Plan Review Details - Permit 17020787
Plan Review Stops For Permit 17020787
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-06-05 Cont ID  
Sent By tklarge Date 2017-06-14 Time 12:01 Rev Time 0.00
Received By scaldero Date 2017-06-05 Time 12:31 Sent To P
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-05-01 Cont ID  
Sent By scaldero Date 2017-05-01 Time 16:08 Rev Time 0.00
Received By scaldero Date 2017-05-01 Time 14:27 Sent To P
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-03-28 Cont ID  
Sent By scaldero Date 2017-03-28 Time 14:32 Rev Time 0.00
Received By scaldero Date 2017-03-28 Time 14:32 Sent To M
Notes
2017-03-28 14:34:09PERMIT # 17020787
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) ADDRESS ON PERMIT DOES NOT MATCH ADDRESS ON PLANS
 SUBMITTED.
  
 2) ADDRESS ON PLAN DOES NOT APPEAR TO BE A VALID WEST
 PALM BEACH OR PALM BEACH COUNTY ADDRESS. ADDITIONALLY,
 PLANS STATE "LANTANA" AS THE CITY.
  
 3) SHEET FP-1, FIRE PREVENTION NOTE #14: STATES FLOW
 TEST PERFORMED BY CITY OF PEMBROKE PINES ON 7-17-15.
 THIS INFORMATION DOES NOT APPEAR TO BE ACCURATE FOR
 THIS PROJECT.
 FLOW TESTS SHALL BE PERFORMED BY THE CITY OF WEST PALM
 BEACH, OR A CERTIFIED COMPANY APPROVED BY THE AHJ, AND
 THE PERFORMED NO MORE THAN 1 YEAR IN ADVANCE OF PERMIT
 APPLICATION SUBMISSION.
  
 4) A BRIEF REVIEW OF THE PLANS SUBMITTED RAISE
 QUESTIONS REGARDING WHETHER THE DRAWINGS ARE FOR THE
 CORRECT PROJECT. THE SUITE NUMBERS DO NOT MATCH THE
 OTHER DRAWINGS ON THE PLAN NOR THE PERMIT APPLICATION.
  
 5) A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE
 COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION
 SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED DURING PLAN RESUBMISSION.
  
 6) PLEASE REVIEW THE PLANS AND MAKE THE APPROPRIATE
 CORRECTIONS. ALL DATA AND INFORMATION SUBMITTED ON THE
 PLANS MUST BE ACCURATE AND PERTAIN DIRECTLY TO THE
 ADDRESS/UNIT LISTED ON THE PERMIT APPLICATION. ANY
 INACCURATE INFORMATION WILL
 BE CAUSE FOR DENIAL OF THE PLAN.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-14 Cont ID  
Sent By tklarge Date 2017-06-14 Time 12:01 Rev Time 0.00
Received By tklarge Date 2017-06-01 Time 09:24 Sent To FIRE
Notes
2017-06-02 09:24:39TRAVELLING WITH 17020777, 17020778, 17020779, 17020787,
 17020788, 17020789, 17020790, 17020791, 17020785,
 17020784, 170207783, 17020782, 17020781 & 17020780

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-08 Cont ID  
Sent By tklarge Date 2017-05-08 Time 12:15 Rev Time 0.00
Received By tklarge Date 2017-04-24 Time 12:40 Sent To  
Notes
2017-04-25 12:41:04RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-21 Cont ID  
Sent By lmarchan Date 2017-04-21 Time 15:45 Rev Time 0.00
Received By lmarchan Date 2017-03-16 Time 07:57 Sent To  
Notes
2017-03-23 07:58:05ROUTED TO FIRE INBOX

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-06-14 Cont ID  
Sent By tklarge Date 2017-06-14 Time 12:01 Rev Time 0.00
Received By tklarge Date 2017-06-14 Time 12:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-05-08 Cont ID  
Sent By tklarge Date 2017-05-08 Time 12:15 Rev Time 0.00
Received By tklarge Date 2017-05-08 Time 12:15 Sent To  
Notes
2017-05-08 12:15:231) SHT. FP-1 STATES THAT THE SYSTEM WILL NOT BE
 PRESSURIZED PER NFPA 13D SEC. 4.2.CLARIFY. 2ND REQUEST.
 2) SHT. FP-1- NOTE #14 STATES THE FLOW TEST WAS
 PERFORMED BY THE CITY OF PEMBROKE PINES. CLARIFY. 2ND
 REQUEST
 3) SHT. FP-1 - THE LOCATION NOTED IN THE LOWER LEFT
 HAND CORNER UNDER "FLOW TEST INFO" LISTS THE NAME OF
 THIS PROJECT AS PELICAN GRAND BEACH RESORT. CLARIFY.
 THE NAME OF THIS PROJECT IS PARK SLOPE. ONE SET STILL
 READS "PELICAN GRAND BEACH RESORT." 2ND REQUEST
 4) UNIT "A" CALCULATIONS DO NOT HAVE THE LOCATION OF
 THE JOB ON THEM AND THE UNIT "B" CALCULATIONS HAVE THE
 LOCATION NOTED AS LANTANA. CLARIFY. 2ND REQUEST.
 5) SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS FOR
 ALL TYPES OF SPRINKLER HEADS.WPB AMEND. TO FBC SEC.
 107.2.1. 2ND REQUEST.
 6) SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION INSTRUCTIONS FOR THE AMES
 200B BACKFLOW PREVENTER. 2ND REQUEST.
 7) CLEARLY SHOW COMPLIANCE WITH NFPA 13D SEC.7.1.1 OR
 7.1.2 FOR THE REQUIRED CONTROL VALVE. 2ND REQUEST.
 8) SUBMIT DOCUMENTATION THAT THE SPRINKLER HEAD
 DISCHARGE COMPLIES WITH NFPA 13D SEC.8.1.1.1.1,
 8.1.1.1.2 OR 8.1.1.2. 2ND REQUEST.
 9) SUBMIT AN ENLARGED PLAN SHOWING THE DESIGN AREA FOR
 UNIT B. 2ND REQUEST.
 10) THE BACKFLOW PREVENTERS SHALL BE LEAD FREE PER FPC
 605.2 7 CITY OF WPB CROSS-CONNECTION CONTROL MANUAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-04-15 Cont ID  
Sent By tklarge Date 2017-04-15 Time 08:39 Rev Time 0.00
Received By tklarge Date 2017-04-15 Time 08:39 Sent To  
Notes
2017-04-15 08:39:341) SHT. FP-1 STATES THAT THE SYSTEM WILL NOT BE
 PRESSURIZED PER NFPA 13D SEC. 4.2.CLARIFY.
 2) SHT. FP-1- NOTE #14 STATES THE FLOW TEST WAS
 PERFORMED BY THE CITY OF PEMBROKE PINES. CLARIFY.
 3) SHT. FP-1 - THE LOCATION NOTED IN THE LOWER LEFT
 HAND CORNER UNDER "FLOW TEST INFO" LISTS THE NAME OF
 THIS PROJECT AS PELICAN GRAND BEACH RESORT. CLARIFY.
 THE NAME OF THIS PROJECT IS PARK SLOPE.
 4) UNIT "A" CALCULATIONS DO NOT HAVE THE LOCATION OF
 THE JOB ON THEM AND THE UNIT "B" CALCULATIONS HAVE THE
 LOCATION NOTED AS LANTANA. CLARIFY.
 5) THE LOCATION OF THE PROJECT ON THE PLANS IS LISTED
 AS LANTANA. CORRECT THE LOCATION ON THE PLANS TO WEST
 PALM BEACH. ALSO, ENSURE THE LOCATION & ADDRESS ON THE
 PERMIT APPLICATION MATCHES THE ADDRESS ON THE PLANS.
 WPB AMEND. TO FBC SEC. 107.2.1.
 6) SUBMIT THE MANUFACTURER'S SPECIFICATION SHEETS FOR
 ALL TYPES OF SPRINKLER HEADS.WWPB AMEND. TO FBC SEC.
 107.2.1.
 7) SHT. FP-4 - CLARIFY THE CONNECTION OF THE FIRE
 SPRINKLER SYSTEM TO THE DOMESTIC WATER SYSTEM. THE
 ISOMETRIC IS VAGUE AND CONFUSING.WPB AMEND. TO FBC SEC.
 107.2.1.
 8) SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS/INSTALLATION INSTRUCTIONS FOR THE AMES
 200B BACKFLOW PREVENTER.
 9) CLEARLY SHOW COMPLIANCE WITH NFPA 13D SEC.7.1.1 OR
 7.1.2 FOR THE REQUIRED CONTROL VALVE.
 10) SUBMIT DOCUMENTATION THAT THE SPRINKLER HEAD
 DISCHARGE COMPLIES WITH NFPA 13D SEC.8.1.1.1.1,
 8.1.1.1.2 OR 8.1.1.2.
 11) SUBMIT AN ENLARGED PLAN SHOWING THE DESIGN AREA FOR
 UNIT B.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW