Plan Review Details - Permit 17020645
Plan Review Stops For Permit 17020645
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-15 Cont ID  
Sent By ccole Date 2017-03-15 Time 08:11 Rev Time 0.00
Received By ccole Date 2017-03-13 Time 14:02 Sent To  
Notes
2017-03-13 14:02:57CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-17 Cont ID  
Sent By ccole Date 2017-02-17 Time 08:58 Rev Time 0.00
Received By ccole Date 2017-02-14 Time 11:18 Sent To  
Notes
2017-02-15 11:18:48REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-15 Cont ID  
Sent By ccole Date 2017-03-15 Time 08:11 Rev Time 0.00
Received By ccole Date 2017-03-15 Time 08:11 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-17 Cont ID  
Sent By ccole Date 2017-02-17 Time 08:58 Rev Time 0.00
Received By ccole Date 2017-02-17 Time 08:58 Sent To  
Notes
2017-02-17 09:04:501ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020645
 2/17/17
  
 1) PLEASE REFER TO SECTION 306.5. ACCESS TO THE BDD
 WILL STILL BE REQUIRED BECAUSE IT MEETS THE DEFINITION
 OF EQUIPMENT PER SECTION 202. PLEASE PROVIDE A
 PERMANENT LADDER AND ACCESS PLATFORM PER THE
 INSPECTOR'S REQUEST.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  