Plan Review Details - Permit 17020507
Plan Review Stops For Permit 17020507
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-02-24 Cont ID  
Sent By vperez Date 2017-02-24 Time 11:35 Rev Time 0.00
Received By vperez Date 2017-02-24 Time 11:35 Sent To  
Notes
2017-02-24 11:36:04INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PROVISO COMMENTS:
  
 1. PLEASE PROVIDE DATA SHEETS REFLECTING LISTINGS FOR
 FOOD CARTS, DOCUMENTATION SUBMITTED DOES NOT REFLECT.
 FBC 107.3.5
 2. PROVIDE VOLTAGE DROP CALCULATIONS ON DISTRIBUTION
 PANELS. FBC 107.3.5
 3. PLEASE PROVIDE OVERCURRENT PROTECTION AND CONDUCTOR
 AMPACITIES BASED ON NEC 310.15B16 AND FBC 107.3.5
 4. PLEASE PROVIDE PORTABLE GENERATOR GROUNDING PER NEC
 702.11A- GROUND PER NEC 250.30
 5. FEEL FREE TO CONTACT ME AT THE NUMBER LISTED BELOW
 SHOULD YOU HAVE ANY QUESTIONS OR CONCERNS.
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-02-24 Cont ID  
Sent By wjolin Date 2017-02-24 Time 11:29 Rev Time 0.00
Received By wjolin Date 2017-02-24 Time 11:29 Sent To  
Notes
2017-02-24 11:29:52CART B2 IS OBSTRUCTING THE EGRESS PATH. RELOCATE.
  
 GENERATOR EXHAUST SHALL BE LOCATED AT LEAST 10 FEET
 FROM ANY BUILDING OPENING.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-24 Cont ID  
Sent By vperez Date 2017-02-24 Time 11:35 Rev Time 0.00
Received By vperez Date 2017-02-24 Time 11:35 Sent To  
Notes
***NONE***