1.2.00.
 PLEASE CORRELATE AND NOTE THAT ALL GATES WILL INCLUDE
 PANIC HARDWARE (PER FBC B 1008.2. NO INFORMATION WAS
 PROVIDED REGARDING THE WIDTH OF THESE ELEMENTS.
  
 THE ELECTRICAL SITE PLAN E1.1.01 APPEARS TO CONFLICT
 WITH THE EXIT DISCHARGE (GENERATOR, OTHER ITEMS);
 PLEASE CORRELATE. IF THEY DO NOT CONLICT PROVIDE ENOUGH
 DIMENSIONS ON THE PLAN TO SHOW THAT THE GENERATOR IS
 NOT INTERFEREING WITH THE HATCHED EXIT DISCHARGE SHOWN
 ON OTHER SHEETS.
  
 ADVISORY ONLY; THE LANDSCAPE PLANS APPEAR TO CONFLICT
 WITH THE EXIT DISCHARGE. LANDSCAPE PERMIT REQUIRES A
 SEPARATE SUBMITTAL; PERMIT APPLICATION, FEES, AND PLANS
 AND ARE NOT REVIEWED BY BUILDING.
  
 ON THE ELECTRICAL PAGES, I WAS NOT ABLE TO LOCATE VOICE
 EVAC. SHEET E2.1.01 SHOWS A FIRE ALARM CONTROL PANEL,
 DETAILS ON E3.1.02, BUT I WAS UNABLE TO LOCATE THE
 LABEL "EVAC" ON THE FLOOR PLANS (PER ELECTRICAL LEGEND)
 AND E3.1.02 WAS NOT CLEAR. PLEASE DIRECT WHERE THIS
 INFORMATION CAN BE FOUND OR CLARIFY INTENT. NOTE THAT
 FBC B 1005.3.1 REQUIRES .3" PER OCCUPANT, BUT .2" WAS
 USED PER EXCEPTION.
  
 3. COMMENT FROM FIRST REVIEW: ACCESSIBLE MEANS OF
 EGRESS SELECTED NOT CLEAR; SEE FBC 1007, FBC A 207.1.
 REVISE PLAN TO STATE WHICH METHOD IS SELECTED AND
 CONFIRM COMPLIANCE WITH METHOD SELECTED; REVISE PLAN IF
 NECESSARY TO SHOW COMPLIANCE.
  
 2ND REVIEW, RESPONSE LETTER GIVES INFORMATION REGARDING
 STAIRS. THIS DOES NOT ADDRESS THE COMMENT.
  
 FBC B 1007 REFERS TO FBC A 207.1.
 FBC A 207.1 MEANS OF EGRESS SHALL COMPLY WITH SECTION
 1003.2.13 OF THE INTERNATIONAL BUILDING CODE 2000 AND
 2001 SUPPLEMENT OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE 2003 EDITION. COMPLIANCE WITH ONE OF
 THESE TWO METHODS OF COMPLIANCE IS NOT CLEAR;
 PARTICULARLY THE EXIT DISCHARGE (SEE ALSO IBC 2003
 1007.2).
  
 THIS ITEM HAS NOT BEEN REVIEWED.
  
 AS THE FINISHED FLOOR AFFECTS THE ACCESSIBLE ROUTE,
 EXIT DISCHARGE, AND ACCESSIBLE EXIT DISCHARGE,
 COMPLIANCE SHOULD BE DEMONSTRATED PRIOR TO ISSUANCE OF
 A FOUNDATION PERMIT - RESOLUTION TO COMMENTS #2 AND #3
 NEED TO BE RESOLVED PRIOR TO FOUNDATION PERMIT
 ISSUANCE.
  
 APPLICANT MAY SEND AN EMAIL EXPLAINING COMPLIANCE AND
 HOW THIS WILL BE ADDRESSED UPON RESUBMITTAL TO GET THIS
 ISSUE RESOLVED PRIOR TO REVIEW OF FOUNDATION PERMIT.
  
 4-6. OK
  
 7. COMMENT FROM FIRST REVIEW: A1.4.01B, FITNESS ROOM TO
 COMPLY WITH FBC A 1004, REVISE TO SHOW COMPLIANCE.
  
 IF DETAILS SUCH AS SPECIFIC TYPES OF MACHINES PROPOSED
 IS NOT AVAILABLE AT THIS TIME, REVISE THE PLAN TO SHOW
 GENERAL COMPLIANCE. INCLUDE NOTES REGARDING COMPLIANCE.
 THIS PERMIT WILL BE ISSUED WITH PROVISO, ISSUED AT
 CONTRACTOR'S RISK, PROVIDE A DETAILED PLAN AT
 INSPECTION. SUBJECT TO FIELD INSPECTOR'S DISCRETION,
 FITNESS CENTER PLAN MAY BE REQUIRED TO BE SUBMITTED FOR
 PLAN REVIEW.
  
 2ND REVIEW, CLEAR FLOOR SPACE WAS ADDED BUT IS ALMOST
 ILLEGIBLE. PLEASE DARKEN THESE LINES, AT LEAST TO THE
 GREY VALUE OF THE EQUIPENT. IT'S ABOUT .25 DARKNESS OF
 THE EQUIPMENT WHICH IS ABOUT .5 COMPARED TO THE
 BLACKLINES.
  
 I WAS UNABLE TO LOCATE NOTES REGARDING COMPLIANCE;
 PLEASE ADD NOTE OR PROVIDE ALL INFORMATION FOR REVIEW.
  
 8. OK
  
 9. ADVISORY; ENGINEER ADDED A NOTE RE: FRT FOR ALL
 WOOD. SEE SHEET S2.02A-R, PORTE COCHERE ROOF FRAMING
 NOTES, HEAVY TIMBER FRAMING PROPOSED. PLEASE NOTE THAT
 THIS IS ALSO REQUIRED TO BE FRT; PLAN HAS BEEN REDLINED
 IN THIS AND OTHER LOCATIONS.
  
 10-11. OK
  
 12. COMMENT FROM FIRST REVIEW: SOIL BEARING VALUES. THE
 TEST BY UNIVERSAL ENGINEERING SCIENCES REFERENCES THE
 TEST IS PRELIMINARY GEOTECHNICAL ENGINEERING REPORT
 BANYAN CAY- HOTEL PLEASE NOTE THE BORING SAMPLES TAKEN
 CH-1 AND CH-2 ARE SHOWN FOR THE CLUBHOUSE, THIS SOILS
 REPORT HAS NO BORINGS SHOWN IN THE REPORT FOR THE
 HOTEL. NOTE FOR THE TENNIS CLUB CENTER UP TO 6 FEET OF
 MUCK WAS ENCOUNTERED WITHIN THE BUILDING FOOTPRINT.
 PLEASE COMPLY WITH: 2014 FBC-B 1803.3 BASIS OF
 INVESTIGATION.
 SOIL CLASSIFICATION SHALL BE BASED ON OBSERVATION AND
 ANY NECESSARY TESTS OF THE MATERIALS DISCLOSED BY
 BORINGS, TEST PITS OR OTHER SUBSURFACE EXPLORATION MADE
 IN APPROPRIATE LOCATIONS. ADDITIONAL STUDIES SHALL BE
 MADE AS NECESSARY TO EVALUATE SLOPE STABILITY, SOIL
 STRENGTH, POSITION AND ADEQUACY OF LOAD-BEARING SOILS,
 THE EFFECT OF MOISTURE VARIATION ON SOIL-BEARING
 CAPACITY, COMPRESSIBILITY, LIQUEFACTION AND
 EXPANSIVENESS.
  
 2ND REVIEW, NOT ADDRESSED. ENGINEER OF RECORD IS TO
 REVIEW THE SOILS, EITHER WITH A SHOP DRAWING REVIEW
 STAMP OR BY INCORPORATING A REFERENCE INTO THE PLAN.
 THE SOILS REPORT WAS PROVIDED FOR THE FOUNDATION PERMIT
 APPLICATION (17010911). AFTER THE FOUNDATION PERMIT IS
 ISSUED, THE SOILS WILL BE PUBLIC RECORD AND IS NOT
 NEEDED FOR THIS PERMIT. IF YOU RESUBMIT PRIOR TO
 ISSUANCE OF FOUNDATION PERMIT, PLEASE INCLUDE IN YOUR
 RESUBMITTAL.
  
 13-15. OK
  
  
 16. SEE FBC A 209.2.1, 209.4, LABEL ALL PASSENGER
 LOADING ZONES ON THE PLAN, REVISE PLAN TO SHOW
 COMPLIANCE WITH REQUIREMENTS.
  
 2ND REVIEW, PLEASE SUBMIT REQUEST FOR AN ALTERNATE
 DESIGN TO BE ACCEPTED VIA EMAIL. THE LETTER SHOULD
 INCLUDE A PLAN SHOWING WHAT IS PROPOSED ALONG WITH THE
 HOTEL SOP FOR THE LOADING ZONE ALONG WITH RATIONALE.
  
 17-24. OK
  
 25. COMMENT FROM FIRST REVIEW: SHEET A5.1.04 IS BLANK,
 FBC 107 PROVIDE INFORMATION INCLUDING PANIC HARDWARE
 FBC B 1008.1.10.
  
 2ND REVIEW: A5.1.04 HAS BEEN UPDATED, BUT REFERS TO
 HARDWARE SETS. HARDWARE SETS ARE DESCRIBED ON SHEET
 A5.1.05. A SEARCH OF THE WORD "PANIC" AND "FIRE"
 YIELDED NO RESULTS.
  
 TO EXPEDITE PLAN REVIEW: IF AN ADDITIONAL COLUMN WITH
 "PANIC BAR" OR "FIRE EXIT HARDWARE" IS ADDED, AND A
 MARK TO INDICATE WHICH DOORS WILL HAVE PANIC BARS, IN
 PLAN REVIEW A SPOT CHECK WILL BE DONE, AND A PROVISO
 ADDED (ALL DOORS AND GATES IN THE MEANS OF EGRESS FOR
 ASSEMBLY OCCUPANCY, ELECTRICAL ROOMS, STAIRS, AND OTHER
 LOCATIONS REQUIRED ARE TO HAVE PANIC BARS OR FIRE EXIT
 HARDWARE IN ACCORDANCE WITH FBC B 1008.1.10).
  
 26. BUILT IN BENCHES TO COMPLY WITH FBC A 903.
 27. DRESSING, FITTING AND LOCKER ROOMS TO COMPLY WITH
 FBC A 222, REVISE PLAN TO SHOW COMPLIANCE.
 28. SPA RECEPTION/ RETAIL DESK, ANY OTHER CHECK OUT
 AREAS, SEE FBC A 904 NOTE ON PLAN AND PROVIDE A DETAIL
 2ND REVIEW: RESPONSE TO 26, 27, 28 REFERS TO D SHEETS;
 THESE PAGES ARE NOT SIGNED AND SEALED AND IT IS NOT
 CLEAR WHO IS TAKING RESPONSIBILITY FOR THE PAGES.
 PLEASE REMOVE THE SHEETS AS IT APPEARS MOST OF THE
 INFORMATION IS NOT REQUIRED. ITEMS 26, 27, AND 28 CAN
 BE A PROVISO ITEM.
  
 29. OK
  
 30. ARCHITECT'S TITLE BLOCK LACKS THE ARCHITECT
 BUSINESS NUMBER, REVISE TO INCLUDE, FS481, FAC 61G16.
  
 2ND REVIEW, AR7073 IS THE ARCHITECT'S LICENSE NUMBER AS
 AN INDIVIDUAL. THE FIRM, ADACHE GROUP ARCHITECTS, IS
 REQUIRED TO HAVE A ARCHITECT BUSINESS NUMBER. PER DBPR
 WEBSITE, THIS IS AA26002281. PLEASE ADD THIS NUMBER TO
 ALL SHEETS, BUT ONLY UPLOAD PAGES WHICH CHANGE DUE TO
 COMMENTS TO AVOID A LENGTHY 3RD REVIEW CYCLE.
  
 31. SEE SIGNATURE REVIEW.
  
 32. 2ND REVIEW; THE CERTIFICATE OF AUTHORIZATION IS
 LACKING (FMEP), FS471, FAC61G15-23. PLEASE ADD TO ALL
 SHEETS, BUT ONLY UPLOAD PAGES WHICH CHANGE DUE TO
 COMMENTS.
  
 33. OK
  
 34. SEE SIGNATURE REVIEW.
  
 35. SEE IMPACT FEE REVIEW.
  
 NEW COMMENTS
  
 37. 05.31.2017 BCR FOOD SERVICE SPECIFICATIONS AND
 11.25.2016 BCR FOOD SERVICE PROPOSED LAYOUT WERE
 UPLOADED INTO THE "DRAWINGS" FOLDER RATHER THAN
 "SUPPORTING DOCUMENTS"; PLEASE MOVE (OR REMOVE) FROM
 DRAWINGS FOLDER AND ENSURE THAT ALL REQUIRED
 INFORMATION IS IN THE SUPPORTING DOCUMENTS FOLDER.
  
 38. FBC B 603.1, A4.4.02 DETAIL 12 SHOWS POLYSTYRENE
 OUTRIGGER AT METAL ROOFS AND POSSIBLY OTHER LOCATIONS,
 OTHER DETAILS. PLEASE PROVIDE MORE INFORMATION VIA
 EMAIL REGARDING HEIGHT OF LOCATIONS PROPOSED (OVER
 30'?), OVER EXITS. A4.4.03 SHOWS EXTERIOR FOAM; PROVIDE
 INFORMATION VIA EMAIL. ARE THESE PRODUCTS
 NONCOMBUSTIBLE?
  
 39. ADVISORY ONLY, NEW SHEET A4.5.03 DETAIL 8 SHOWS A 1
 HOUR GLASS WALL AND REFERS TO WATER CURTAIN WALL. NOTE
 THAT THE GLASS DETAIL SHOWS HORIZONTAL MULL BARS.
 PLEASE NOTE THAT, IF THIS OPTION IS ELECTED VIA A
 REVISION, EITHER THE HORIZONTAL MULL BARS ARE TO BE
 REMOVED OR DOR IS REQUIRED TO REVIEW SPRINKLER HEAD
 SPEC SHEETS TO CONFIRM THAT HORIZONTAL MULLIONS ARE
 PERMITTED. IF THIS OPTION IS ELECTED VIA A REVISION,
 PLANS ARE TO BE REVISED AND THE WINDOW SPRINKLER SPEC
 SHEET IS TO BE SUBMITTED.
  
 40. FBC 107, NEW SHEET 3-A4.5.04 SHOWS "CONTENTIOUS
 WOOD BLOCKING", CLARIFY OR REVISE (DO YOU MEAN
 CONTINUOUS?).
  
 41. ADVISORY ONLY; SHEET D0.0.00 SHOWS A PLATFORM BED.
 IT IS NOT CLEAR IF THIS BED COMPLIES WITH FBC A
 806.4(II), OPEN-FRAME TYPE BEDS REQUIRED. THIS WILL BE
 A PROVISO ITEM.
  
 42. THIS PERMIT WILL BE ISSUED WITH PROVISOS:
  
 A. COMPLIANCE WITH ART IN PUBLIC PLACES ORDINANCE
 78-123 REQUIRED: MS. SYBILLE WELTER, 561-822-1515,
 [email protected]. MS. WELTER WILL ADVISE VIA EMAIL WHEN
 THIS IS COMPLETE.
  
 B. SEPARATE PERMITS REQUIRED. SUB PERMITS FOR
 MECHANICAL, ELECTRICAL, PLUMBING ARE REQUIRED. SEPARATE
 PERMITS (APPLICATION, FEES, PLANS, REVIEWS) REQUIRED
 FOR ALL OTHER ITEMS SUCH AS PARKING, SIGNAGE, ETC.
  
 C. COMPLIANCE WITH FBC B 1006, MEANS OF EGRESS
 ILLUMINATION, INCLUDING EXIT DISCHARGE, REQUIRED.
  
 D. VOICE EVAC REQUIRED (NOTE 35, SHEET E3.1.02).
  
 E. ADVISORY ONLY; THE LANDSCAPE PLANS APPEAR TO
 CONFLICT WITH THE EXIT DISCHARGE. LANDSCAPE PERMIT
 REQUIRES A SEPARATE SUBMITTAL; PERMIT APPLICATION,
 FEES, AND PLANS AND ARE NOT REVIEWED BY BUILDING.
  
 F. PRODUCT APPROVALS FOR ALL COMPONENTS AND CLADDING
 ARE TO BE SUBMITTED, REVIEWED BY DESIGNER OF RECORD,
 REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 G. SHORING/RESHORE ENGINEERING ARE REQUIRED TO BE
 SUBMITTED, REVIEWED, AND ISSUED PRIOR TO INSTALLATION.
 FAILURE TO DO SO WILL RESULT IN A STOP WORK ORDER.
  
 H. AN ENGINEERED CONSTRUCTION GUARD RAIL DETAIL IS
 REQUIRED PRIOR TO INSTALLATION. THIS MAY BE SUBMITTED
 AS A SUBMITTAL ALONG WITH THE SHORING/RESHORE, BUT MAY
 BE PROVIDED IN THE FIELD TO KEN CONRAD, SUBJECT TO HIS
 APPROVAL.
  
 I. RECORDED REPLAT REQUIRED PRIOR TO C.O.; PROVIDE
 BOOK/PAGE VIA EMAIL.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-04-24 Cont ID  
Sent By shill Date 2017-04-24 Time 17:36 Rev Time 0.00
Received By shill Date 2017-04-17 Time 07:24 Sent To  
Notes
2017-04-24 17:36:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 W. P. B. PERMIT: 17020796 (BANYAN CAY HOTEL)
 ADD: 3200 N. CONGRESS AVE. (ADDRESS TO BE ASSIGNED)
 CONT: HEDRICK BROTHERS
 TEL: 561-689-8880
 E-MAIL: [email protected]
  
 1. REVISE SITE PLAN TO SHOW DISTANCE TO PROPERTY LINE
 OR ASSUMED PROPERTY LINE BETWEEN BUIDINGS LOCATED ON
 THE SAME LOT, DISTANCE OF PROPOSED HOTEL TO PROPERTY
 LINE AND/OR ASSUMED PROPERTY LINE, DISTANCE OF ADJACENT
 STRUCTURES TO ASSUMED PROPERTY LINE (IF APPLICABLE),
 FBC B TABLE 602, 705.3.
  
 2. A1.2.01 EXIT DISCHARGE NOT CLEAR; REVISE PLAN TO
 SHOW COMPLIANCE WITH FBC B 1027.
  
 3. ACCESSIBLE MEANS OF EGRESS SELECTED NOT CLEAR; SEE
 FBC 1007, FBC A 207.1. REVISE PLAN TO STATE WHICH
 METHOD IS SELECTED AND CONFIRM COMPLIANCE WITH METHOD
 SELECTED; REVISE PLAN IF NECESSARY TO SHOW COMPLIANCE.
  
 4. A1.2.01 1ST FLOOR SQUARE FOOT AREA IS 31,750,
 PROJECT DATA SHOWS 41,956. OTHER FLOORS ALSO
 INCONSISTENT. REVISE TO CLARIFY DISCREPANCY, FBC 107.
  
 5. SOME AREAS WERE NOT INCLUDED ON THE OCCUPANT LOAD
 CHART; FOR INSTANCE, HOUSEKEEPING. ALTHOUGH OCCUPANT
 LOADS FOR THESE AREA WILL BE LOW, THEY SHOULD BE
 INCLUDED FOR AN ACCURATE TOTAL. THIS INFORMATION IS
 REQUIRED FOR CO.
  
 6. A1.2.01, CLARIFY FIRE RATED WALL AT RETAIL/COFFEE.
 THIS, AND SOME OTHER FIRE RATED WALLS ARE NOT CLEAR AS
 TO PURPOSE OR CONTINUITY, FBC 107. IF YOU WISH, PLEASE
 CONTACT ME TO DISCUSS PRIOR TO RESUBMITTAL. FOR
 INSTANCE, 2 HOUR BETWEEN MENS ROOM 1149 AND SALE &
 ADMIN 1142, 1 HR BETWEEN BOARD RM #1 AND MEETING ROOM
 #2.
  
 ALL FIRE RATED WALLS, PARTITIONS, BARRIERS SHOWN ON THE
 PLAN WILL BE ENFORCED AS SUCH AT TIME OF INSPECTION.
  
 7. A1.4.01B, FITNESS ROOM TO COMPLY WITH FBC A 1004,
 REVISE TO SHOW COMPLIANCE.
  
 IF DETAILS SUCH AS SPECIFIC TYPES OF MACHINES PROPOSED
 IS NOT AVAILABLE AT THIS TIME, REVISE THE PLAN TO SHOW
 GENERAL COMPLIANCE. INCLUDE NOTES REGARDING COMPLIANCE.
 THIS PERMIT WILL BE ISSUED WITH PROVISO, ISSUED AT
 CONTRACTOR'S RISK, PROVIDE A DETAILED PLAN AT
 INSPECTION. SUBJECT TO FIELD INSPECTOR'S DISCRETION,
 FITNESS CENTER PLAN MAY BE REQUIRED TO BE SUBMITTED FOR
 PLAN REVIEW.
  
 8. A1.4.02A WALL BETWEEN CORRIDOR AND AREA "OPEN TO
 BELOW" LACKS A WALL TAG, FBC 107.
  
 9. S2.04B, A4.2.01, OTHER PAGES, PLAN SPECS LUMBER IN
 SEVERAL LOCATIONS (T&G SHEATHING, PLYWOOD, PRESSURE
 TREATED PLYWOOD, WOOD TRUSS). FBC 603.1, REVISE PLAN TO
 SPEC FRT OR REVISE PLAN INCLUDE EXCEPTION.
  
 10. S2.04BT SPECS LIGHT GAUGE METAL TRUSSES, S2.04
 NOTES SPECS WOOD TRUSSES FOR MANSARD. REVISE PLAN TO
 CLARIFY; CHECK ALL FOR CONSISTENCY, FBC 107. SEE ALSO
 A4.2.01.
  
 11. THRESHOLD BLDG., REQUIRED STATEMENT:
 FS553.79(7)(D), W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE ARCHITECT'S OR
 ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS
 COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRESAFETY STANDARDS AS DETERMINED BY
 THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND
 CHAPTER 633.
  
 SEE ALSO THRESHOLD REVIEW FOR ADDITIONAL REQUIREMENTS
 (SI AGREEMENT, RESUMES, ETC.).
  
 12. SOIL BEARING VALUES. THE TEST BY UNIVERSAL
 ENGINEERING SCIENCES REFERENCES THE TEST IS PRELIMINARY
 GEOTECHNICAL ENGINEERING REPORT BANYAN CAY- HOTEL
 PLEASE NOTE THE BORING SAMPLES TAKEN CH-1 AND CH-2 ARE
 SHOWN FOR THE CLUBHOUSE, THIS SOILS REPORT HAS NO
 BORINGS SHOWN IN THE REPORT FOR THE HOTEL. NOTE FOR THE
 TENNIS CLUB CENTER UP TO 6 FEET OF MUCK WAS ENCOUNTERED
 WITHIN THE BUILDING FOOTPRINT. PLEASE COMPLY WITH: 2014
 FBC-B 1803.3 BASIS OF INVESTIGATION.
 SOIL CLASSIFICATION SHALL BE BASED ON OBSERVATION AND
 ANY NECESSARY TESTS OF THE MATERIALS DISCLOSED BY
 BORINGS, TEST PITS OR OTHER SUBSURFACE EXPLORATION MADE
 IN APPROPRIATE LOCATIONS. ADDITIONAL STUDIES SHALL BE
 MADE AS NECESSARY TO EVALUATE SLOPE STABILITY, SOIL
 STRENGTH, POSITION AND ADEQUACY OF LOAD-BEARING SOILS,
 THE EFFECT OF MOISTURE VARIATION ON SOIL-BEARING
 CAPACITY, COMPRESSIBILITY, LIQUEFACTION AND
 EXPANSIVENESS.
  
 13. SHEET 019-S-4.10, PRESSURES MAY BE LOW; PROVIDE
 CALCULATIONS FBC B 1609. REVISE PLAN TO INCLUDE PITCH
 AND MEAN ROOF HEIGHT. WILL DESIGN PRESSURES SPECIFIED
 APPLY TO ALL ROOF AREAS, REGARDLESS OF PITCH? ROOF PLAN
 APPEARS TO INCLUDE ROOF AREAS OVER THE 4TH LEVEL, BUT
 OTHER ROOF AREAS ARE NOT INCLUDED - FOR EXAMPLE, THE
 PORTE COCHERE. REVISE PLAN TO INCLUDE ALL ROOF AREAS.
  
 14. SOME SECTION DETAIL MARKERS APPEAR TO BE LABELED
 INCORRECTLY AND DETAILS DO NOT CORRELATE WITH FLOOR
 PLANS; FOR INSTANCE, SEE SHEET S2.00A. DETAIL MARKERS
 REFERENCE PAGES S3.40, S3.41, UNABLE TO LOCATE; S4.08
 AND OTHER PAGES ALSO HAVE THIS ERROR. SEE SHEETS S3.42
 AND OTHER PAGES, UNABLE TO LOCATE THE SHEARWALL
 LOCATIONS ON THE PLAN, REVISE OR DIRECT.
  
 15. A1.8.01 AND OTHER PAGES PROVIDE A LEGEND FOR THE
 FLOOR PLAN NOTE (THE BOX IN THE MIDDLE OF EACH FLOOR
 PLAN). IT IS NOT CLEAR WHAT "P-1" MENAS. SOME AREAS
 HAVE A "?"; CLARIFY.
  
 16. SEE FBC A 209.2.1, 209.4, LABEL ALL PASSENGER
 LOADING ZONES ON THE PLAN, REVISE PLAN TO SHOW
 COMPLIANCE WITH REQUIREMENTS.
  
 17. FBC A 806, REVISE PLAN TO SHOW COMPLIANCE. SOME ADA
 ROOMS HAVE ACCESSIBILITY CLEAR FLOOR SPACE (4-1.5.02),
 OTHERS DO NOT (3-1.5.02).
  
 18. FBC 107, NO DETAILS FOR TUB, SHOWER, LAV, TOILETS,
 URINALS PROVIDED. SEE PLUMBING REVIEW; ALL ARE
 APPLICABLE FOR BUILDING REVIEW.
  
 19. FBC A 806, PROVIDE A DETAIL TO SHOW COMPLIANCE,
 ACCESSIBLE ROUTE TO GUEST ROOM BALCONY. THIS SHOULD
 CORRELATE WITH THE SLIDING GLASS DOOR PRODUCT APPROVAL.
 THE DETAIL ON A5.2.01 DOES NOT INCLUDE DIMENSIONS TO
 SHOW COMPLIANCE WITH FBC A 303. ALSO PROVIDE THE
 SLIDING GLASS DOOR PRODUCT APPROVAL.
  
 20. 4-A1.5.05, REVISE PLAN TO CLARIFY WHAT "ELEV #5"
 AND "ELEV #3" ARE.
  
 21. A1.2.02, THE RATED WALL REQUIRED BY FBC B 708.1 IS
 NOT CONTINUOUS FOR SOME ROOMS (ROOMS NOT NUMBERED, SEE
 LINES C8 THROUGH C10).
  
 22. COMPLIANCE WITH FBC 1509.6.4 (ROOFTOP EQUIPMENT)
 NOT CLEAR, REVISE PLAN TO CLARIFY.
  
 23. ADVISE AS TO WHERE THE DOOR MARKERS FOR THE UNITS
 CAN BE FOUND, FBC 107. LOCATION OF "BARN" DOORS IN THE
 UNITS IS NOT CLEAR.
  
 24. REVISE PLAN TO INCLUDE ASSEMBLIES FOR THE FIRE
 RATED ELEMENTS REQUIRED BY FBC B TABLE 601.
  
 25. SHEET A5.1.04 IS BLANK, FBC 107 PROVIDE INFORMATION
 INCLUDING PANIC HARDWARE FBC B 1008.1.10.
  
 26. BUILT IN BENCHES TO COMPLY WITH FBC A 903.
  
 27. DRESSING, FITTING AND LOCKER ROOMS TO COMPLY WITH
 FBC A 222, REVISE PLAN TO SHOW COMPLIANCE.
  
 28. SPA RECEPTION/ RETAIL DESK, ANY OTHER CHECK OUT
 AREAS, SEE FBC A 904 NOTE ON PLAN AND PROVIDE A DETAIL.
  
 29. CIVIL SHEETS USE NGVD29 VERTICAL DATUM. A0.0.02
 PROPOSES A FINISHED FLOOR OF 22'0' NAVD88. THERE IS A
 CONFLICT OF APPROXIMATELY 18"; REVISE TO BE CONSISTENT.
 NGVD29 IS RECOMMENDED AT THIS TIME.
  
 30. ARCHITECT'S TITLE BLOCK LACKS THE ARCHITECT
 BUSINESS NUMBER, REVISE TO INCLUDE, FS481, FAC 61G16.
  
 31. CIVIL, STRUCTURAL, AND ARCHITECTURAL (AND OTHER)
 SHEETS ARE NOT DIGITALLY SIGNED. A SHEETS APPEAR TO BE
 DIGITALLY SIGNED BUT LACK THE CERTIFICATE. PRIOR TO
 RESUBMITTAL, PLEASE DIGITALLY SIGN EACH SHEET. IF
 UNSURE AS TO ACCEPTABLE (PER FS471/FS481) FORMAT,
 PLEASE SEND TEST PAGES TO ME VIA EMAIL FOR PRELIMINARY
 REVIEW. FAILURE TO PROVIDE INDIVIDUALLY SIGNED PAGES
 WILL RESULT IN A SEPARATE SIGNATURE REVIEW AFTER ALL
 REVIEWS HAVE PASSED. THIS REVIEW MAY TAKE UP TO A WEEK
 TO COMPLETE. INDIVIDUALLY SIGNED PAGES IS STRONGLY
 ENCOURAGED IN ORDER TO TIMELY PROCESS THIS PERMIT.
 PLEASE FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS
 OPTIONS.
  
 32. IT IS NOT CLEAR WHICH OF THE ENGINEERING COMPANIES
 IN THE COMPANY BLOCK IS TO SERVE AS THE TITLE BLOCK FOR
 THE VARIOUS ENGINEERS (FMEP). ALSO, THE CERTIFICATE OF
 AUTHORIZATION IS LACKING, FS471, FAC61G15-23.
  
 33. OK
  
 34. SEE SIGNATURE REVIEW.
  
 35. SEE IMPACT FEE REVIEW.
  
 36. THIS PERMIT WILL BE ISSUED WITH PROVISOS:
  
 A. COMPLIANCE WITH ART IN PUBLIC PLACES ORDINANCE
 78-123 REQUIRED: MS. SYBILLE WELTER, 561-822-1515,
 [email protected]. MS. WELTER WILL ADVISE VIA EMAIL WHEN
 THIS IS COMPLETE.
  
 B. SEPARATE PERMITS REQUIRED. SUB PERMITS FOR
 MECHANICAL, ELECTRICAL, PLUMBING ARE REQUIRED. SEPARATE
 PERMITS (APPLICATION, FEES, PLANS, REVIEWS) REQUIRED
 FOR ALL OTHER ITEMS SUCH AS PARKING, SIGNAGE, ETC.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-10-16 Cont ID  
Sent By jpearson Date 2018-10-16 Time 14:00 Rev Time 0.00
Received By jpearson Date 2018-10-16 Time 14:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-08-24 Cont ID  
Sent By jpearson Date 2018-08-24 Time 12:29 Rev Time 0.00
Received By jpearson Date 2018-08-24 Time 12:29 Sent To  
Notes
2018-08-24 12:29:00REVIEWED PER PREVIOUS COMMENTS ONLY.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. REVISION SHOWS MAIN #1 AS 1200 AMPS. THE FEEDERS TO
 THIS MAIN ARE SHOWN AS 3 SETS OF 400KCMIL COPPER, WHICH
 HAS AN AMPACITY OF 1005 AMPS. PROVIDE CORRECTION. NEC
 240.4(C)
 2. NOTE 12 ON RISER DIAGRAM SHOWS THE GENERATOR AS A
 120/208 VOLT, 3 PHASE GENERATOR. HOWEVER, THIS
 GENERATOR IS SHOWN FEEDING 277/480 VOLT, 3 PHASE LOADS.
 PROVIDE CORRECTION. WPB FBC 107.2.1
 3. EXPANDED VIEW OF MAIN ELECTRICAL ROOM, IN THE
 EMERGENCY AREA, PLAN DOES NOT SHOW THE REQUIRED 4 FEET
 OF CLEARANCE BETWEEN PANELS AND ATS. PROVIDE
 CORRECTION. NEC 110.26(A)(1)
  
 ALL OTHER COMMENTS HAVE BEEN ADDRESSED SATISFACTORILY.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-04-30 Cont ID  
Sent By jleahy Date 2018-04-30 Time 16:33 Rev Time 0.00
Received By jleahy Date 2018-04-27 Time 09:29 Sent To  
Notes
2018-04-30 16:39:04FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED A RISER DIAGRAM SHOWING ALL OF THE FIREPUMP AND
 CONTROLER, PLEASE INDICATE THE SIZES HP RATING, WIRE
 SIZES, OVERCURRENT PROTECTION, ECT, ECT
  
 ARC FLASH MITIGATION REQUIRED ON MAINS PER 240.87
  
 FAULT CURRENT CALCLULATION PER 110.10 FOR THE SERVICE
 AND DOWNSTREAM PANELS.
  
 RISER SHOWS PANEL ISHB DIFFERENT THAN THE OTHER PANEL ?
 IS THIS A SPECIAL PANEL?

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-04-11 Cont ID  
Sent By vperez Date 2017-04-11 Time 09:18 Rev Time 0.00
Received By vperez Date 2017-04-11 Time 09:18 Sent To  
Notes
2017-04-11 09:18:36INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE
 LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR, ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE,
 WIRELESS SYSTEMS, ELEVATORS, KITCHEN HOOD SYSTEMS, ETC.
 A NOTE WILL SUFFICE.
 2. SHEET E0.0.02- PLEASE ADD A GENERAL NOTE TO SHEET TO
 INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE
 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND
 THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE
 LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL
 SUFFICE
 3. SHEET E0.0.02- ADD A NOTE TO MAINTAIN ALL ELECTRICAL
 EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE
 AND CITY REGULATORY AGENCIES.
 4. SHEET E0.0.02- PLEASE CORRECT ALL CODES APPLICABLE
 REFERENCES TO REFLECT ABOVE STATED. DELETE BROWARD AND
 INTERNATIONAL CODES. ADD WPB AMENDMENTS.
 5. NOTE THAT PLANS ARE NOT DIGITALLY SIGNED AND SEALED.
 FBC 107.3.5
 6. E1.3.01B- PLEASE PROVIDE EM LIGHTING FOR MAIN
 ELECTRICAL ROOM AND ELECTRICAL ROOMS. FBC 107.3.5
 7. ALL BALCONIES MUST HAVE A RECEPTACLE OUTLET, SEE ALL
 UNITS. NEC 210.52E3.
 8. PROVIDE A NOTE TO COMPLY WITH NEC 210.5-
 IDENTIFICATION FOR BRANCH CIRCUITS- A- GROUNDED
 CONDUCTOR PER NEC 200.6 AND UNGROUNDED CONDUCTORS PER
 NEC 210.5C1,2,3- APPLICATION, MEANS OF IDENTIFICATION
 AND POSTING OF IDENTIFICATION MEANS.
 9. PROVIDE A NOTE ON UNIT SHEETS TO INDICATE TAMPER
 RESISTANT RECEPTACLE REQUIRED PER NEC 406.13
 10. SHOW A MASTER SWITCH FOR ALL UNITS AT THE ENTRY PER
 FBC EC405.2.3 LIGHTING AND SWITCHED RECEPTACLE. SHOW
 COMPLIANCE.
 11. SHEET E-2.2.00- PROVIDE A NOTE INDICATING GFCI
 PROTECTION REQUIRED WITHIN 6FT OF EVERY SINK PER NEC
 210.8B5, AND FOOD PREPARATION ADJACENT AREAS.
 12. RISER DIAGRAM AND PANEL SCHEDULES SHEETS. PLEASE
 PROVIDE AVAILABLE FAULT CURRENT AVAILABLE AT THE FPL
 SERVICE. ATTACH TO DOCUMENTS LETTER FROM FLORIDA POWER
 & LIGHT INDICATING AIC. SHOW AIC CALCULATION BASED ON
 INFORMATION PROVIDED BY UTILITY FOR APPROVAL. NEC
 110.24 FBC 107.3.5
 13. AIC RATINGS REQUIRED TO BE SHOWN ON ALL
 PANELBOARDS. FBC 107.3.5
 14. PROVIDE ACTUAL VOLTAGE DROP CALCULATIONS NOT ONLY
 FOR FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7
 15. MAIN ELECTRICAL ROOMS MUST COMPLY WITH NEC
 110.26C3, REQUIRES PERSONNEL DOORS TO BE EQUIPPED WITH
 PANIC HARDWARE AND OPEN IN THE DIRECTION OF EGRESS. A
 NOTE WILL SUFFICE.
 16. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM
 TO INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 17. PLEASE CLARIFY FIRE PUMP SHOWN ON RISER DIAGRAM FOR
 A COMPLETE REVIEW. COULD NOT LOCATE WHERE IT IS
 LOCATED, AND LOCATION OF ATS/FP CONTROLLER. FBC 107.3.5
 18. PROVIDE INFORMATION ON DRAWINGS AND DATA SHEETS FOR
 LIGHTING CONTROL PANELS. CLARIFY COMPLIANCE WITH FBC
 ENERGY CONSERVATION.
 19. CLARIFY AS NO ELEVATOR MACHINE ROOMS ARE SHOWN TO
 COMPLY WITH NEC 620.23 A,B AND C.
 20. ADDRESS FIRE AND MECHANICAL COMMENTS RELATED TO
 ELECTRICAL.ADDITIONAL EXIT LIGHTS AND EM. PHOTOMETRICS
 FOR MINIMUM EGRESS LIGHTING LEVELS TO BE
 MAINTAINED.SHOW ADDITIONAL ELECTRICAL DEMAND FOR DUCT
 DETECTORS AND DAMPERS MISSING AND ROOFTOP ELECTRICAL
 RECEPTACLES FOR SERVICE OF EQUIPMENT IN AREA. NEC
 210.63, FBC 107.3.5
 21. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2018-09-12 Cont ID  
Sent By RRossano Date 2018-09-12 Time   Rev Time 1.00
Received By rrossano Date 2018-09-12 Time   Sent To I
Notes
2018-09-12 12:24:37UNDER REVIEW IN ENGINEERING.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2018-05-07 Cont ID  
Sent By shill Date 2018-05-07 Time 06:19 Rev Time 0.00
Received By shill Date 2018-05-07 Time 06:19 Sent To  
Notes
2018-05-07 06:19:37APPROVAL BY ENGINEERING REQUIRED
 ENGINEERING REVIEW WILL BE DONE VIA A FORMAL
 ENGINEERING SUBMITTAL
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2017-05-11 Cont ID  
Sent By shill Date 2017-05-11 Time 13:37 Rev Time 0.00
Received By shill Date 2017-05-11 Time 13:37 Sent To  
Notes
2017-05-11 13:38:02APPROVAL BY ENGINEERING REQUIRED
 ENGINEERING REVIEW WILL BE DONE VIA A FORMAL
 ENGINEERING SUBMITTAL
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2018-10-16 Cont ID  
Sent By scaldero Date 2018-10-16 Time 13:48 Rev Time 0.00
Received By scaldero Date 2018-10-16 Time 13:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-08-08 Cont ID  
Sent By scaldero Date 2018-08-08 Time 10:18 Rev Time 0.00
Received By scaldero Date 2018-08-08 Time 10:15 Sent To  
Notes
2018-08-08 10:18:23SEE COMMENTS FROM FIRE REVIEW ON 5/17/18.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-05-17 Cont ID  
Sent By pleduc Date 2018-05-17 Time   Rev Time 0.00
Received By pleduc Date 2018-04-25 Time 16:34 Sent To  
Notes
2018-05-17 13:37:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PREVIOUS COMMENTS OF FIRE PREVENTION APPEARED TO
 HAVE BEEN ADDRESSED.
  
 THIS APPROVAL DOES NOT SUPERSEDE THE RESPONSIBILITY TO
 MEET THE REQUIREMENTS OF ANYLLIFE SAFETY CODE AS THE
 CONSTRUCTION PROOJECT PROGESSES AND DETAILED FIRE
 INSPECTIONS FIND COMFLICTS.
  
 DEFICIENCIES FOUND IN CONFLICT WITH THE CODE SHALL
 REQUIRE CORRECTIONS OR MODICIFCATIONS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-24 Cont ID  
Sent By wjolin Date 2017-03-24 Time 11:01 Rev Time 0.00
Received By wjolin Date 2017-03-22 Time 16:16 Sent To  
Notes
2017-03-23 11:31:253200 NORTH CONGRESS AVENUE - HOTEL
 PERMIT #17020796
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 NO INFORMATION SUBMITTED FOR POOL, POOL DECK, WEDDING
 STAGE, CONCERT LAWN, EVENT TENT, PHASE II OR PARKING
 GARAGE. THESE AREAS HAVE NOT BEEN REVIEWED OR APPROVED
 AT THIS TIME.
  
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
 TEMPORARY CONSTRUCTION TRAILERS OR MODULAR BUILDINGS
 WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE
 FOLLOWING:
 PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PER NFPA 241 SECTION 8.7.2.3, WHERE UNDERGROUND WATER
 MAINS AND HYDRANTS ARE TO BE PROVIDED, THEY SHALL BE
 INSTALLED, COMPLETED, AND IN SERVICE PRIOR TO
 CONSTRUCTION WORK.
  
 PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL BE
 PROVIDED WITH CLEARANCES OF 7'-6" TO THE FRONT AND
 SIDES AND 4'-0" TO THE BACKSIDE OF THE STEAMER CAP.
  
 PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT
 ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO
 ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 36 TONS.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT
 LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
  
 PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE
 MARKED WITH FREESTANDING SIGNS READING, "FIRE LANE - NO
 PARKING BY ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL
 BE 12" X 18" WITH A WHITE BACKGROUND AND RED LETTERS
 AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE
 BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE
 TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART.
  
 SHEET A-0.0.02: APPLICABLE CODES SECTION INDICATES,
 "BROWARD COUNTY AMENDMENTS TO THE FLORIDA FIRE
 PREVENTION CODE."
  
 SHEET A-1.2.01: EGRESS PLAN DOES NOT SHOW ENOUGH DETAIL
 REGARDING ALL EXITS DISCHARGING TO A PUBLIC WAY.
 SEVERAL EXIT DISCHARGE APPEAR TO TERMINATE DIRECTLY
 OUTSIDE OF THE BUILDING AND DO NOT PROVIDE A MEANS OF
 EGRESS TO ACHIEVE A SAFE DISTANCE AWAY FROM THE
 BUILDING SUCH AS PRE-FUNCTION #1318, BALLROOM #2, AND
 SALE/ADMIN TO NAME A FEW.
  
 SHEET A-1.2.01: NEARLY HALF THE EXITS DISCHARGE ONTO
 THE POOL DECK IN LIEU OF A PUBLIC WAY. A LIFE SAFETY
 PLAN IS NEEDED FOR THE FIRST FLOOR AND POOL DECK IF THE
 DECK IS TO BE USED HOTEL OCCUPANT EGRESS. HOW WILL
 UNOBSTRUCTED EGRESS BE PROVIDED AND MAINTAINED ON THE
 POOL DECK LEADING TO A PUBLIC WAY? HOW DO THE
 ADDITIONAL LARGE ASSEMBLY SPACES (TIKI BAR, WEDDING
 STAGE, CONCERT LAWN, EVENT TENT AND PHASE II) AFFECT
 TOTAL EGRESS PLAN?
  
 SHEET A-1.2.01: NO FIRE PROTECTION RATING SHOWN AROUND
 FIRE PUMP ROOM.
  
 SHEET A-1.2.02: NO FIRE PROTECTION RATING SHOWN AROUND
 STAIR #3 (TYPICAL UPPER FLOORS) AND ELEVATOR SHAFT AT
 COLUMN INTERSECTION B/24.
  
 SHEET A-1.2.04 & SHEET M-1.3.04B: HOUSEKEEPING #4001
 NEEDS A TWO-HOUR FIRE RESISTANCE RATING AND 90 MINUTE
 FIRE RATED DOOR. WHERE THE GREASE DUCT SYSTEM CONNECTED
 TO THE IN-LINE EXHAUST FAN IS IN AN ENCLOSURE, THE
 SPACE OR ROOM IN WHICH THE EXHAUST FAN IS LOCATED SHALL
 HAVE THE SAME FIRE RESISTANCE RATING AS THE ENCLOSURE
 (NFPA 96 SECTION 8.1.3.6)
  
 SHEET A-1.3.02: PLANS INDICATE GLAZING WITH A FIRE
 RATING IN SECOND FLOOR CORRIDOR LOOKING DOWN INTO THE
 FIRST FLOOR LOBBY; HOWEVER, NO WALL OR GLAZING DETAILS
 FOR THIS ASSEMBLY WAS LOCATED.
  
 SHEET A-5.1.01: INDIVIDUAL DOORS IN SCHEDULE DO NOT
 INDICATE THE USE OF PANIC OR FIRE EXIT HARDWARE.
  
 SHEET A-5.1.04: SHEET IS BLANK.
  
 SHEET FP-0.0.00: COULD NOT LOCATE ANY OF THE FOLLOWING
 INFORMATION: YEAR OF STANDARD DESIGNED (NFPA 13, 14, 20
 ETC.0, HYDRANT FLOW TEST DATA, HAZARD AND DENSITY
 CLASSIFICATION OF EACH AREA, FIRE DEPARTMENT
 CONNECTION.
  
 SHEET FP-0.0.00: PLANS INDICATE, "100 PSI @ 500 GPM
 REQUIRED FOR CITY OF MIAMI."
  
 SHEET FP-1.3.01B: PER NFPA 24 SECTION 6.2.1, ALL
 CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 SHEET FP-1.3.01B: CONFIRM FIRE PUMP ROOM IS LARGE
 ENOUGH TO ACCOMMODATE THE FIRE PUMP, JOCKEY PUMP,
 CONTROL PANELS WITH TRANSFER SWITCH, DOMESTIC WATER
 BOOSTER PUMP AND ALL REQUIRED WORKING CLEARANCES.
  
 PLUMBING/FIRE PROTECTION: NEITHER THE FIRE PROTECTION
 DRAWINGS NOR THE PLUMBING DRAWINGS SHOW THE
 SPRINKLER/STANDPIPE SYSTEM DRAINS OR TIE INTO THE
 SANITARY OR SEWER SYSTEMS.
  
 SHEET M-1.3.04B: GREASE DUCT EXHAUST LOUVER IS LOCATED
 CLOSER THAN 10 FEET TO THE ADJACENT PERPENDICULAR
 CORRIDOR WALL.
  
 SHEET M-1.3.04B: HOUSEKEEPING #4001 NEEDS A TWO-HOUR
 FIRE RESISTANCE RATING AND 90 MINUTE FIRE RATED DOOR.
 WHERE THE DUCT SYSTEM CONNECTED TO THE IN-LINE EXHAUST
 FAN IS IN AN ENCLOSURE, THE SPACE OR ROOM IN WHICH THE
 EXHAUST FAN IS LOCATED SHALL HAVE THE SAME FIRE
 RESISTANCE RATING AS THE ENCLOSURE (NFPA 96 SECTION
 8.1.3.6)
  
 ELECTRICAL: INSUFFICIENT EXIT SIGNAGE THROUGHOUT
 BUILDING, ESPECIALLY THE FIRST FLOOR. NO EMERGENCY
 LIGHTING INDICATED INSIDE OR OUTSIDE THE BUILDING
 EXCEPT INSIDE THE EXIT STAIRS.
  
 SHEET E-1.4.01A: NO FIRE ALARM NOTIFICATION PROVIDED IN
 THE FOLLOWING LOCATIONS: BUILDING EXTERIOR, MEETING
 #1113, RESTROOM #1111, PANTRY FREEZER #1118, RESTROOM
 #1108 (ONE TOILET).
  
 SHEET E-1.4.01B: NO FIRE ALARM NOTIFICATION PROVIDED IN
 THE FOLLOWING LOCATIONS: KITCHEN #1129 (LARGER FREEZERS
 AND DRY STORAGE), SAUNA #1206, SAUNA #1224
  
 SHEET E-1.4.02: NO FIRE ALARM NOTIFICATION PROVIDED FOR
 THE LARGE OUTSIDE KING BALCONIES (TYPICAL UPPER
 FLOORS).
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2018-11-30 Cont ID  
Sent By gjohnson Date 2018-11-30 Time 14:31 Rev Time 0.00
Received By gjohnson Date 2018-11-30 Time 14:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2018-11-14 Cont ID  
Sent By gjohnson Date 2018-11-14 Time 10:46 Rev Time 0.00
Received By gjohnson Date 2018-11-07 Time 14:51 Sent To  
Notes
2018-11-14 10:47:094TH REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
 1. SHT. P-3.0.07 THE GAS RISER DIAGRAM IS LABELED
 PRESSURE 2-4 FL SOUTH. PLEASE CLARIFY WPB AMEND TO FBC
 107.2.1
 2. SHT. P-3.0.07 UNDER THE EQUIPMENT SCHEDULE #304 THE
 BTU LOAD IS ILLEGIBLE. PLEASE CLARIFY WPB AMEND TO FBC
 107.2.1
 3. SHT. P-3.0.07 UNDER THE EQUIPMENT SCHEDULE # 2011,
 2014 AND 1002 ARE NOT SHOWN ON THE RISER DIAGRAM.
 PLEASE CLARIFY WPB AMEND TO FBC 107.2.1
 4. BELOW THE EQUIPMENT SCHEDULE THERE IS A NOTE
 REFERENCING THE KITCHEN CONSULTANT?S DRAWINGS FOR
 EQUIPMENT LOCATION AND FINAL LOADS. FOR THE GAS RISER
 IT IS REQUIRED THAT THE CORRECT BTU LOAD BE INDICATED
 ON THE PLAN AND THEY SHALL MATCH THE KITCHEN
 CONSULTANTS DRAWINGS. PLEASE CLARIFY WPB AMEND TO FBC
 107.2.1.
 5. SHT. P-3.0.07 THE BTU LOAD ON THE RISER FOR THE
 BANQUET KITCHEN DETAIL #D DOES NOT MATCH THE TOTAL FROM
 WHEN I ADDED UP THE EQUIPMENT SCHEDULE. PLEASE CLARIFY
 WPB AMEND TO FBC 107.2.1.
 6. SHT. P-3.0.07 THE BTU LOAD ON THE A BRANCH OFF THE
 MAIN DOES NOT MATCH THE BTU LOAD ON THE ENLARGED
 ISOMETRIC #A . PLEASE CLARIFY WPB AMEND TO FBC 107.2.1.
 7. SHT. P-3.0.07 THE BTU LOAD ON THE C BRANCH OFF THE
 MAIN DOES NOT MATCH THE BTU LOAD ON THE ENLARGED
 ISOMETRIC #C . PLEASE CLARIFY WPB AMEND TO FBC 107.2.1.
 8. SHT. P-3.0.07 WHEN I TOTALED UP THE BTU LOADS FROM
 THE EQUIPMENT SCHEDULE IT WAS 4,783,000 THE TOTAL GAS
 LOAD UNDER THE 1ST STAGE GAS LOAD CALCULATION WAS
 4,624,000 PLEASE CLARIFY WPB AMEND TO FBC 107.2.1.
  
 PREVIOUS COMMENTS 2. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR PER THE FBC-2014
 FUEL GAS CODE SEC. 304. PLEASE PROVIDE COMBUSTION AIR
 CALC FOR
 THE KITCHEN APPLIANCES.
 RESPONSE: GAS WATER HEATER IS DIRECT VENT/INTAKE.
 PLEASE CONFIRM REQUIREMENT OF CALCULATION.
 PLEASE REFER TO KITCHEN CONSULTANT FOR KITCHEN
 EQUIPMENT INFORMATION.
 THIS RESPONSE DOES NOT COMPLY PLEASE PROVIDE COMBUSTION
 AIR CALCULATIONS FOR THE KITCHENS THEY SHALL BE
 INCLUDED IN THE GAS OR MECHANICAL PLANS.
  
 PREVIOUS COMMENT 4. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA
 58, AND FBC-2014 FUEL GAS SEC. 402.2 WE NEED THESE TO
 VERIFY BTU
 LOADS-IF THEY CAN NOT BE PROVIDED FOR PLAN REVIEW PLACE
 A
 NOTE ON THE PLAN TO BE ON JOBSITE FOR FIRST ROUGH
 INSPECTION.
 RESPONSE: PLEASE REFER TO KITCHEN EQUIPMENT CONSULTANT
 PLANS FOR REFERENCE.
 THE RESPONSE DOES NOT COMPLY THE KITCHEN CONSULTANTS
 PLANS ARE NOT INCLUDED IN SUBMITTAL AND WE REQUIRE THE
 SPECIFICATION FROM THE APPLIANCE MANUFACTURE NOT THE
 CONSULTANT.
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-09-11 Cont ID  
Sent By gjohnson Date 2018-09-11 Time 12:26 Rev Time 0.00
Received By gjohnson Date 2018-09-11 Time 10:30 Sent To  
Notes
2018-09-11 12:35:153ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS: PREVIOUS COMMENTS
  
 PARTIALLY COMPLIED 1. 1. SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS ALL CUT SECTIONS OF PIPE AND
 CORRESPONDING LENGTHS PER FBC-2014 FUEL GAS, SECS.
 402.4.1, 402.4.2. AND BTU LOAD OF EACH APPLIANCE. ALSO
 SHOW ALL VALVE DRIP LEGS AND REGULATORS REFER TO THE
 FBC-2014 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES
 402.4(1) THRU 402.4(37).
 PLEASE PROVIDE THE LENGTH OF EACH CUT SECTION OF PIPE.
 PLEASE SHOW BTU LOAD FOR EACH GAS APPLIANCE.THE NUMBERS
 ON THE ENLARGE BANQUET KITCHEN ISO DO NOT ALL MATCH THE
 GAS EQUIPMENT SCHEDULE.
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304. PLEASE PROVIDE
 COMBUSTION AIR CALC FOR THE KITCHEN APPLIANCES.
  
 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505. IN YOUR RESPONSE YOU NOTE VENT
 DETAILS ON SHT P-3.0.08 I COULD NOT LOCATE ANY VENT
 DETAILS ON THAT SHT PLEASE CLARIFY.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 WE NEED
 THESE TO VERIFY BTU LOADS-IF THEY CAN NOT BE PROVIDED
 FOR PLAN REVIEW PLACE A NOTE ON THE PLAN TO BE ON
 JOBSITE FOR FIRST ROUGH INSPECTION.
  
 2ND REVIEW COMMENTS: NOT COMPLIED
  
 1. SHT. P-3.0.08 ON THE GAS ISOMETRIC THE 2ND BRANCH
 UPSTREAM OF THE METER HAS IS LABELED AS MAIN KITCHEN
 SHT. P-1.5.07 WHICH LABELS IT AS THE BANQUET KITCHEN
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. WHAT IS THE 3/4" BRANCH WITH THE NOTE FIX TAG PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. WHAT IS THE 2" AT THE UPSTREAM END OF THE ISOMETRIC
 WITH THE TAG XXXMBH/L.F.=XX' PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 6. ON THE ENLARGED ISOMETRIC DRAWING PLEASE SHOW THE
 PRESSURE REGULATORS AND THE VALVES ALSO SHOW THE LENGTH
 AND SIZE OF THE PIPING BETWEEN THE REGULATOR AND THE
 APPLIANCE. PER WPB AMEND TO FBC 107.2.1
  
 7. PLEASE LABEL THE ENDS OF THE PIPE WHERE THEY
 CONTINUES. PER WPB AMEND TO FBC 107.2.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-05-07 Cont ID  
Sent By gjohnson Date 2018-05-07 Time 08:31 Rev Time 0.00
Received By gjohnson Date 2018-05-07 Time 08:31 Sent To  
Notes
2018-05-07 09:28:262ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS: PREVIOUS COMMENTS
  
 PARTIALLY COMPLIED 1. 1. SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS ALL CUT SECTIONS OF PIPE AND
 CORRESPONDING LENGTHS PER FBC-2014 FUEL GAS, SECS.
 402.4.1, 402.4.2. AND BTU LOAD OF EACH APPLIANCE. ALSO
 SHOW ALL VALVE DRIP LEGS AND REGULATORS REFER TO THE
 FBC-2014 FUEL GAS SECS. 401.8 THRU 402.6.1 AND TABLES
 402.4(1) THRU 402.4(37).
 PLEASE PROVIDE THE LENGTH OF EACH CUT SECTION OF PIPE.
 PLEASE SHOW BTU LOAD FOR EACH GAS APPLIANCE.THE NUMBERS
 ON THE ENLARGE BANQUET KITCHEN ISO DO NOT ALL MATCH THE
 GAS EQUIPMENT SCHEDULE.
  
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304. PLEASE PROVIDE
 COMBUSTION AIR CALC FOR THE KITCHEN APPLIANCES.
  
 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505. IN YOUR RESPONSE YOU NOTE VENT
 DETAILS ON SHT P-3.0.08 I COULD NOT LOCATE ANY VENT
 DETAILS ON THAT SHT PLEASE CLARIFY.
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 WE NEED
 THESE TO VERIFY BTU LOADS-IF THEY CAN NOT BE PROVIDED
 FOR PLAN REVIEW PLACE A NOTE ON THE PLAN TO BE ON
 JOBSITE FOR FIRST ROUGH INSPECTION.
  
 NEW COMMENTS:
  
 1. SHT. P-3.0.08 ON THE GAS ISOMETRIC THE 2ND BRANCH
 UPSTREAM OF THE METER HAS IS LABELED AS MAIN KITCHEN
 SHT. P-1.5.07 WHICH LABELS IT AS THE BANQUET KITCHEN
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. PROVIDE AN ENLARGED ISOMETRIC FOR RMAIN KITCHEN. PER
 WPB AMEND TO FBC 107.2.1
  
 3. PLEASE LABEL THE BRANCHES ON THE MAIN ISOMETRIC
 DRAWING TO MATCH THE PIPING ON THE ENLARGED ISOMETRIC
 DRAWINGS. PER WPB AMEND TO FBC 107.2.1
  
 4. WHAT IS THE 3/4" BRANCH WITH THE NOTE FIX TAG PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. WHAT IS THE 2" AT THE UPSTREAM END OF THE ISOMETRIC
 WITH THE TAG XXXMBH/L.F.=XX' PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 6. ON THE ENLARGED ISOMETRIC DRAWING PLEASE SHOW THE
 PRESSURE REGULATORS AND THE VALVES ALSO SHOW THE LENGTH
 AND SIZE OF THE PIPING BETWEEN THE REGULATOR AND THE
 APPLIANCE. PER WPB AMEND TO FBC 107.2.1
  
 7. SHT. A-1.4.01A IT IS SHOWING A VENT FREE GAS FIRE
 PLACE UNVENTED GAS APPLIANCES ARE PROHIBITED IN
 ASSEMBLY OCCUPANCY'S. PER FBC FG 621.4
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-04-21 Cont ID  
Sent By gjohnson Date 2017-04-21 Time 11:16 Rev Time 0.00
Received By gjohnson Date 2017-04-21 Time 11:16 Sent To  
Notes
2017-04-21 11:26:57 
  
 1ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS
 ALL CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. AND BTU LOAD
 OF EACH APPLIANCE. ALSO SHOW ALL VALVE DRIP LEGS AND
 REGULATORS REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
 5. SHT. P-3.0.08 ON NOTE FOR THE SIZING TABLES IT
 REFERRANCES 2010 FBC WE ARE UNDER 2014 5TH EDITION
 CLARIFY. WPB AMEND TO FBC 107.2.1
  
  
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2018-12-12 Cont ID  
Sent By dbattles Date 2018-12-12 Time 15:06 Rev Time 0.00
Received By dbattles Date 2018-12-06 Time 14:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status P Date 2018-11-14 Cont ID  
Sent By lmarchan Date 2018-11-14 Time 14:24 Rev Time 0.00
Received By lmarchan Date 2018-10-11 Time 09:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-01 Cont ID  
Sent By cpuell Date 2018-10-01 Time 13:08 Rev Time 0.00
Received By cpuell Date 2018-08-06 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-06-07 Cont ID  
Sent By lmarchan Date 2018-06-07 Time 13:39 Rev Time 0.00
Received By lmarchan Date 2018-04-17 Time 08:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-05-11 Cont ID  
Sent By shill Date 2017-05-04 Time 13:37 Rev Time 0.00
Received By shill Date 2017-03-17 Time 15:10 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-11-06 Cont ID  
Sent By shill Date 2018-11-06 Time 10:27 Rev Time 0.00
Received By shill Date 2018-11-06 Time 10:27 Sent To  
Notes
2018-11-06 10:27:34MU2017-15390
 $166,344.24 PAID
 REVIEWED UNDER 18090472 (STRUCTURE REVISION)

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-04-17 Cont ID  
Sent By shill Date 2017-04-17 Time 15:57 Rev Time 0.00
Received By shill Date 2017-04-17 Time 15:57 Sent To  
Notes
2017-04-17 16:00:12IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 THE PLANS ARE TO BE STAMPED AND THE RECEIPT PROVIDED.
 CONTACT 561-233-5025 FOR MORE INFORMATION
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2018-11-13 Cont ID  
Sent By ccole Date 2018-11-13 Time 12:43 Rev Time 0.00
Received By ccole Date 2018-11-06 Time 10:45 Sent To  
Notes
2018-11-13 12:47:27MECHANICAL PROVISOS:
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 EXHAUST HOODS, KITCHEN FIRE SUPPRESSION SYSTEMS, AND
 WALKIN COOLERS AND FREEZERS.
  
 2) INCLUDED WITH THE KITCHEN EXHAUST HOOD DRAWINGS
 SHALL BE: A) INSTALLATION DETAILS FOR THE MAKEUP AIR
 AND EXHAUST FANS AND DUCTS INCLUDING HOW THE ALL
 COMPONENTS WILL BE SUPPORTED INSIDE THE ROOF STRUCTURE.
 B) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE EXHAUST DUCT FIREWRAPPING. C)
 CLEARANCE DISTANCE MEASUREMENTS FOR THE GREASE EXHAUST
 TERMINATION TO VERIFY COMPLIANCE WITH REQUIRED
 CLEARANCES TO PARTS OF THE BUILDING- SECTION
 506.3.13.3. D) VERIFICATION THAT THE TEMPORATURE OF THE
 MAKEUP AIR DOES NOT EXCEED 10 DEGREES OF THE AIR
 TEMPERATURE IN THE KITCHEN- SECTION 508.1.1.
  
 3) DEFERRED SUBMITTALS:
  
 A) WIND LOAD ENGINEERING FOR INSTALLATION OF THE
 CHILLERS, PUMPS, AND OTHER ALL EXTERIOR MECHANICAL
 EQUIPMENT.
 B) MIAMI-DADE AND/OR FLORIDA PRODUCT APPROVALS FOR THE
 EXHAUST AND OUTDOOR AIR LOUVERS, INCLUDING
 MANUFACTURER'S SPECIFICATIONS.
 C) FIRE DAMPERS
 D) MOTORIZED DAMPERS.
 E) DUCT SMOKE DETECTORS.
 F) CHILLED WATER PIPING SPECIFICATIONS AND PIIPE
 INSULATIONS.
 G) FLAMEBAR DUCT INSTALLATION DETAILS.
 H) COMMISSSIONING REPORT AND ACKNOWLEDGEMENT LETTER
 FROM BUILDING OWNERSHIP.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2018-09-07 Cont ID  
Sent By ccole Date 2018-09-07 Time 11:04 Rev Time 0.00
Received By ccole Date 2018-09-07 Time 11:03 Sent To  
Notes
2018-09-07 11:32:543RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17020796
 9/7/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE MATCH THE GUEST ROOM FC SYSTEM
 IDENTIFICATIONS ON THE AC AND ENERGY CALCULATIONS, AND
 THE SCHEDULE ON SHEET M-0.0.02. EACH DOCUMENT
 IDENTIFIES THEM DIFFERENTLY WHICH MAKES OT DIFFICULT TO
 REVIEW FOR COMPLIANCE. IT APPEARS THAT MANY OF THE
 SYSTEMS AS THEY ARE SHOWN IN THE CALCULATIONS ARE BEING
 GROUPED TOGETHER BUT THERE IS NO EXPALNATION OF HOW
 THEY ARE BEING GROUPED- PLEASE CLARIFY.
  
 2) THE PREVIOUSLY REQUESTED COMBUSTION AIR CALCULATIONS
 FOR THE GAS-FIRED COOKING APPLIANCES WERE NOT PROVIDED.
  
 3) SHEET M-1.3.01B: THE VENTILATION CA;LCULATION FOR
 THE WOMEN'S LOCKER ROOM IS INCORRECTLY LISTED AT 170
 CFMS , HOWEVER 204 CFMS ARE REQUIRED.
  
 4) M-1.3.01B & M-1.4.01: IT APPEARS THAT RECIRCULATION
 OF THE AIR FROM THE MANI/PEDI ROOM IS BEING
 RECIRCULATED TO OTHER ROOMS AND SPACES VIA THE RETURN
 TRANSFER FROM THE ROOM INTO THE PLENUM WHICH IS
 PROHIBITED PER TABLE 403.3 FOOTNOTE B.
  
 5) M-1.3.01B & M-1.4.01: THE MANI/PEDI PLAN DOES NOT
 INDICATE THAT SOURCE CAPTURE SYSTEMS ARE TO BE
 INSTALLED AT EACH MANICURE TABLE AND PEDICURE CHAIR-
 TABLE 403.3 FOOTNOTE
  
 6) M-1.3.01B: VENTILATION IS REQUIRED FOR THE FIRE PUMP
 ROOM- SECTIONS 4.12.6 & 11.3.2.1 NFPA 20.
  
 7) M-1.3.01B: FIRE DAMPERS MISSING AT: A) 20X14 SUPPLY
 DUCT PENETRATING THE BOH CORRIDOR WALL. B) THE 30X14
 SUPPLY AND RETURN DUCTS PENETRATING MECH RM 1205 WALLS-
 SECTION 607.5.2.
  
 8) PROVIDE AN AC CONDENSATE PIPING PLAN AND RISER
 DRAWING- SECTION 307.
  
 9) PROVIDE UL APPROVED FIRESTOPPING SYSTEMS FOR THE
 CHILLED WATER PIPING AND CONDENSATE PIPING.
  
 10) REFER TO SECTION 3004.1 FBC-14 BUILDING AND
 INDICATE HOW THE ELEVATOR HOISTWAYS ARE BEING VENTED.
  
 11) REFER TO SECTIONS C408.1 & C408.2 FBC-14 ENERGY
 CONSERVATION: COMMISSIONING OF THE MECHANICAL AND
 ELECTRICAL POWER AND LIGHTING SYSTEMS IS REQUIRED.
  
 C408.2 MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION
 REQUIREMENTS.
 PRIOR TO PASSING THE FINAL MECHANICAL INSPECTION, THE
 REGISTERED DESIGN PROFESSIONAL SHALL PROVIDE EVIDENCE
 OF MECHANICAL SYSTEMS COMMISSIONING AND COMPLETION IN
 ACCORDANCE THE PROVISIONS OF THIS SECTION.
  
 CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE
 PROVISIONS FOR COMMISSIONING AND COMPLETION
 REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE
 PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER
 REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE
 GIVEN TO THE OWNER AND MADE AVAILABLE TO THE CODE
 OFFICIAL UPON REQUEST IN ACCORDANCE WITH SECTIONS
 C408.2.4 AND C408.2.5.
  
  
 ADVISORIES:
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 EXHAUST HOODS, KITCHEN FIRE SUPPRESSION SYSTEMS, WALKIN
 COOLERS AND FREEZERS, FIRE ALARM, FIRE SPRINKLER.
  
 2) INCLUDED WIH THE KITCHEN EXHAUST HOOD DRAWINGS SHALL
 BE: A) INSTALLATION DETAILS FOR THE MAKEUP AIR AND
 EXHAUST FANS AND DUCTS INCLUDING HOW THE ALL COMPONENTS
 WILL BE SUPPORTED INSIDE THE ROOF STRUCTURE. B)
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE EXHAUST DUCT FIREWRAPPING. C)
 CLEARANCE DISTANCE MEASUREMENTS FOR THE GREASE EXHAUST
 TERMINATION TO VERIFY COMPLIANCE WITH REQUIRED
 CLEARANCES TO PARTS OF THE BUILDING- SECTION
 506.3.13.3. D) VERIFICATION THAT THE TEMPORATURE OF THE
 MAKEUP AIR DOES NOT EXCEED 10 DEGREES OF THE AIR
 TEMPERATURE IN THE KITCHEN- SECTION 508.1.1.
  
 3) DEFERRED SUBMITTALS:
  
 A) WIND LOAD ENGINEERING FOR INSTALLATION OF THE
 CHILLERS, PUMPS, AND OTHER ALL EXTERIOR MECHANICAL
 EQUIPMENT.
 B) MIAMI-DADE AND/OR FLORIDA PRODUCT APPROVALS FOR THE
 EXHAUST AND OUTDOOR AIR LOUVERS, INCLUDING
 MANUFACTURER'S SPECIFICATIONS.
 C) FIRE DAMPERS
 D) MOTORIZED DAMPERS.
 E) DUCT SMOKE DETECTORS.
 F) CHILLED WATER PIPING SPECIFICATIONS AND PIIPE
 INSULATIONS.
 G) FLAMEBAR DUCT INSTALLATION DETAILS.
 H) COMMISSSIONING REPORT AND ACKNOWLEDGEMENT LETTER
 FROM BUILDING OWNERSHIP.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-05-08 Cont ID  
Sent By ccole Date 2018-05-08 Time 17:03 Rev Time 0.00
Received By ccole Date 2018-05-03 Time 15:30 Sent To  
Notes
2018-05-08 17:07:222ND REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17020796
 5/8/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 THIS FOLLOW-UP REVIEW IS BASED ON THE RESUBMITTED
 PLANS, DOCUMENTS, AND RESPONSE NARRATIVE BY THE
 ENGINEER OF RECORD. ALL 1ST REVIEW COMMENTS NOT
 COMPLETELY RESOLVED ARE LISTED BELOW IN THEIR ORIGINAL
 NUMERICAL ORDER.
  
  
 1) THE FOLLOWING LIST OF NEW UPLOADED PLAN SHEETS NEED
 TO BE ELECTRONICALLY SIGNED AND SEALED: M-1.3.01C,
 M-1.3.03A, M4.0.00, M-5.0.01, M-5.0.02, M-5.0.03,
 M-5.0.05
  
 1A) THE REVISED ENERGY CALCULATIONS ARE INDICATING
 CAPACITIES FOR AHU 3 & 5, AND OA-1 THAT DON'T MATCH THE
 SCHEDULE ON SHEET M-0.0.02. B) THE FC TYPICAL-345
 IDENTIFICATION AND THE NO. OF UNITS SHOWN IN THE ENERGY
 CALCULATIONS DOES NOT MATCH THE FC SCHEDULE- SHEET
 M-0.0.02. C) THE ENERGY CALCULATIONS DO NOT PROVIDE ANY
 HEATING COMPLIANCE DATA.
  
 4) THE 19.8 BTUH FC SYSTEMS SELECTED FOR THE GUEST
 ROOMS ARE OVERSIZED PER THE SUBMITTED AC CALCULATIONS
 WHICH SHOW ALL THE SYSTEMS CALCULATED AT 1-TON OR LESS-
 SECTION C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 10) THE REQUESTED ENLARGED FOOD SERVICE DRAWINGS AND
 EQUIPMENT SCHEDULE NOT PROVIDED. PLEASE NOTE THE
 SUBMITTAL PACKAGE FROM CHENEY INCLUDES A WOOD-FIRED
 GRILL WHICH MUST BE UL 2162 LISTED AND LABELED PER
 SECTION 917.1.
  
 11) THE REQUESTED COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES AND WATER HEATERS WERE NOT
 PROVIDED. PLEASE SEE SECTION 304 FBC-14 FUEL GAS AND
 COMPLY.
  
 14) THE REQUESTED FLEX DUCT SIZES WERE NOT PROVIDED.
  
 16) THE REQUESTED DUCT SMOKE DETECTOR SYMBOLS TO BE
 PLACED ON THE PLAN WERE NOT PROVIDED.
  
 17) THE REQUESTED EXHAUST VENTILATION AND AIR BALANCE
 CALCULATIONS FOR THE LOCKER ROOMS AND THE MANI-PEDI
 ROOM WERE NOT PROVIDED.
  
 A) THE NEW TOILET EXHAUST RISER FOR THE GUEST ROOMS ON
 SHEET M-3.0.002 INDICATES AN ERV WILL BE REQUIRED FOR
 THE SYSTEMS- SEE TABLE C403.2.6 FBC-14 ENERGY
 CONSERVATION AND REVISE THE PLANS.
  
 B) SPORTS LOCKER ROOMS ARE CALCULATED AT 0.50 CFMS PER
 SQ. FT. PER TABLE 403.3. ASHRAE 62.1-10 IS A STANDARD
 HOWEVER, PER FLORIDA STATURE 553, THE PLANS SHALL BE
 DESIGNED IN ACCORDANCE WITH THE FBC-14 MECHANICAL CODE.
 PLEASE REVISE THE CALCULATIONS AND EXHAUST SYSTEMS, AND
 INCLUDE AN AIR BALANCE CALCULATION THAT INCLUDES THE
 MAKEUP AIR.
  
 C) THE REQUESTED ENLARGED DRAWINGS FOR THE MANI-PEDI
 HVAC SYSTEM WAS NOT PROVIDED. PLEASE SEE TABLE 403.3
 AND FOOTNOTES B AND H. RECIRCULATION OF AIR FROM THE
 SPACE IS PROHIBITED AND A SOURCE CAPTURE SYSTEM MUST BE
 INSTALLED AT EACH MANICURE AND PEDICURE STATION. REVISE
 THE DRAWINGS, AND EXHAUST AND AIR BALANCE CALCULATIONS.
 THE CURRENT PLAN APPEARS TO INDICATE
  
 MAKEUP AIR FOR EXHAUST BEING TRANSFERRED FROM THE
 CORRIDOR. THIS IS NOT PERMITTED BECAUSE THE CORRIDOR IS
 NOT BEING DIRECTLY SUPPLIED WITH OUTDOOR AIR AT A RATE
 HIGHER THAN THE RATE OF MAKEUP AIR TAKEN FROM THE
 CORRIDOR- SECTION 601.2(1). THIS RESTRICTION ALSO
 APPLIES TO THE TRANSFERS AT THE ADJACENT LOCKER ROOMS
 AND RESTROOMS.
  
 D) SHEETS M1.301A & M1-301B: THERE ARE TRANSFER DUCTS
 SHOWN INTO THE CORRIDORS FROM ROOMS 1112, 1112B, 1113,
 AND 1114. PLEASE CLARIFY IF THESE ARE TRANSFERS INTO AN
 ABOVE CEILING PLENUM, OR DIRECTLY INTO THE CORRIDORS.
 INDICATE WITH DOTTED LINES THE AREAS OF ABOVE-CEILING
 PLENUM SPACES AND IDENTIFY THEM USING KEYED NOTE #1.
 PLEASE NOTE THAT CORRIDORS CANNOT BE USED AS
  
 RETURN DUCTS PER SECTION 601.2, HOWEVER THE CEILINGS
 ABOVE ARE PERMITTED UNDER SECTION 601.2.1.
  
 20) PROVIDE MIAMI-DADE NOA'S OR FLORIDA PRODUCT
 APPROVALS FOR THE EXHAUST AND O/A INTAKE LOUVERS. CAN
 BE A DEFERRED SUBMITTAL. PLEASE PROVIDE A LIST OF ALL
 DEFERRED SUBMITTALS ON THE PLANS OR IN THE DOCUMENTS.
  
 25) ACKNOWLEDGED THAN WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE CHILLER, PUMPS ETC. WILL BE A
 DEFERRED SUBMITTAL.
  
 26) LABEL THE GRAVITY DAMPERS AT THE GUEST ROOM FAN
 COIL UNITS, AND PROVIDE A SUBMITTAL FOR THE FAN-COIL
 UNITS. CAN BE DEFERRED.
  
 29) ACKNOWLEDGED THAT THE TOILET EXHAUST DUCTWORK WILL
 BE FLAMEBAR. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION DETAILS REVIEWED AND
 STAMPED BY THE EOR. CAN BE A DEFERRED SUBMITTAL.
  
 32 & 33) ACKNOWLEDGED THAT THE DISCHARGE LOCATIONS FOR
 THE KITCHEN EXHAUST FANS WILL BE IN COMPLIANCE WITH THE
 CLEARANCES REQUIRED UNDER SECTIONS 506.13.1 &
 506.3.13.3, AND THE PLANS AND DETAILS WILL BE REVIEWED
 UNDER SEPARATE PERMIT. A) SHEETS M1.3.01A & B, M1.3.02A
 & B, M1.3.03A & B, AND M1.3.04A & B: THE GREASE EXHAUST
 DUCTS FROM THE KITCHEN HOODS ARE NOT
  
 PERMITTED TO BE LOCATED IN THE SAME SHAFTS- SEE SECTION
 506.3.11. PLEASE NOTE THAT THE REQUIRED SHAFT FOR HOOD
 4 & 5 GREASE DUCTS IS NOT SHOWN ON THE SECOND FLOOR
 MECHANICAL PLAN SHEET M-1.3.02A.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-04-05 Cont ID  
Sent By ccole Date 2017-04-05 Time 12:58 Rev Time 0.00
Received By ccole Date 2017-04-03 Time 11:55 Sent To  
Notes
2017-04-05 12:58:381ST REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17020796
 4/3/17
  
 1) THE UPLOADED DIGITAL MECHANICAL PLANS, ENERGY AND AC
 CALCULATIONS REQUIRE ELECTRONIC SEALS AND SIGNATURES BY
 THE ENGINEER OF RECORD IN ACCORDANCE WITH SECTION
 471.025 FLORIDA STATUTES, AND SECTION 61G15-23.005
 FLORIDA ADMINISTRATIVE CODE.
  
 2) ADVISORY: SEPARATE PERMITS AND PLANS ARE REQUIRED
 FOR THE KITCHEN HOOD EXHAUST AND FIRE SUPPRESSION
 SYSTEMS, AND THE WALK-IN COOLERS AND FREEZERS.
 REGARDING THE KITCHEN HOODS PLEASE SEE SECTION 508.1.1
 FBC-14 MECHANICAL- MAKEUP AIR TEMPERATURE. THE CURRENT
 PLAN IS NOT IN COMPLIANCE.
  
 3) THE AC COOLING AND HEATING CALCULATIONS ARE
 INCORRECTLY SPECIFYING MIAMI AS THE LOCATION AND ORIGIN
 OF DESIGN DATA FOR THE PROJECT.
  
 4) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 GUEST ROOMS AND ALL OTHER HABITABLE ROOMS SERVED BY THE
 FAN COIL UNITS- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 5) REGARDING THE UPLOADED AC CALCULATIONS PLEASE NOTE
 THE TOTAL COOLING CAPACITIES FOR AHU?S 3 & 5 SHOWN IN
 THE SCHEDULE ON SHEET M-0.0.02- (68.6 & 63.3 MBH) DO
 NOT MATCH THE CALCULATED LOADS OF (169.3 & 127 MBH).
  
 6) REFER TO TABLE C403.2.3(7) FBC-14 ENERGY
 CONSERVATION: IT APPEARS THE EFFICIENCY CRITERIA FOR
 THE CHILLER SHOWN ON THE ENERGYGAUGE COMPLIANCE
 SUBMITTAL IS INCORRECT FOR AN AIR-COOLED CHILLER.
  
 7) SHEET M-0.0.0.1: PLEASE UPDATE THE SMACNA SECOND
 EDITION REFERENCE AND PROVIDE DUCT HANGER TABLES IN
 COMPLIANCE WITH THE 2005 THIRD EDITION.
  
 8) SHEET M-0.0.03: PLEASE UPDATE THE ASHRAE 62.1-2004
 REFERENCE AND PROVIDE VENTILATION RATES IN ACCORDANCE
 WITH THE CURRENT 2010 STANDARD IN EFFECT. PLEASE SEE
 TABLE 6-1 ASHRAE 62.1-2010, OR TABLE 403.3 FBC-14
 MECHANICAL AND PROVIDE THE VENTILATION RATES FOR THE
 GUESTROOMS.
  
 9) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE AIR
 HANDLERS AND FAN COIL UNITS- SECTION 307.
  
 10) PROVIDE ENLARGED KITCHEN AND FOOD SERVICE DRAWINGS.
  
 11) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED TO
 THE GAS-FIRE COOKING APPLIANCES AND WATER HEATERS AND
 PROVIDE CALCULATIONS- REFER TO SECTION 304 FBC-14 FUEL
 GAS. PROVIDE WATER HEATER VENTING DIAGRAMS THAT
 INDICATE THE TYPE AND SIZE OF THE VENTS, TOTAL VENT
 RUNS AND TERMINATION LOCATIONS.
  
 12) M-1.3.01A: LABEL THE EXHAUST RISER LOCATIONS FOR
 KEF-4 & 5.
  
 13) M-1.3.01A: MISSING FIRE DAMPERS- A) 8X8 DUCT
 PENETRATING THE UNISEX RESTROOM/BOARDROOM #1 WALL. B)
 30X14 DUCT AT CORRIDOR 1110/BANQUET PANTRY WALL.
  
 14) M-1.3.01A & B: PROVIDE THE FLEX DUCT SIZES ON THE
 PLAN.
  
 15) M-1.3.01A & B: SHOW THE LOCATIONS OF ALL REQUIRED
 ACCESS PANELS FOR ALL FAN COIL UNITS AND VAV BOXES
 LOCATED ABOVE HARD CEILINGS- SECTION 306.1.
  
 16) M-1.3.01A & B: PROVIDE DUCT SMOKE DETECTORS IN THE
 RETURN AIR SYSTEMS OF THE AHU'S- SECTION 606.2.1.
  
 17) M-1.3.01A & B: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE KITCHENS, THE TOILET AND
 BATHROOMS, THE LOCKER ROOMS, AND THE MANICURE/PEDICURE
 SPA- SEE TABLE 403.3. PROVIDE ENLARGED DRAWINGS OF THE
 EXHAUST SYSTEMS THAT INDICATE THE TYPES AND SIZES OF
 EXHAUST DUCTS, TOTAL EXHSAUST VENT RUNS, AND INLET AND
 OUTLET LOCATIONS- SEE TABLE 403.3 FOOTNOTE B AND H.
  
 18) M-1.3.01A & B: PROVIDE AIR BALANCE CALCULATIONS.
  
 19) M-1.3.01A & B: DEMAND CONTROLLED VENTILATION IS
 REQUIRED FOR THE DINING/LOUNGE, FITNESS, AND BALLROOMS
 1 & 2- REFER TO SECTION C403.2.5.1 AND PROVIDE A MEANS
 OF COMPLIANCE ON THE PLAN.
  
 20) M-1.3.01A & B: THE LOCATIONS AND REQUIRED CLEARANCE
 DISTANCES FOR O/A INTAKES AND EXHAUST OUTLETS SHALL BE
 IN COMPLIANCE WITH SECTIONS 401.4 AND 501.3.1. PLEASE
 PLACE NOTES OR SHOW CLEARANCE DISTANCE MEASUREMENTS ON
 THE PLAN TO VERIFY COMPLIANCE.
  
 21) M-1.3.01A: CLARIFY HOW O/A IS BEING PROVIDED TO
 AHU-5. IT APPEARS THE INLET AT MECHANICAL 11120 IS
 LABELED MAKEUP AIR.
  
 22) M-1.3.01B: MISSING FIRE DAMPERS FOR DUCTS
 PENETRATING A) CORRIDOR 1135/SECURITY-RECEIVING WALL.
 B) DUCT PENETRATING THE CORRIDOR 1157/F.O. ADMIN WALL.
  
 23) M-1.3.01B: LABEL THE O/A INLET FOR AHU-3.
  
 24) M-1.3.01C: PROVIDE AN ENLARGED DETAIL SHOWING THE
 UNDERGROUND CHILLED WATER PIPING RUNS FROM THE CHILLER
 AND PUMPS ETC. INTO THE BUILDING. INDICATE THE TYPE AND
 SIZE OF PIPING, TYPE AND THICKNESS OF INSULATION.
  
 25) M-1.3.01C: WIND LOAD ENGINEERING IS REQUIRED FOR
 ANCHORING THE CHILLER, THE PUMPS, AIR SEPARATOR,
 EXPANSION TANK, AND THE CHILLED WATER PIPING- SEE
 SECTION 301.15 . PLEASE SEE SECTION 1609 FBC-14
 BUILDING AND PROVIDE DETAILS AND DESIGN CRITERIA.
  
 26) M-1.3.02A, 2B, 3A, 3B, 4A, 4B: LABEL THE O/A
 INTAKES FOR THE FC UNITS, AND PROVIDE AUTOMATIC SHUTOFF
 DAMPERS FOR THE O/A DUCTS- SECTION C403.2.4.4 FBC-14
 ENERGY CONSERVATION.
  
 27) M-1.5.02, 03, 04, 05: PROVIDE RETURN AIR FOR THE FC
 UNITS IN THE GUESTROOMS, AND PROVIDE AN ENLARGED DETAIL
 SHOWING HOW ACCESS WILL BE PROVIDED FOR MAINTENANCE AND
 REPLACEMENT OF THE UNITS- SECTION 306.1.
  
 28) M-3.0.00: PROVIDE EITHER NOTES OR DETAILS ON THE
 RISER PLAN INDICATING THE TYPE OF O/A DUCTWORK,
 LOCATIONS OF FIRE DAMPERS ETC.
  
 29) PLEASE PROVIDE TOILET EXHAUST RISER DRAWINGS
 INCLUDING THE TYPES AND SIZES OF EXHAUST DUCTS,
 VERTICAL RUN LENGTHS OF SUB-DUCTS, AND EXHAUST CFMS.
  
 30) M-1.3.04A, 4B, 5A & 5B: PROVIDE WIND LOAD
 ENGINEERING FOR TIE-DOWN OF THE ROOFTOP DUCTWORK, THE
 TOILET EXHAUST OUTLETS, AND THE O/A INTAKE HOODS.
 PLEASE NOTE THAT FLORIDA PRODUCT APPROVALS AND/OR
 MIAMI-DADE NOA'S ARE REQUIRED FOR ANY MANUFACTURED
 EXTERIOR MECHANICAL EQUIPMENT SUPPORTS OR STANDS.
  
 31) M-1.3.05A, 5B: IT APPEARS THAT FLAMEBAR DUCTWORK IS
 MISSPELLED AS BAMEBAR- PLEASE CORRECT.
  
 32) M-1.3.04B: THE LOCATION OF THE EXHAUST OUTLETS FOR
 KEF- 1, 2 & 3 APPEAR TO BE NON-COMPLIANT WITH SECTION
 506.13.3 WHICH REQUIRES A 10' HORIZONTAL CLEARANCE
 DISTANCE FROM THE OUTLETS TO PARTS OF THE SAME OR
 CONTIGUOUS BUILDING. PLEASE SEE THE EXCEPTION UNDER
 THIS SECTION FOR FURTHER INFORMATION.
  
 33) M-1.3.05A: THE LOCATIONS OF THE EXHAUST OUTLETS FOR
 KEF-4 & 5 APPEAR TO BE NON-COMPLIANT WITH SECTIONS
 506.3.13.1 & 506.3.13.3. PLEASE PROVIDE CLEARANCE
 DISTANCE MEASUREMENTS. PLEASE NOTE THAT ADDITIONAL
 COMMENTS REGARDING THE KITCHEN COOKING EXHAUST SYSTEMS
 MAY OCCUR AFTER COMPLETE PLANS AND SPECIFICATIONS ARE
 SUBMITTED FOR REVIEW UNDER SEPARATE PERMIT.
  
 34) INDICATE HOW ACCESS IS BEING PROVIDED FOR
 SERVICEABLE MECHANICAL EQUIPMENT LOCATED ON THE
 BUILDING ROOFTOPS (I.E. EF-4-1, EF-5-1, KEF-4 & 5)-
 SECTION 306.5. ADDITIONALLY PLEASE NOTE THAT ACCESS
 SHALL NOT REQUIRE WALKING ON ROOFS WITH A SLOPE GREATER
 THAN 4 UNITS VERTICAL IN 12 HORIZONTAL.
  
 35) PROVIDE FL. PRODUCT APPROVALS AND/OR MIAMI-DADE
 NOA'S FOR THE O/A INTAKE AND EXHAUST OUTLET LOUVERS.
  
 36) PROVIDE APPROVED PRODUCT SUBMITTAL DOCUMENTS FOR
 THE FLAMEBAR DUCT, THE MOTORIZED DAMPERS, AND THE CO2
 SENSORS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-11-30 Cont ID  
Sent By gjohnson Date 2018-11-14 Time 08:44 Rev Time 0.00
Received By gjohnson Date 2018-11-30 Time 14:29 Sent To  
Notes
2018-11-14 08:45:11PLUMBING PROVISOO:
  
 1. SHT. P-3.0.01 IN PROJECT DOX IS LABELED RISER
 DIAGRAM GRAVITY 2-4 FL NORTH THE PLAN SHEET IS THE
 RISER DIAGRAM 1ST FL SOUTH PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 2. SHT. P- 3.0.03 IN PROJECT DOX IS LABELED RISER
 DIAGRAM GRAVITY 2-4 FL SOUTH THE PLAN SHEET IT PLUMBING
 RISER PRESSURE 1ST FL SOUTH PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 3. SHT. P-3.0.04 IN PROJECT DOX IS LABELED RISER
 DIAGRAM PRESSURE 1ST FL NORTH THE PLAN SHEET IS THE
 SOUTH SIDE RISERS PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 4. SHT P-1.3.01B LABEL THE SOIL STACKS IN THESE ROOMS
 TO MATCH SANITARY ISOMETRIC SOME ARE NOT LABELED SOME
 ARE LABELED AS WCO THE FOLLOWING ROOMS MAIN ELECTRICAL
 1151, NEXT TO CORRIDOR 1138, IN FRONT OF LIQUOR ROOM
 1129D, 1137, 1221 TOILET STALL, 223 TRIPLE SINK. . PER
 WPB AMEND TO FBC 107.2.1
 5. SHT. P-3.0.02A ON THE LEFT SIDE OF THE ISOMETRIC
 THERE IS A SOIL STACK LABELED S30 I COULD NOT FIND THAT
 RISER ON THE FLOOR PLAN PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
 6. SHTS. P-3.0.01 AND P-3.0.02 ARE THE SAME DRAWING
 JUST DIFFERENT VERSIONS BOTH ISOMETRICS HAVE SOIL
 STACKS THAT ARE NOT LABELED AND FIXTURES THAT ARE NOT
 LABELED THESE ISSUES SHALL BE CLEARED UP BEFORE A
 PLUMBING PERMIT CAN BE ISSUED.
 7. SHTS. P-1.3.02A AND B THESE SHEETS WERE JUST
 UPLOADED TO SHOW THE CONDENSATE DRAIN IT APPEARS THAT
 THEY ARE SHOWING THE UNDERGROUND PIPING ON THE SECOND
 FLOOR IT SHOULD BE SHOWN ON THE 1ST FLOOR. PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
 8. SHT. P-3.0.08 THE CONDENSATE ISOMETRIC DRAWING NORTH
 SIDE IS LABELED AS THE NATURAL GAS RISER . PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-09-11 Cont ID  
Sent By gjohnson Date 2018-09-11 Time 08:23 Rev Time 0.00
Received By gjohnson Date 2018-09-04 Time 12:14 Sent To  
Notes
2018-09-11 10:30:43FBC 2014 5TH EDITION
  
 3RD REVIEW PLUMBING COMMENTS:
  
 1. PREVIOUS COMMENT #12 PARTIALLY COMPLIED PLEASE
 CORRECT THE FOLLOWING. PER WPB AMEND TO FBC 107.2.1
 A) SHT. P-1.3.01A I CAN NOT FIND THE SOIL STACK FOR S8,
 S3, S2.
 B) SHT. P-3.0.00 SOIL STACK N6, N7, N8 ARE NOT LABELED
 TO MATCH THE ENLARGED ISOMETRICS S#
 C) SOIL STACK N6 APPEARS TO BE LABELED WCO ON SHT.
 P-1.3.01A
 D) SHT. P-1.3.01A PLEASE LABEL THE SOIL STACKS BETWEEN
 GRID LINES 16 +14 TO MATCH THE ISOMETRICS.
 E) SHT. P-3.0.00 PLEASE LABEL ALL STACKS IN THE AREA OF
 SOIL STACKS N7 + N8
  
 2. SHT. P-3.0.01 AND SHT. P-3.0.02 THESE ISOMETRIC
 DRAWINGS SEEM TO BE INCOMPLETE PLEASE LABEL THE ALL
 FIXTURES , LABEL THE SANITARY STACKS DOWN, SOME OF THE
 SS DON'T SHOW ANY BRANCHES SUCH AS S5,7,8,9. THERE ARE
 PIPES SHOWN THAT DON'T CONNECT AND ARE NOT LABELED IT
 SEEMS THAT SOME OF THE FIXTURES WERE LABELED FCO PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. P3.0.02 THIS ISOMETRIC DRAWING IS TO CONGESTED
 TO DETERMINE CODE COMPLIANCE PLEASE EXPAND AND CLOUD
 AREAS AND LABEL TO COINCIDE WITH ENLARGED DRAWINGS. PER
 WPB AMEND TO FBC 107.2.1
  
 4. SHT. P-1.5.05 PLEASE LABEL ALL PLUMBING FIXTURES ON
 THE WATER AND SANITARY ISOMETRICS.. PER WPB AMEND TO
 FBC 107.2.1
  
 5. SHT. P 3.0.05 THE ISOMETRIC APPEARS TO BE INCOMPLETE
 PLEASE LABEL THE FIXTURE, BRANCHES AND NOTE WHERE
 PIPING CONTINUES. PER WPB AMEND TO FBC 107.2.1
  
 6. SHT. P-1.3.01B PLEASE LABEL THE SOIL STACKS TO MATCH
 THE ISOMETRICS AND LABEL THE GREASE, SANITARY LINES.
 PER WPB AMEND TO FBC 107.2.1
  
 7. PREVIOUS COMMENT #3 SHT. P-1.5.10 THE ENLARGED
 SANITARY ISOMETRIC IS MISSING PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-05-08 Cont ID  
Sent By gjohnson Date 2018-05-08 Time 09:03 Rev Time 0.00
Received By gjohnson Date 2018-05-04 Time 12:22 Sent To  
Notes
2018-05-08 12:31:122ND REVIEW
 FBC 2014 5TH EDITION
 PERMIT# 17020796
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
  
 !!!! IN ORDER TO TO EXPIDITE AN APPROVAL FOR THIS
 PERMIT I SUGEST A MEETING BE SCHDULED TO GO OVER THE
 PLAN PLEASE CONNTACT ME @ 561-805-6711 !!!
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED SEE
 NEW COMMENTS
  
 10. PLEASE PROVIDE SLOPE OF PIPE ON RISER DIAGRAMS. PER
 FBC PL 704.
  
 12. PLEASE LABEL THE STACKS ON THE RISER TO MATCH THE
 FLOOR PLAN, WATER AND SANITARY. PER WPB AMEND TO FBC
 107.2.1
  
 17. SOME OF THE SOIL STACK ARE NOTE SIZED OR LABELED
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 24. SHT. P-3.0.03 AND P-3.0.01 SHOW BRANCH LINES FOR
 EACH UNIT AND SHOW FLOOR LEVEL. PER WPB AMEND TO FBC
 107.2.1
  
 NEW COMMENTS:
  
 1. ALL THE ACCESSIBILITY SHALL COMPLY WITH FLORIDA
 BUILDING CODE ACCESSIBILITY 2014 5TH EDITION PLEASE
 NOTE ON THE PLAN. PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. P-3.0.05 THE 1" HOT WATER RECIRCULATION LINE
 DOES NOT SHOW UP ON THIS SHEET PLEASE CLARIFY. PER FBC
 PL 607.2
  
 3. SHT. P- 1.5.10 THE SANITARY PIPING DID NOT SHOW UP
 ON THIS SHEET PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. SHT. P-3.0.00 AND P-3.0.02 PLEASE SHOW THE SIZE AND
 SLOPE ON THE ISOMETRIC WE NEED THIS TO CHECK SIZING THE
 TABLE THAT WAS PROVIDED DOES NOT SPECIFY THE SLOPE IT
 ONLY GIVES A MINIMUM THE SIZING TABLE FBC PL TABLE
 710.1(1) USES SPECIFIC SLOPE TO SIZE THE PIPE. PER WPB
 AMEND TO FBC 107.2.1
  
 5. SHT. P-1.1.00 THE SOUTH GREASE INTERCEPTOR DID NOT
 SHOW UP ON THE SHEET IT IS ALSO MISSING THE GREASE AND
 SANITARY PIPING PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 6. SHT. P-3.0.02 TWOWAY CLEANOUTS ARE REQUIRED BETWEEN
 EACH INTERCEPTOR PLEASE SHOW ON PLAN. PER WPB AMEND TO
 FBC 107.2.1
  
 7. ON THE SANITARY ISOMETRIC DRAWINGS GOING FROM THE
 FIRST FLOOR TO THE 2ND, 3RD, AND 4TH FLOOR SOME OF THE
 ID TAGS ARE NOT MATCHING UP SOME ARE MISSING AND ON THE
 DRAWING FOR THE UPPER FLOOR IT APPEARS THE BRANCHES ARE
 MISSING THESE ISOMETRIC DRAWING ARE TO CONFUSING TO
 DETERMINE CODE COMPLIANCE PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
  
 8. THE FLOOR PLANS ARE MISSING THE ID TAGS TO MATCH UP
 THE SANITARY STACKS TO THE ISOMETRIC DRAWINGS PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 9. IN YOUR RESPONSE TO COMMENT #21 YOU REFER TO DETAIL
 ON SHT. P-4.0.04 THIS SHEET IS MISSING FROM THIS
 SUBMITTAL PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 10. SHT. P- 1.4.07 PLEASE REMOVE THE GAS ISOMETRIC FROM
 THE WATER ISO IT SHOULD BE ON SHT. P-3.0.08 AND LABEL
 ALL FIXTURE SOME ARE MISSING LABELS. PER WPB AMEND TO
 FBC 107.2.1
  
 11. SHT. P-3.0.07 PLEASE LABEL ALL THE FIXTURES AND
 BRANCHES FOR THE UNITS ALSO SHOW THE SIZE ON ALL THE
 PIPING. PER WPB AMEND TO FBC 107.2.1
  
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-21 Cont ID  
Sent By gjohnson Date 2017-04-21 Time 11:14 Rev Time 0.00
Received By gjohnson Date 2017-04-19 Time 09:42 Sent To  
Notes
2017-04-21 11:15:071ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. A1.9.01 PLEASE SHOW CLEAR FLOOR SPACE FOR
 ACCESSIBLE URINAL COMPLYING WITH FBC ACC 605.3
 2. PLEASE SHOW COMPLIANCE FOR SEATS, CONTROLS, GRAB
 BARS, CLEAR FLOOR SPACE, SIZES PER FBC ACC 607 TUBS AND
 608 SHOWERS.
 3. PROVIDE ELEVATIONS AND CLEAR FLOOR SPACE FOR
 ACCESSIBLE GUEST BATHROOMS. PER FBC ACC 806.2.4
 4. SHT. A-1.5.02 DETAILS 3 AND 4 GUESTROOM DOUBLE 6 AND
 7 SHOW THE SAME ROOM NUMBERS PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 5. PLEASE PROVIDE ENLARGED FLOW PLANS FOR ACCESSIBLE,
 KING W/SHOWER RM # 3315 AND DOUBLE W/SHOWER RM# 3313
 PLEASE INCLUDE DIMENSIONS FOR SHOWER. PER WPB AMEND TO
 FBC 107.2.1
 6. SHT. A-1.5.02 DETAIL 3 DOUBLE 6 THE LAVATORY TOP IS
 ENCROACHING INTO THE 60? CLEAR FLOOR SPACE OF TOILET.
 PER FBC PL 604.3.1
 7. SHT. P-4.0.01 FOR THE FIRE ASSEMBLY?S, PROVIDE
 MANUFACTURE AND STANDARD THEY MEET SUCH AS UL. PER WPB
 AMEND TO FBC 107.2.1
 8. PROVIDE TYP. WATER RISER FOR GUEST UNIT BATHROOMS.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
 9. A CLEAN OUT IS REQUIRED AT THE BASE OF EACH SOIL OR
 WASTE STACK. PER FBC PL708.3.4
 10. PLEASE PROVIDE SLOPE OF PIPE ON RISER DIAGRAMS. PER
 FBC PL 704.
 11. PROVIDE DFU LOAD ON STACKS AND BUILDING DRAIN. PER
 WPB AMEND TO FBC 107.2.1
 12. PLEASE LABEL THE STACKS ON THE RISER TO MATCH THE
 FLOOR PLAN, WATER AND SANITARY. PER WPB AMEND TO FBC
 107.2.1
 13. SHT. P-4.0.00 DETAIL # 2 SHOWS DRAIN FROM SUMP PUMP
 DRAINING TO THE STORM DRAIN IT IS ALSO SHOWN DUMPING
 INTO SANITARY PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 14. SHT. P-1.1.00 THE GREASE TRAP CALCULATION THAT WERE
 USED ARE FOR ESTABLISHMENTS WITH COMMERCIAL KITCHENS
 THIS APPLICATION SHALL BE FOR RESTAURANTS IT?S A
 DIFFERENT CALCULATION USING NUMBER OF SEATS AND HOURS
 OF OPERATION. PER FBC PL 1003.2
 15. LABEL ALL FIXTURES ON RISER DIAGRAMS. PER WPB
 AMEND TO FBC 107.2.1
 16. P-3.0.02 THE BRANCH DRAIN FOR THE FLOOR DRAIN AND
 LAVS IN MEN?S BATHROOM #1149 SHALL NOT ROLL UP OVER THE
 8" BUILDING DRAIN YOU CAN ROLL THE BRANCH DRAIN FOR THE
 WHOLE GAIN BATHROOM UP TO CLEAR THE BUILDING DRAIN MAIN
 TRUNK LINE. PER FBC PL 901.2.1
 17. SOME OF THE SOIL STACK ARE NOTE SIZED OR LABELED
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 18. PLEASE PROVIDE KITCHEN EQUIPMENT PLAN AND SCHEDULE
 FOR #1129, #1118 AND #1119. PER WPB AMEND TO FBC
 107.2.1
 19. PROVIDE PLUMBING FLOOR PLAN WITH THE SOIL STACKS
 LABELED TO MATCH RISER DIAGRAM. FOR FIRST FLOOR. PER
 WPB AMEND TO FBC 107.2.1
 20. HORIZONTAL DRY VENTS ARE PROHIBITED BELOW FLOOD
 LEVEL RIM OF FIXTURES I FOUND A FEW IN THE KITCHEN,
 RETAIL COFFEE AND THE BAR ALSO IN THE COUPLE?S SUITE ON
 THE TUB DRAIN. PER FBC PL 905.3/ 905.4
 21. PROVIDE TRAP PRIMERS ON ALL FLOOR DRAINS. PER FBC
 PL 1002.4
 22. SHT. P-1.3.01B AND P-1.4.01B SHOWS A SINGLE
 DRINKING FOUNTAIN IN FITNESS AREA, TWO DRINKING
 FOUNTAINS ARE REQUIRED. PER FBC ACC 211.2
 23. SHT. P-1.4.01B AND P-3.0.06 WATER PIPING FOR
 DRINKING FOUNTAIN IN FITNESS AREA IS NOT SHOWN PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
 24. SHT. P-3.0.03 AND P-3.0.01 SHOW BRANCH LINES FOR
 EACH UNIT AND SHOW FLOOR LEVEL. PER WPB AMEND TO FBC
 107.2.1
 25. SHT. P-3.0.07 SHOWS UNITS 3309 AND 3314 PROVIDE
 RISER FOR 4TH FLOOR WITH THESE UNITS REMOVED. PER WPB
 AMEND TO FBC 107.2.1
 26. PROVIDE WATER RISERS FOR BOTH KITCHENS, BAR, RETAIL
 COFFEE AND SERVICE PER WPB AMEND TO FBC 107.2.1EA.
 27. SHT. P-4.0.00 THE GAS WATER HEATER DETAIL DOES NOT
 MATCH THE RISER ON SHT. P3.0.07 PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
 28. SHT. P-4.0.00 THE GAS WATER HEATER DETAIL SHOWS A
 110 DEG. AND 140 DEG. PIPE BUT THE RISER DOES NOT A MIN
 OF 110 DEG IS REQUIRED IN THE KITCHENS HOW WILL THIS BE
 ACCOMPLISHED PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 29. SHT. P.3.0.02 THE RISER IS MISSING THE DRAIN FOR
 THE ACCESSIBLE SHOWERS IN THE MEN?S AND WOMEN?S LOCKER
 ROOM PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 30. PROVIDE THE DIMENSION FOR ALL SHOWERS IN THE LOCKER
 ROOMS. PER WPB AMEND TO FBC 107.2.1
 31. ALL PLAN SHEETS SHALL BE DIGITALLY SIGNED BY THE
 DESIGN PROFESSIONAL RESPONSIBLE FOR DRAWING. PER FAC
 61G1-16.005
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2017-04-24 Cont ID  
Sent By shill Date 2017-04-24 Time 07:21 Rev Time 0.00
Received By shill Date 2017-04-24 Time 07:21 Sent To  
Notes
2017-04-24 07:23:22ROOF INFORMATION NOT SUBMITTED
 PRIOR TO INSTALLATION, A ROOF PERMIT IS REQUIRED.
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD ARE TO
 BE SUBMITTED. ENGINEERING, IF APPLICABLE, AND ASSEMBLY
 PROPOSED IS TO BE PROVIDED FOR REVIEW.
  
 ROOF ASSEMBLY TO COMPLY WITH THE PRESSURES ON SHEET
 S4.10.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2018-12-13 Cont ID  
Sent By dbattles Date 2018-12-12 Time 16:16 Rev Time 0.00
Received By dbattles Date 2018-12-12 Time 16:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2018-12-12 Cont ID  
Sent By dbattles Date 2018-12-12 Time 15:02 Rev Time 0.00
Received By dbattles Date 2018-12-12 Time 14:27 Sent To  
Notes
2018-12-12 15:06:12PLEASE UPLOAD THESE TWO SHEETS WITH DIGITAL SIGNATURE.
 120 - S2.03 B-PT
 121 - S2.03 B-R
  
 SHEETS S-3.00 THRU S3.06 WILL BE DELETED SINCE THEY
 WEREN'T RE-LOADED WITH DIGITAL SIGNATURE, AND THOSE
 DRAWINGS ARE NOT REFERENCES BY ANY OTHER STRUCTURAL
 DRAWING.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2018-12-04 Cont ID  
Sent By shill Date 2018-12-04 Time 17:31 Rev Time 0.00
Received By shill Date 2018-12-04 Time 17:09 Sent To  
Notes
2018-12-04 17:16:44THE FOLLOWING SHEETS ARE NOT DIGITALLY SIGNED:
  
 S2.00
 S2.00A
 S2.00B
 S2.01
 S2.01A
 S2.01B
 S2.02
 S2.02A PT
 S2.02A R
 S2.02B PT
 S2.02B R
 S2.03
 S2.03A PT
 S2.03A R
 S2.06
 S2.06A
 S2.06B
 S3.00
 S3.01
 S3.02
 S3.03
 S3.04
 S3.05
 S3.06
 S3.09
 S7.00
 S7.01
 S7.02
 S7.03
 S7.04
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-11-14 Cont ID  
Sent By shill Date 2018-11-14 Time 11:03 Rev Time 0.00
Received By shill Date 2018-11-14 Time 11:03 Sent To  
Notes
2018-11-14 11:03:54SIGNATURES WILL BE VERIFIED AFTER ALL REVIEWS HAVE
 PASSED
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-05-04 Cont ID  
Sent By shill Date 2018-05-04 Time 07:00 Rev Time 0.00
Received By shill Date 2018-05-04 Time 06:06 Sent To  
Notes
2018-05-08 12:59:205/8/18 THESES PLUMBING SHEETS ARE MISSING THE DIGITAL
 SIGNATURE THE DIGITAL SIGNATURES ARE INVALID ON
 PLUMBING PAGES THEY SHALL COMPLY WITH FAC 61G15-23.003
 P-1.3.00
 P- 1.5.10
 P-4.0.02
 P-4.0.01
 P-1.5.09
 P-1.3.05B
 P-1.3.05A
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
2018-05-04 07:00:38****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE MAJORITY OF A SHEETS ARE NOT DIGITALLY SIGNED
 AND SEALED. A0.0.01, BUT EVERY OTHER A SHEET CHECKED IS
 NOT SIGNED AND SEALED, FS481, FOR EXAMPLE:
 A1.1.05, A1.2.02, A1.4.02B, A1.5.05, A1.7.03B, TOO MANY
 TO LIST
  
 2. SURVEY NOT SIGNED & SEALED; APPLICANT CAN PROVIDE A
 PAPER ORIGINAL IF SURVEYOR DOES NOT HAVE A DIGITAL
 SEAL.
  
 3. S SHEETS CHECKED ARE DIGITALLY SIGNED AND SEALED -
 OK. NEW SHEETS SUBMITTED FOR A THIRD REVIEW CYCLE NEED
 VERIFICATION, IF APPLICABLE.
  
 4. FP SHEETS ARE NOT DIGITALLY SIGNED AND SEALED,
 FS471.
  
 5. M SHEETS CHECKED ARE DIGITALLY SIGNED AND SEALED -
 OK. NEW SHEETS SUBMITTED FOR A THIRD REVIEW CYCLE NEED
 VERIFICATION, IF APPLICABLE.
  
 6. P SHEETS CHECKED ARE DIGITALLY SIGNED AND SEALED -
 OK. NEW SHEETS SUBMITTED FOR A THIRD REVIEW CYCLE NEED
 VERIFICATION, IF APPLICABLE.
  
 7. ONE E SHEET IS DIGITALLY SIGNED AND SEALED
 (E0.0.01), THE REMAINDER CHECKED ARE NOT DIGITALLY
 SIGNED AND SEALED, FS471 (FOR EXAMPLE, E5.1.05,
 5.1.0-8).
  
 8. CIVIL SHEETS ARE NOT DIGITALLY SIGNED AND SEALED,
 FS471.
  
 9. D SHEETS ARE NOT DIGITALLY SIGNED AND SEALED.
  
 10. L SHEETS ARE LABELED "FOR REFERENCE ONLY"; A
 SEPARATE PERMIT WITH SEPARATE PLANS, APPLICATION, FEES
 IS REQUIRED. SIGNED AND SEALED PAGES ARE REQUIRED AT
 THAT TIME.
  
 11. DUE TO THE DISCREPANCIES IN OTHER SHEETS, WHEN
 RESUBMITTING VERIFY ALL SHEETS, INCLUDING PAGES NOTED
 AS OK.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2017-05-11 Cont ID  
Sent By shill Date 2017-05-11 Time 13:40 Rev Time 0.00
Received By shill Date 2017-05-11 Time 13:40 Sent To  
Notes
2017-05-11 13:41:35APPLICANT IS TO CONFIRM THAT ALL SHEETS ARE
 INDIVIDUALLY DIGITALLY SIGNED PRIOR TO RESUBMITTAL
  
 IF APPLICANT IS UNABLE TO DO SO, PLEASE CONTACT ME
 REGARDING OTHER OPTIONS.
  
 SAMANTHA HILL
 [email protected]
 561-805-6724
2017-04-21 13:05:434/21/17 PLUMB SHEETS NOT DIGITALLY SIGNED/GPJ
2017-04-17 11:23:49THRESHOLD INSPECTION PLAN OK
 ARCHITECTURAL, STRUCTURAL, CIVIL SHEETS NOT DIGITALLY
 SIGNED
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2018-11-27 Cont ID  
Sent By dbattles Date 2018-10-16 Time 14:20 Rev Time 0.00
Received By shill Date 2018-10-16 Time 14:20 Sent To  
Notes
2018-11-27 12:41:00SI AGREEMENT APPROVED BY KC
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THRESHOLD INSPECTION PLAN = OK.
  
 2. THRESHOLD STATEMENT ON PLANS, ARCHITECT: OK
 THRESHOLD STATEMENT ON PLANS, ENGINEER: OK
  
 3. SPECIAL INSPECTOR AGREEMENT -
  
 ANDREW PATRICK SULLIVAN, PE 54091, SI
 INSPECTOR: CHAD CASSETT, PE 80449
 CONTRACTOR: DON PERRY
 OWNER: DOMINIC GATTO
  
 PENDING RECEIPT OF ADDITIONAL INSPECTOR AND RESUME
  
  
2018-10-16 14:21:46[FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2018-08-04 Cont ID  
Sent By shill Date 2018-07-12 Time 07:22 Rev Time 0.00
Received By shill Date 2018-07-07 Time 15:48 Sent To  
Notes
2018-07-07 15:57:57SI AGREEMENT APPROVED BY KC
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THRESHOLD INSPECTION PLAN = OK.
  
 2. THRESHOLD STATEMENT ON PLANS, ARCHITECT: OK
 THRESHOLD STATEMENT ON PLANS, ENGINEER: OK
  
 3. SPECIAL INSPECTOR AGREEMENT -
  
 ANDREW PATRICK SULLIVAN, PE 54091, SI
 INSPECTOR: CHAD CASSETT, PE 80449
 CONTRACTOR: DON PERRY
 OWNER: DOMINIC GATTO
  
 PENDING RECEIPT OF ADDITIONAL INSPECTOR AND RESUME
  
  
  
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2018-05-07 Cont ID  
Sent By shill Date 2018-05-07 Time 06:18 Rev Time 0.00
Received By shill Date 2018-05-07 Time 06:10 Sent To  
Notes
2018-05-07 06:18:47****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THRESHOLD INSPECTION PLAN = OK.
  
 2. THRESHOLD STATEMENT ON PLANS, ARCHITECT: OK
 THRESHOLD STATEMENT ON PLANS, ENGINEER: OK
  
 3. SPECIAL INSPECTOR AGREEMENT - NEEDS; SEND VIA EMAIL
 WHEN AVAILABLE
  
 4. RESUMES FOR INSPECTORS (SI, BN) - NEEDS; SEND VIA
 EMAIL WHEN AVAILABLE
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-04-24 Cont ID  
Sent By shill Date 2017-04-24 Time 11:35 Rev Time 0.00
Received By shill Date 2017-04-24 Time 11:35 Sent To  
Notes
2017-04-17 07:24:57THRESHOLD INSPECTION PLAN OK
 SEE BUILDING REVIEW FOR OTHER COMMENTS
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2018-11-14 Cont ID  
Sent By jroach Date 2018-11-14 Time 13:40 Rev Time 0.00
Received By jroach Date 2018-11-14 Time 13:40 Sent To  
Notes
2018-11-14 13:40:18NO COMMENTS, PLANS WILL BE STAMPED/PASSED WHEN APPROVED
 BY ALL OTHER TRADES.

Review Stop Z ZONING
Rev No 3 Status P Date 2018-10-01 Cont ID  
Sent By jroach Date 2018-10-01 Time 11:31 Rev Time 0.00
Received By jroach Date 2018-10-01 Time 11:31 Sent To  
Notes
2018-10-01 11:31:21NO COMMENTS, PLANS WILL BE STAMPED/PASSED WHEN APPROVED
 BY ALL OTHER TRADES.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-06-07 Cont ID  
Sent By JR Date 2018-06-07 Time 13:33 Rev Time 0.00
Received By jroach Date 2018-06-07 Time 13:33 Sent To  
Notes
2018-06-07 13:34:04NO COMMENTS, PLANS WILL BE STAMPED/PASSED WHEN APPROVED
 BY ALL OTHER TRADES.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-05-04 Cont ID  
Sent By jroach Date 2017-05-04 Time 11:22 Rev Time 0.00
Received By jroach Date 2017-05-04 Time 11:22 Sent To  
Notes
2017-05-04 11:22:40ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.04.2017
 PERMIT NO.: 17070911
 ADDRESS: 3200 N CONGRESS AVENUE
 CONTRACTOR/CONTACT:
 TELEPHONE NO.:
 SCOPE OF REVIEW: NEW HOTEL
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. AS THE SITE PLAN DOES NOT MATCH THAT WHICH WAS
 APPROVED BY THE DEVELOPMENT SERVICES DEPARTMENT -
 PLANNING DIVISION VIA MINOR AMENDMENT TO THE BANYAN CAY
 PLANNED DEVELOPMENT ON MAY 13, 2016, AN AMENDMENT TO
 THE PLANNED DEVELOPMENT WILL BE REQUIRED PRIOR TO
 ISSUANCE OF THE PERMIT. SUCH AMENDMENT APPLICATION HAS
 BEEN SUBMITTED BUT SHALL BE APPROVED PRIOR TO ISSUANCE
 OF THE PERMIT.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved