Plan Review Stops For Permit 17020791 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2017-06-05 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-06-14 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2017-06-05 |
Time |
12:32 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2017-05-01 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2017-05-01 |
Time |
16:11 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2017-05-01 |
Time |
14:29 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2017-03-28 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2017-03-28 |
Time |
14:36 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2017-03-28 |
Time |
14:36 |
Sent To |
M |
|
Notes |
2017-03-28 14:36:26 | PERMIT # 17020791 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FAILED COMMENTS: | | | | 1) ADDRESS ON PERMIT DOES NOT MATCH ADDRESS ON PLANS | | SUBMITTED. | | | | 2) ADDRESS ON PLAN DOES NOT APPEAR TO BE A VALID WEST | | PALM BEACH OR PALM BEACH COUNTY ADDRESS. ADDITIONALLY, | | PLANS STATE "LANTANA" AS THE CITY. | | | | 3) SHEET FP-1, FIRE PREVENTION NOTE #14: STATES FLOW | | TEST PERFORMED BY CITY OF PEMBROKE PINES ON 7-17-15. | | THIS INFORMATION DOES NOT APPEAR TO BE ACCURATE FOR | | THIS PROJECT. | | FLOW TESTS SHALL BE PERFORMED BY THE CITY OF WEST PALM | | BEACH, OR A CERTIFIED COMPANY APPROVED BY THE AHJ, AND | | THE PERFORMED NO MORE THAN 1 YEAR IN ADVANCE OF PERMIT | | APPLICATION SUBMISSION. | | | | 4) A BRIEF REVIEW OF THE PLANS SUBMITTED RAISE | | QUESTIONS REGARDING WHETHER THE DRAWINGS ARE FOR THE | | CORRECT PROJECT. THE SUITE NUMBERS DO NOT MATCH THE | | OTHER DRAWINGS ON THE PLAN NOR THE PERMIT APPLICATION. | | | | 5) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE | | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION | | SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS | | MAY BE GENERATED DURING PLAN RESUBMISSION. | | | | 6) PLEASE REVIEW THE PLANS AND MAKE THE APPROPRIATE | | CORRECTIONS. ALL DATA AND INFORMATION SUBMITTED ON THE | | PLANS MUST BE ACCURATE AND PERTAIN DIRECTLY TO THE | | ADDRESS/UNIT LISTED ON THE PERMIT APPLICATION. ANY | | INACCURATE INFORMATION WILL | | BE CAUSE FOR DENIAL OF THE PLAN. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | FIRE INVESTIGATOR & INSPECTOR | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 804-4751 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2017-06-14 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-06-14 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-06-01 |
Time |
09:41 |
Sent To |
FIRE |
|
Notes |
2017-06-02 09:41:23 | TRAVELLING WITH 17020777, 17020778, 17020779, 17020787, | | 17020788, 17020789, 17020790, 17020791, 17020785, | | 17020784, 170207783, 17020782, 17020781 & 17020780 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-05-08 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-05-08 |
Time |
12:26 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-04-24 |
Time |
12:42 |
Sent To |
|
|
Notes |
2017-04-25 12:42:38 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-04-21 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2017-04-21 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-03-16 |
Time |
07:58 |
Sent To |
|
|
Notes |
2017-03-23 07:59:02 | ROUTED TO FIRE INBOX |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2017-06-14 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-06-14 |
Time |
12:03 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-06-14 |
Time |
12:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2017-05-08 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-05-08 |
Time |
12:25 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-05-08 |
Time |
12:25 |
Sent To |
|
|
Notes |
2017-05-08 12:25:23 | 1) SHT. FP-1 STATES THAT THE SYSTEM WILL NOT BE | | PRESSURIZED PER NFPA 13D SEC. 4.2.CLARIFY. 2ND REQUEST. | | 2) SHT. FP-1- NOTE #14 STATES THE FLOW TEST WAS | | PERFORMED BY THE CITY OF PEMBROKE PINES. CLARIFY. 2ND | | REQUEST | | 3) SHT. FP-1 - THE LOCATION NOTED IN THE LOWER LEFT | | HAND CORNER UNDER "FLOW TEST INFO" LISTS THE NAME OF | | THIS PROJECT AS PELICAN GRAND BEACH RESORT. CLARIFY. | | THE NAME OF THIS PROJECT IS PARK SLOPE. ONE SET STILL | | READS "PELICAN GRAND BEACH RESORT." 2ND REQUEST | | 4) UNIT "A" CALCULATIONS DO NOT HAVE THE LOCATION OF | | THE JOB ON THEM AND THE UNIT "B" CALCULATIONS HAVE THE | | LOCATION NOTED AS LANTANA. CLARIFY. 2ND REQUEST. | | 5) SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS FOR | | ALL TYPES OF SPRINKLER HEADS.WPB AMEND. TO FBC SEC. | | 107.2.1. 2ND REQUEST. | | 6) SUBMIT THE MANUFACTURER'S | | SPECIFICATIONS/INSTALLATION INSTRUCTIONS FOR THE AMES | | 200B BACKFLOW PREVENTER. 2ND REQUEST. | | 7) CLEARLY SHOW COMPLIANCE WITH NFPA 13D SEC.7.1.1 OR | | 7.1.2 FOR THE REQUIRED CONTROL VALVE. 2ND REQUEST. | | 8) SUBMIT DOCUMENTATION THAT THE SPRINKLER HEAD | | DISCHARGE COMPLIES WITH NFPA 13D SEC.8.1.1.1.1, | | 8.1.1.1.2 OR 8.1.1.2. 2ND REQUEST. | | 9) SUBMIT AN ENLARGED PLAN SHOWING THE DESIGN AREA FOR | | UNIT B. 2ND REQUEST. | | 10) THE BACKFLOW PREVENTERS SHALL BE LEAD FREE PER FPC | | 605.2 7 CITY OF WPB CROSS-CONNECTION CONTROL MANUAL. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2017-04-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2017-04-15 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2017-04-15 |
Time |
08:43 |
Sent To |
|
|
Notes |
2017-04-15 08:43:10 | 1) SHT. FP-1 STATES THAT THE SYSTEM WILL NOT BE | | PRESSURIZED PER NFPA 13D SEC. 4.2.CLARIFY. | | 2) SHT. FP-1- NOTE #14 STATES THE FLOW TEST WAS | | PERFORMED BY THE CITY OF PEMBROKE PINES. CLARIFY. | | 3) SHT. FP-1 - THE LOCATION NOTED IN THE LOWER LEFT | | HAND CORNER UNDER "FLOW TEST INFO" LISTS THE NAME OF | | THIS PROJECT AS PELICAN GRAND BEACH RESORT. CLARIFY. | | THE NAME OF THIS PROJECT IS PARK SLOPE. | | 4) UNIT "A" CALCULATIONS DO NOT HAVE THE LOCATION OF | | THE JOB ON THEM AND THE UNIT "B" CALCULATIONS HAVE THE | | LOCATION NOTED AS LANTANA. CLARIFY. | | 5) THE LOCATION OF THE PROJECT ON THE PLANS IS LISTED | | AS LANTANA. CORRECT THE LOCATION ON THE PLANS TO WEST | | PALM BEACH. ALSO, ENSURE THE LOCATION & ADDRESS ON THE | | PERMIT APPLICATION MATCHES THE ADDRESS ON THE PLANS. | | WPB AMEND. TO FBC SEC. 107.2.1. | | 6) SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS FOR | | ALL TYPES OF SPRINKLER HEADS.WWPB AMEND. TO FBC SEC. | | 107.2.1. | | 7) SHT. FP-4 - CLARIFY THE CONNECTION OF THE FIRE | | SPRINKLER SYSTEM TO THE DOMESTIC WATER SYSTEM. THE | | ISOMETRIC IS VAGUE AND CONFUSING.WPB AMEND. TO FBC SEC. | | 107.2.1. | | 8) SUBMIT THE MANUFACTURER'S | | SPECIFICATIONS/INSTALLATION INSTRUCTIONS FOR THE AMES | | 200B BACKFLOW PREVENTER. | | 9) CLEARLY SHOW COMPLIANCE WITH NFPA 13D SEC.7.1.1 OR | | 7.1.2 FOR THE REQUIRED CONTROL VALVE. | | 10) SUBMIT DOCUMENTATION THAT THE SPRINKLER HEAD | | DISCHARGE COMPLIES WITH NFPA 13D SEC.8.1.1.1.1, | | 8.1.1.1.2 OR 8.1.1.2. | | 11) SUBMIT AN ENLARGED PLAN SHOWING THE DESIGN AREA FOR | | UNIT B. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|
|