Plan Review Details - Permit 17020758
Plan Review Stops For Permit 17020758
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-04-12 Cont ID  
Sent By jwitmer Date 2017-04-12 Time 11:03 Rev Time 0.00
Received By jwitmer Date 2017-04-12 Time 09:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-22 Cont ID  
Sent By jwitmer Date 2017-02-22 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2017-02-22 Time 06:24 Sent To  
Notes
2017-02-22 07:17:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020758
 ADD: 501 S. FLAGLER DR. SUITE # 400
 CONT: ANDERSON-MOORE
 TEL: 561-308-1590
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 22/ 2017
 ACTION: DENIED
  
 1) SHEET A1.1.1:
 1A) DOOR MARKED ETR FROM THE LOBBY TO CORRIDOR 452 IS
 MISSING THE 18 INCHES ON THE LATCHSIDE OF THE DOOR.
 DOES NOT COMPLY WITH 2014 FBC-ACCESS. CODE SECTION
 404.2.4 MANEUVERING CLEARANCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY
 WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE
 FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE
 OR HINGE SIDE CLEARANCE. FIGURE 404.2.4.1(A).
  
 1B) ENTRY DOOR FROM THE ELEVATOR LOBBY TO CORRIDOR 448
 IS MISSING THE 18 INCHES ON THE LATCHSIDE OF THE DOOR.
 DOES NOT COMPLY WITH 2014 FBC-ACCESS. CODE SECTION
 404.2.4 MANEUVERING CLEARANCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY
 WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE
 FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE
 OR HINGE SIDE CLEARANCE. FIGURE 404.2.4.1(A). WHILE THE
 DOOR IS CONTRAVERSIAL AS TO LANDLORD OR TENANT
 RESPONSIBILITY THE VIOLATION IS ON THE TENANT SIDE AND
 CAN BE MADE CODE COMPLIANT WITH AN ELECTRIC PUSH BUTTON
 AND DOOR ACTUATOR.
 FBC-ACCESS. CODE 404.3 AUTOMATIC AND POWER-ASSISTED
 DOORS AND GATES.
  
 1C) DOOR 436 MAY OR MAY NOT MEET THE 18 INCHES ON THE
 LATCHSIDE OF THE DOOR THE PLAN IS IN 1/8 INCH SCALE AND
 THIS AREA IS NOT DIMENSIONED. DOES NOT COMPLY WITH 2014
 FBC-ACCESS. CODE SECTION 404.2.4 MANEUVERING CLEARANCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS AND
 GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES
 SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE
 REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE. FIGURE
 404.2.4.1(A).
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 2) THE PERMIT APPLICATION INDICATES THE DECLARED VALUE
 OF THE PERMIT TO BE $500,000.00 IN VALUE. THE
 FBC-ACCESS. CODE ALLOW UP TO 20% OF THE VALUE OF THE
 PERMIT BEFORE DISPROPORTIONATE COST ARE MET. 202.4.2
 ACCESSIBLE FEATURES IN THE EVENT OF DISPROPORTIONALITY.
 PLEASE ITEMIZE WHERE THESE FUNDS ARE SPENT AND THE
 ORDER IN WHICH THEY ARE SPENT TO ACHIEVE CODE
 COMPLIANCE OR DISPROPORTIONALITY. 2014 FBC-ACCESS. CODE
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
  
 3) SHEET A2.0.1 DETAIL # 4 SHOWS A HIGH/ LOW DRINKING
 FONTAIN BUT THE DETAIL DOES NOT INDICATE AT WHAT LEVEL
 THE SPOUT HEIGHT COMPLING WITH ACCESS. CODE 602.4 &
 602.7.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-03 Cont ID  
Sent By jleahy Date 2017-03-03 Time 15:11 Rev Time 0.00
Received By jleahy Date 2017-03-03 Time 15:11 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-02-21 Cont ID  
Sent By wjolin Date 2017-02-21 Time 11:20 Rev Time 0.00
Received By wjolin Date 2017-02-21 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-12 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By cpuell Date 2017-04-07 Time 11:32 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-04-10 Cont ID  
Sent By cpuell Date 2017-04-10 Time 11:24 Rev Time 0.00
Received By cpuell Date 2017-02-16 Time 10:07 Sent To  
Notes
2017-02-17 10:07:14C20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-02-22 Cont ID  
Sent By   Date 2017-02-22 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2017-02-22 Time 06:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-03-03 Cont ID  
Sent By ccole Date 2017-03-03 Time 10:36 Rev Time 0.00
Received By ccole Date 2017-03-03 Time 10:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-04-11 Cont ID  
Sent By gjohnson Date 2017-04-11 Time 17:17 Rev Time 0.00
Received By gjohnson Date 2017-04-11 Time 17:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-03-03 Cont ID  
Sent By gjohnson Date 2017-03-03 Time 14:02 Rev Time 0.00
Received By gjohnson Date 2017-03-03 Time 14:02 Sent To E
Notes
2017-03-03 14:16:011ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. A2.0.1 DETAIL #2 GRAB BAR IS NOTED AS 30" IT
 SHALL BE 36" MIN. PER FBC ACC 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
 2. GRAB BARS SHALL BE MEASURED FROM THE FINISHED FLOOR
 TO THE TOP OF THE GRIPPING SURFACE. FBC ACC 609.4
  
 3. SHT. P2.1, E3.1, ALS1.1 SHOWS A PARTITION IN-THE
 BATHEOOM 407 NEXT TO WC SHT. A1.1.1, A1.1.3 DOES NOT
 SHOW THE PARTITION PLEASE CLARIFY. WPB AMEND TO FBC
 107.2.1
  
 4. ON THE ARCHITECTURAL PAGES THE LAYOUT FOR THE SINK
 IN THE CONFERENCE RM 440 DIFFERS FROM THR MEP PAGES
 PLEASE CLARIFY. WPB AMEND TO FBC 107.2.1
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  