Plan Review Details - Permit 17020391
Plan Review Stops For Permit 17020391
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-29 Cont ID  
Sent By vperez Date 2017-03-29 Time 11:27 Rev Time 0.00
Received By vperez Date 2017-03-29 Time 11:27 Sent To  
Notes
2017-03-24 09:38:35SENT TO FIRE

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-15 Cont ID  
Sent By vperez Date 2017-02-15 Time 09:40 Rev Time 0.00
Received By vperez Date 2017-02-15 Time 09:40 Sent To FIRE
Notes
2017-02-15 09:42:00INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
  
 1- PLEASE ADDRESS ZONING COMMENTS RELATED TO GENERATOR
 LOCATION, SHOW DISTANCE FRON OPENINGS TO BUILDING...
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-27 Cont ID  
Sent By pleduc Date 2017-03-27 Time   Rev Time 0.00
Received By pleduc Date 2017-03-27 Time 15:13 Sent To P
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-22 Cont ID  
Sent By pleduc Date 2017-02-22 Time   Rev Time 0.00
Received By pleduc Date 2017-02-22 Time 13:40 Sent To PC
Notes
2017-02-22 13:44:43THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) PROVIDE A DETAILED SITE PLAN SHOWING EXACT
 LOCATIONS, WINDOWS, DOORS INCLUDING ALL DIMENSION.
  
  
  
 2) THERE IS NO INDICATIONS OF ROOFING AND/OR VENTING
 FOR THE GENERATORS
  
 PLEASE PROVIDE DETAILS RELATING TO THE ABOVE COMMENT.
  
  
  
 3) PLEASE PROVIDE A DETAILED REVIEW OR CLARIFY THE
 SCOPE OF WORK. YOU ARE PROVIDING THE SPECS FOR
 UNDERGROUND PIPING BUT THE SCOPE INDICATES A RECONNECT.
  
  
  
 4) PLEASE NOTE THAT THE INSTALL SHALL COMPLY WITH THE
 REQUIREMENTS OF NFPA 58.
  
  
  
 5) ADDRESS OTHER CITY DEPARTMENT COMMENTS.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-03-29 Cont ID  
Sent By tklarge Date 2017-03-29 Time 06:55 Rev Time 0.00
Received By tklarge Date 2017-03-29 Time 05:57 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-02-28 Cont ID  
Sent By tklarge Date 2017-02-28 Time 09:04 Rev Time 0.00
Received By tklarge Date 2017-02-28 Time 05:38 Sent To  
Notes
2017-02-28 07:13:421) SUBMIT A SITE PLAN SHOWING THE LOCATION OF BOTH
 GENERATORS IN RELATION TO OPERABLE WINDOWS, DOORS AND
 ANY OTHER OPENINGS INTO THE STRUCTURE. WPB AMEND. TTO
 FBC SEC. 107.2.1.
 2) SHOW THE DISTANCES FROM THE GENERATOR EXHAUST TO ALL
 OPERABLE WINDOWS AND DOORS AND ANY OTHER OPENINGS INTO
 THE STRUCTURE. COMPLY WITH NFPA 58 & NFPA 37. WPB
 AMEND. TTO FBC SEC. 107.2.1.
 3) SHOW THE LOCATION OF THE EXISTING LP TANK ON THE
 SITE PLAN. WPB AMEND. TTO FBC SEC. 107.2.1.
 4) THE PLANS REFERENCE TWO PE SIZING TABLES IN THE FUEL
 GAS CODE BUT YOU HAVE ALSO SUBMITTED A SIZING TABLE
 FROM THE MANUFACTURER. CLARIFY.
 5) THE PLANS SHOW THE UNDERGROUND LP PIPING AS EXISTING
 BUT YOU HAVE SUBMITTED MANUFACTURER'S SPECIFICATIONS
 FOR PE PIPING. CLEARLY INDICATE ON THE PLANS IF ANY NEW
 PE PIPING IS BEING INSTALLED AND LIST THE TOTAL
 DEVELOPED LENGTH AND PSI OF THE SYTEM ON THE NEW PE
 PIPE. WPB AMEND. TTO FBC SEC. 107.2.1.THE PLANS NOTE
 THIS AS A DISCONNECT/RECONNECT.CLARIFY.
 6) THE PLANS SHOW ONE OF THE GENERATORS WITH A BTU LOAD
 OF 340,000. THERE ARE TWO GENERATORS BEING INSTALLED SO
 THE BTU LOAD SHOULD BE 680,000 BUT THE TOTAL LOAD SHOWN
 ON THE PLAN IS 340,000. CLARIFY. THE PIPING SHALL BE
 SIZED FOR THE TOTAL BTU LOAD ON THE SYSTEM.AS SHOWN,
 THE SYSTM IS UNDERSIZED.
 7) SHOW THE DEVELOPED LENGTH OF THE SCH. 40 METALLIC
 PIPE FROM THE STEP- DOWN REGULATOR TO EACH GENERATOR.
 8) THE GAS SIZING TABLES THAT ARE REFERENCED ON THE
 PLAN FROM THE 2014 FBC-FUEL GAS CODE ARE FOR NATURAL
 GAS AND THIS IS AN LP GAS SYSTEM. REFERENCE THE CORRECT
 APPLICABLE SIZING TABLES ON THE PLANS. INCLUDE THE
 REFERENCE TO THE CORRECT TABLE FOR THE METALLIC PIPE.
 WPB AMEND. TTO FBC SEC. 107.2.1.
 9) CLARIFY THE PIPE RUN OF 30 FEET SHOWN ON THE
 PLANS.IS THIS FOR THE EXISTING UNDERGROUND? INDICATE
 THE PSI OF THE EXISTING SYSTEM FROM THE LP TANK TO THE
 REGULATOR. WPB AMEND. TTO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-29 Cont ID  
Sent By vperez Date 2017-03-29 Time 11:27 Rev Time 0.00
Received By vperez Date 2017-03-29 Time 11:27 Sent To  
Notes
2017-03-16 10:16:33RESUB ROUTED TO NJWIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-22 Cont ID  
Sent By pleduc Date 2017-02-22 Time   Rev Time 0.00
Received By pleduc Date 2017-02-09 Time 12:12 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-03-23 Cont ID  
Sent By njwira Date 2017-03-23 Time 15:37 Rev Time 0.00
Received By njwira Date 2017-03-20 Time 15:07 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2017-02-14 Cont ID  
Sent By pleduc Date 2017-02-22 Time 13:44 Rev Time 0.00
Received By njwira Date 2017-02-13 Time 15:44 Sent To E
Notes
2017-02-14 16:10:412/14/17- FAILED
  
 PLEASE INDICATE WHERE THE MECHANICAL EQUIPMENT IS
 GOING.
  
  
 PLEASE CONTACT
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved