Plan Review Details - Permit 17020366
Plan Review Stops For Permit 17020366
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-06-26 Cont ID  
Sent By jwitmer Date 2017-06-26 Time 06:33 Rev Time 0.00
Received By jwitmer Date 2017-06-24 Time 10:01 Sent To  
Notes
2017-06-26 06:33:44BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020366
 ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2(A)
 CONT: TBD
 TEL: 561-358-9909
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. JUNE 26/ 2017
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SEMI-COMPLIED. BY DEFINITION THE MEZZANINE AREA IS
 NOW A 2ND FLOOR. SINCE THE 2ND FLOOR STILL COMMUNICATES
 WITH THE 1ST FLOOR BY THE WAY OF THE ATMOSPHERE THIS IS
 NOW CONSIDERED A 2 STORY ATRIUM. PLEASE REVIEW ENCLOSE
 OF ATRIUMS UNDER SECTION 404.6 OF THE 2014 FBC-B:
 404.6 ENCLOSURE OF ATRIUMS.
 ATRIUM SPACES SHALL BE SEPARATED FROM ADJACENT SPACES
 BY A 1-HOUR FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH
 SECTION 707 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN
 ACCORDANCE WITH SECTION 711, OR BOTH.
 EXCEPTIONS:
 1. A FIRE BARRIER IS NOT REQUIRED WHERE A GLASS WALL
 FORMING A SMOKE PARTITION IS PROVIDED. THE GLASS WALL
 SHALL COMPLY WITH ALL OF THE FOLLOWING:
  
 1.1. AUTOMATIC SPRINKLERS ARE PROVIDED ALONG BOTH SIDES
 OF THE SEPARATION WALL AND DOORS, OR ON THE ROOM SIDE
 ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM SIDE. THE
 SPRINKLERS SHALL BE LOCATED BETWEEN 4 INCHES AND 12
 INCHES (102 MM AND 305 MM) AWAY FROM THE GLASS AND AT
 INTERVALS ALONG THE GLASS NOT GREATER THAN 6 FEET (1829
 MM). THE SPRINKLER SYSTEM SHALL BE DESIGNED SO THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM WITHOUT OBSTRUCTION;
  
 1.2. THE GLASS WALL SHALL BE INSTALLED IN A GASKETED
 FRAME IN A MANNER THAT THE FRAMING SYSTEM DEFLECTS
 WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE
 SPRINKLER SYSTEM OPERATES; AND
  
 1.3. WHERE GLASS DOORS ARE PROVIDED IN THE GLASS WALL,
 THEY SHALL BE EITHER SELF-CLOSING OR AUTOMATIC-CLOSING.
  
 2. A FIRE BARRIER IS NOT REQUIRED WHERE A GLASS-BLOCK
 WALL ASSEMBLY COMPLYING WITH SECTION 2110 AND HAVING A
 3/4-HOUR FIRE PROTECTION RATING IS PROVIDED.
  
 1ST ROUND OF COMMENTS. SHEET A-0.01 SHOWS AN EXISTING
 MEZZANINE OF 329 SQ. FT. AND AN ADDITIONAL 299 SQ. FT.
 ADDED TO THE MEZZANINE LEVEL TOTALING 628 SQ. FT. THE
 TOTAL SQ. FT. OF THE 1ST FLOOR IS GIVEN 1864 SQ. FT. OR
 28.6 % OF THE FLOOR AREA.
  
 THIS IS NOT THE WAY TO FIGURE THE ALLOWABLE AREA OF
 MEZZANINES. THE SIZE OF THE MEZZANINE IS FIGURED NOT
 GREATER THAN 1/3 THE ROOM THEY ARE LOCATED (FBC-B
 505.2.1). SEE EXCEPTION # 2. THE AGGREGATE AREA OF
 MEZZANINES IN BUILDINGS AND STRUCTURES OF TYPE I OR II
 CONSTRUCTION SHALL BE NOT GREATER THAN ONE-HALF OF THE
 FLOOR AREA OF THE ROOM IN BUILDINGS AND STRUCTURES
 EQUIPPED THROUGHOUT WITH AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1
 AND AN APPROVED EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 THE ENCLOSED AREA OF THE 1ST FLOOR DOES NOT COMMUNICATE
 WITH THE MEZZANINE AREA ARE NOT INCLUDED IN THE
 CALCULATING THE 1ST FLOOR AREA. THE TOTAL AREA OF THE
 1ST FLOOR AREA THAT COMMUNICATES WITH THE MEZZANINE
 LEVEL IS 833.25 SQ. FT.
 833.25 SQ. FT. X 0.33= 274.9725 SQ. FT.
 833.25 SQ. FT. X 0.50= 416.6250 SQ. FT.
 EXISTING MEZZANINE 329.0000 SQ. FT.
 WITH THE WALLS AS SHOWN ON THE 1ST FLOOR THE EXISTING
 MEZZANINE MAYBE AN ISSUE IF THERE IS NO ALARM IN
 COMPLIANCE WITH FBC-B 907.5.2.2.
 907.5.2.2 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS.
 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS REQUIRED BY
 THIS CODE SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH NFPA 72. THE OPERATION OF ANY AUTOMATIC FIRE
 DETECTOR, SPRINKLER WATERFLOW DEVICE OR MANUAL FIRE
 ALARM BOX SHALL AUTOMATICALLY SOUND AN ALERT TONE
 FOLLOWED BY VOICE INSTRUCTIONS GIVING APPROVED
 INFORMATION AND DIRECTIONS FOR A GENERAL OR STAGED
 EVACUATION IN ACCORDANCE WITH THE BUILDINGS FIRE SAFETY
 AND EVACUATION PLANS REQUIRED BY THE FLORIDA FIRE
 PREVENTION CODE. IN HIGH-RISE BUILDINGS, THE SYSTEM
 SHALL OPERATE ON A MINIMUM OF THE ALARMING FLOOR, THE
 FLOOR ABOVE AND THE FLOOR BELOW. SPEAKERS SHALL BE
 PROVIDED THROUGHOUT THE BUILDING BY PAGING ZONES. AT A
 MINIMUM, PAGING ZONES SHALL BE PROVIDED AS FOLLOWS:
 1. ELEVATOR GROUPS.
 2. EXIT STAIRWAYS.
 3. EACH FLOOR.
 4. AREAS OF REFUGE AS DEFINED IN SECTION 1002.1.
  
 2) SINCE THERE IS STRUCTURAL WORK BEING COMPLETED UNDER
 THIS PERMIT AND THIS BUILDING IS A 20 STORY HIGHRISE IT
 QUALIFIES AS A THRESHOLD BUILDING. THRESHOLD BUILDING /
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 2ND REQUEST 109.3.6.1 THRESHOLD INSPECTION PLAN.
 THE ENFORCING AGENCY SHALL REQUIRE A (WRITTEN/ TYPED)
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 2B) 2ND REQUEST. THRESHOLD INSPECTOR: WPB AMENDMENT
 109.3.6.2 W.P.B. CONSTRUCTION SERVICES DEPARTMENT
 REQUEST FOR THRESHOLD BUILDINGS A SPECIAL INSPECTOR AS
 REQUIRED BY FL S 553.79(5) FLORIDA STATUTES TO THE
 MINIMUM INSPECTIONS REQUIRED BY THIS CODE. THE
 THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE FILED OUT
 BY ALL PARTIES WITH INTEREST, NOTARIZED AND RETURNED TO
 THIS OFFICE, AND REVIEWED AND APPROVED BEFORE PERMIT
 ISSUANCE WILL TAKE PLACE.
 FORMS E-MAILED TO: [email protected] 02/15/2017
 11:29AM
  
 2C) COMPLIED. THRESHOLD BLDG., REQUIRED STATEMENT:
 W.P.B. AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) 2ND REQUEST. FOR THE SPECIAL INSPECTOR PLEASE
 PROVIDE A RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS
 PROJECT. THE RESUME' MUST BE ACCOMPANIED BY ALL
 CERTIFICATES AS SPECIFIED HEREIN. THE BUILDING OFFICIAL
 OR HIS DESIGNEE WILL REVIEW THE RESUME'. AFTER THE
 RESUME' IS REVIEWED, AN INTERVIEW WILL BE SCHEDULED.
 UNDER NO CIRCUMSTANCES WILL AN INSPECTOR BE INTERVIEWED
 FOR WORK WITHOUT FIRST MEETING THE ABOVE CRITERIA.
  
 2E)2ND REQUEST. THE CONTRACTOR WILL PRODUCE A JOB
 SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F)SEMI-COMPLIED. IN BOTH THE SOILS REPORTS P.E. MARK
 A. MESIANO AND THE ALL PLANS SIGNED BY EDWARD A LANDERS
 THE SIGNATURES ARE DIGITAL IN NATURE.
 MARK A. MESIANO DOES HAVE 3 DIFFERENT SIGNATURES ON
 EACH SOILS REPORTS BUT ALL THREE REPORTS HAVE PIXILATED
 SIGNATURES, NOT A INK SIGNATURE.
 EDWARD A LANDERS SIGNATURE STATES THIS SIGNATURE IS
 ELECTRONIC.
 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING
 ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 1ST ROUND OF COMMENTS. NOTE FOR PAPER PLANS 3 SETS OF
 DOCUMENTS ARE REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT
 ISSUANCE, PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE
 PERMIT BEING ISSUED, THE PERMIT LIBRARIAN WILL THEN
 E-MAIL YOU THE APPROVED AND BATCH STAMPED PLANS SO YOU
 MAY PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS OTHER PLANS YOU WISH TO
 PRINT MAYBE IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) PROVISO: 110.3.7.4.3 ALL SHORING AND RESHORING
 PROCEDURES, PLANS AND DETAILS SHALL BE SUBMITTED TO THE
 ENFORCEMENT AGENCY FOR RECORDKEEPING. EACH SHORING AND
 RESHORING INSTALLATION SHALL BE SUPERVISED, INSPECTED
 AND CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) PROVISO: PLEASE CALL THE CITY OF WEST PALM BEACHS
 AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700)
 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) PROVISO: 109.3.6 THRESHOLD BUILDINGS, OPERATING
 GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT
 THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING
 PENETRATIONS, FOR WALLS AND CEILINGS.
  
 3-4) COMPLIED.
  
 5) COMPLIED.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-15 Cont ID  
Sent By jwitmer Date 2017-02-15 Time 11:31 Rev Time  
Received By jwitmer Date 2017-02-15 Time 08:16 Sent To  
Notes
2017-02-15 11:31:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020366
 ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2(A)
 CONT: TBD
 TEL: 561-358-9909
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 15/ 2017
 ACTION: DENIED
  
 1) SHEET A-0.01 UNDER THE HEADING LIST THIS BUILDING
 TYPE TO BE A BUILDING TYPE IIA. PLEASE NOTE ABOVE THE
 1ST FLOOR LEVEL THIS HIGH RISE IS A R2 OCCUPANCY TYPE.
 PLEASE NOTE THIS IS A 20 STORY HIGH RISE, THE MINIMUM
 BUILDING TYPE REQUIRED WOULD BE TYPE IA SEE 2014 FBC-B
 TABLE 503.
  
 2) SHEET A-0.01 SHOWS AN EXISTING MEZZANINE OF 329 SQ.
 FT. AND AN ADDITIONAL 299 SQ. FT. ADDED TO THE
 MEZZANINE LEVEL TOTALING 628 SQ. FT. THE TOTAL SQ. FT.
 OF THE 1ST FLOOR IS GIVEN 1864 SQ. FT. OR 28.6 % OF THE
 FLOOR AREA.
  
 THIS IS NOT THE WAY TO FIGURE THE ALLOWABLE AREA OF
 MEZZANINES. THE SIZE OF THE MEZZANINE IS FIGURED NOT
 GREATER THAN 1/3 THE ROOM THEY ARE LOCATED (FBC-B
 505.2.1). SEE EXCEPTION # 2. THE AGGREGATE AREA OF
 MEZZANINES IN BUILDINGS AND STRUCTURES OF TYPE I OR II
 CONSTRUCTION SHALL BE NOT GREATER THAN ONE-HALF OF THE
 FLOOR AREA OF THE ROOM IN BUILDINGS AND STRUCTURES
 EQUIPPED THROUGHOUT WITH AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION 903.3.1.1
 AND AN APPROVED EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM IN ACCORDANCE WITH SECTION 907.5.2.2.
  
 THE ENCLOSED AREA OF THE 1ST FLOOR DOES NOT COMMUNICATE
 WITH THE MEZZANINE AREA ARE NOT INCLUDED IN THE
 CALCULATING THE 1ST FLOOR AREA. THE TOTAL AREA OF THE
 1ST FLOOR AREA THAT COMMUNICATES WITH THE MEZZANINE
 LEVEL IS 833.25 SQ. FT.
 833.25 SQ. FT. X 0.33= 274.9725 SQ. FT.
 833.25 SQ. FT. X 0.50= 416.6250 SQ. FT.
 EXISTING MEZZANINE 329.0000 SQ. FT.
 WITH THE WALLS AS SHOWN ON THE 1ST FLOOR THE EXISTING
 MEZZANINE MAYBE AN ISSUE IF THERE IS NO ALARM IN
 COMPLIANCE WITH FBC-B 907.5.2.2.
 907.5.2.2 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS.
 EMERGENCY VOICE/ALARM COMMUNICATION SYSTEMS REQUIRED BY
 THIS CODE SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE
 WITH NFPA 72. THE OPERATION OF ANY AUTOMATIC FIRE
 DETECTOR, SPRINKLER WATERFLOW DEVICE OR MANUAL FIRE
 ALARM BOX SHALL AUTOMATICALLY SOUND AN ALERT TONE
 FOLLOWED BY VOICE INSTRUCTIONS GIVING APPROVED
 INFORMATION AND DIRECTIONS FOR A GENERAL OR STAGED
 EVACUATION IN ACCORDANCE WITH THE BUILDING?S FIRE
 SAFETY AND EVACUATION PLANS REQUIRED BY THE FLORIDA
 FIRE PREVENTION CODE. IN HIGH-RISE BUILDINGS, THE
 SYSTEM SHALL OPERATE ON A MINIMUM OF THE ALARMING
 FLOOR, THE FLOOR ABOVE AND THE FLOOR BELOW. SPEAKERS
 SHALL BE PROVIDED THROUGHOUT THE BUILDING BY PAGING
 ZONES. AT A MINIMUM, PAGING ZONES SHALL BE PROVIDED AS
 FOLLOWS:
 1. ELEVATOR GROUPS.
 2. EXIT STAIRWAYS.
 3. EACH FLOOR.
 4. AREAS OF REFUGE AS DEFINED IN SECTION 1002.1.
  
 2) SINCE THERE IS STRUCTURAL WORK BEING COMPLETED UNDER
 THIS PERMIT AND THIS BUILDING IS A 20 STORY HIGHRISE IT
 QUALIFIES AS A THRESHOLD BUILDING. THRESHOLD BUILDING /
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 FORMS E-MAILED TO: [email protected] 02/15/2017
 11:29AM
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3) SHEET S-1.01 SHOWS A DETAIL FOR THE HELICAL PILE
 INSTALLATION. PLEASE PROVIDE THE SOILS ANALYSIS OF HOW
 THE PILE SIZE AND LENGTH OF PILE AND FREQUENCY OF
 INSTALLATION WAS ACHIEVED. 1803.5.2 QUESTIONABLE SOIL.
  
 4) SHEET S-1.01 SHOWS A DETAIL FOR THE HELICAL PILE
 INSTALLATION. THE ENGINEER OF RECORD STATES THE PILE
 ARE TO BE INSTALLED UNDER THE SUPERVISION OF AN
 ENGINEER WHO SPECIALIZES IN THE INSTALLATION OF HELICAL
 PILES AND WHO SHALL CERTIFY THEIR INSTALLATION AND
 CAPACITIES. PLEASE PROVIDE DOCUMENTATION.
 FBC-B 1810.3.1.5 HELICAL PILES. HELICAL PILES SHALL BE
 DESIGNED AND MANUFACTURED IN ACCORDANCE WITH ACCEPTED
 ENGINEERING PRACTICE TO RESIST ALL STRESSES INDUCED BY
 INSTALLATION INTO THE GROUND AND SERVICE LOADS.
  
 5) SHEET A-1.01 SHOWS AN EQUIPMENT CLOSET NEXT TO THE
 ELEVATOR SHAFT. PLEASE PROVIDE IF THIS IS THE EQUIPMENT
 ROOM FOR THE ELEVATOR. IF SO THE WALLS ARE SHOWN AS 1
 HOUR FIRE RATING, BUT THE DOORS # 11& 12 SHOW NO RATING
 SEE DOOR SCHEDULE THIS SHEET. SEE FBC-B 3006.4.
 OPENINGS IN THE FIRE BARRIERS SHALL BE PROTECTED WITH
 ASSEMBLIES HAVING A FIRE PROTECTION RATING NOT LESS
 THAN THAT REQUIRED FOR THE HOISTWAY ENCLOSURE DOORS.
 TABLE 716.5.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-06-28 Cont ID  
Sent By jleahy Date 2017-06-28 Time 17:48 Rev Time 0.00
Received By jleahy Date 2017-06-28 Time 17:48 Sent To  
Notes
2017-06-28 17:50:36FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 SEE COMMENTS FROM 2/24/17 PLAN REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-24 Cont ID  
Sent By vperez Date 2017-02-24 Time 12:51 Rev Time 0.00
Received By vperez Date 2017-02-24 Time 12:51 Sent To  
Notes
2017-02-24 12:52:34INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 SITE LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE
 SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM,
 ACCESS CONTROLS, CCTV, PHONE AND DATA, WIRELESS
 SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. PLEASE SHOW AIC CALCULATION BASED ON INFORMATION
 PROVIDED BY FPL UTILITY FOR APPROVAL. NEC 110.24 FBC
 107.
 4. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 5. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405 SEE
 VERBIAGE IN THE CODE REGARDING AUTOMATIC LIGHTING
 CONTROLS AND MINIMUM LIGHTING DENSITIES.
 6. SHOW ON POWER AND LIGHTING LAYOUT, THE BRANCH
 CIRCUIT NUMBERS ASSIGNED TO EACH OUTLET? FBC 107.3.5
 7. PLANS ARE VERY VAGUE AND DEFICIENT; A COMPLETE
 ELECTRICAL REVIEW CANNOT BE PERFORMED TO PROVIDE A
 CHECKLIST TO DESIGNER OF RECORD WITH EVERY APPLICABLE
 FBC, NFPA AND NEC PROVISIONS APPLICABLE TO THIS PROJECT
 WHICH HAS MULTIPLE DEFICIENCIES.
 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2017-06-28 Cont ID  
Sent By wjolin Date 2017-06-28 Time 10:42 Rev Time 0.00
Received By wjolin Date 2017-06-23 Time 15:34 Sent To  
Notes
2017-06-28 10:42:21REFER TO THE BUILDING REVIEW COMMENTS CONCERNING THE
 TWO-STORY ATRIUM/COMMUNICATING SPACE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-15 Cont ID  
Sent By wjolin Date 2017-02-15 Time 16:10 Rev Time 0.00
Received By wjolin Date 2017-02-15 Time 15:54 Sent To  
Notes
2017-02-15 16:10:53550 OKEECHOBEE BOULEVARD
 PERMIT #17020366
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXITS, TRAVEL
 DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 HOW IS THE EXISTING FIRE ALARM AND FIRE SPRINKLER BEING
 AFFECTED?
  
 MEZZANINE DOES NOT APPEAR TO BE IN COMPLIANCE WITH THE
 LIFE SAFETY CODE FOR SIZE (1/3) AND OPENNESS.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-07-17 Cont ID  
Sent By eschneid Date 2017-07-17 Time 14:01 Rev Time 0.00
Received By eschneid Date 2017-06-20 Time 14:39 Sent To  
Notes
2017-06-21 14:39:51B31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-06 Cont ID  
Sent By eschneid Date 2017-03-06 Time 16:25 Rev Time 0.00
Received By eschneid Date 2017-02-09 Time 09:30 Sent To  
Notes
2017-02-13 09:49:00B30

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-06-30 Cont ID  
Sent By ccole Date 2017-06-30 Time 08:18 Rev Time 0.00
Received By ccole Date 2017-06-29 Time 17:34 Sent To Z
Notes
2017-06-30 08:35:592ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17020366
 6/30/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE RESUBMITTED PLANS DO NOT APPREAR TO BE CORRECTED
 PER THE 1ST REVIEW COMMENTS. MANY OF THE DEFICIENCIES
 STILL EXIST, AND NO NARRATIVE FROM THE ENGINEER WAS
 SUBMITTED IN RESPONSE WHICH TYPICALLY HELPS TO CLARIFY
 AND EXPEDITE THE REVIEW PROCESS. I AM REPRINTING THE
 1ST REVIEW COMMENTS BELOW. PLEASE NOTE THAT THE
 BUILDING PLAN REVIEWER'S SECOND REVIEW COMMENTS ARE
 STATING THAT THE RESUBMITTED PLANS ARE INDICATING A NEW
 SECOND FLOOR WALL MUST BE CONSTRUCTED TO SEPARATE THE
 ATRIUM FROM THE SECOND FLOOR LEVEL. THIS REQUIRED
 REDESIGN WILL OBVIOUSLY IMPACT THE CURRENT HVAC DESIGN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 1ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020366
 2/14/17
  
 1) SHEET M1.01: THE SUMMARY "WHOLE SYSTEM HEAT LOADS"
 ARE INCOMPLETE- SEE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION AND PROVIDE CALCULATIONS IN ACCORDANCE
 WITH ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N. SUMMARY
 CALCULATIONS PER THE EXCEPTION MUST INCLUDE ITEMS 1-13,
 BE PERFORMED FOR EACH ZONE, AND BE SUBMITTED ON A
 SIGNED AND SEALED SUMMARY SHEET.
  
 2) M1.01: PLEASE BREAKDOWN THE VENTILATION CALCULATIONS
 FOR THE BEAUTY/NAIL SALON TO PROVIDE 50 CFM PER NAIL
 TABLE AND 0.60 CFMS PER SF FOR THE SALON. THE CURRENT
 PLAN APPEARS TO BE NON-COMPLIANT WITH ONLY THE EF-1
 FUNCTIONING IN THE AREA.
  
 3) M1.01 & M1.02: THE PLAN INDICATES AIR IN THE BEAUTY
 SALON IS BEING RECIRCULATED INTO OTHER ROOMS AND SPACES
 WHICH IS PROHIBITED PER TABLE 403.3 FOOTNOTE B- PLEASE
 CORRECT.
  
 4) M1.01: EXHAUST VENTILATION IS REQUIRED FOR THE
 SHOWER- SEE TABLE 403.3 AND PROVIDE A SYSTEM.
  
 5) M1.01: INDICATE HOW OUTSIDE AIR IS BEING SUPPLIED TO
 AHU-1.
  
 6) M1.02: CLARIFY THE PURPOSE OF EF-1 IN THE WALL BY
 THE ELEVATOR AND INDICATE HOW THE FAN WAS SIZED-
 PROVIDE A CALCULATION.
  
 7) PLEASE CLARIFY WHAT TYPE OF "TREATMENT" IS PERFORMED
 IN THE VARIOUS ROOMS SHOWN ON THE PLAN SO A COMPLETE
 MECHANICAL REVIEW CAN BE ACCOMPLISHED.
  
 8) PROVIDE AN AIR BALANCE CALCULATION.
  
 9) PROVIDE CHILLED WATER AND CONDENSATE PIPING DETAILS-
 TYPE OF PIPING, TYPE OF INSULATION AND INSULATION
 THICKNESSES,
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-14 Cont ID  
Sent By ccole Date 2017-02-14 Time 07:51 Rev Time 0.00
Received By ccole Date 2017-02-13 Time 17:44 Sent To  
Notes
2017-02-14 09:21:391ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020366
 2/14/17
  
 1) SHEET M1.01: THE SUMMARY "WHOLE SYSTEM HEAT LOADS"
 ARE INCOMPLETE- SEE SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION AND PROVIDE CALCULATIONS IN ACCORDANCE
 WITH ASHRAE/ACCA STANDARD 183 OR ACCA MANUAL N. SUMMARY
 CALCULATIONS PER THE EXCEPTION MUST INCLUDE ITEMS 1-13,
 BE PERFORMED FOR EACH ZONE, AND BE SUBMITTED ON A
 SIGNED AND SEALED SUMMARY SHEET.
  
 2) M1.01: PLEASE BREAKDOWN THE VENTILATION CALCULATIONS
 FOR THE BEAUTY/NAIL SALON TO PROVIDE 50 CFM PER NAIL
 TABLE AND 0.60 CFMS PER SF FOR THE SALON. THE CURRENT
 PLAN APPEARS TO BE NON-COMPLIANT WITH ONLY THE EF-1
 FUNCTIONING IN THE AREA.
  
 3) M1.01 & M1.02: THE PLAN INDICATES AIR IN THE BEAUTY
 SALON IS BEING RECIRCULATED INTO OTHER ROOMS AND SPACES
 WHICH IS PROHIBITED PER TABLE 403.3 FOOTNOTE B- PLEASE
 CORRECT.
  
 4) M1.01: EXHAUST VENTILATION IS REQUIRED FOR THE
 SHOWER- SEE TABLE 403.3 AND PROVIDE A SYSTEM.
  
 5) M1.01: INDICATE HOW OUTSIDE AIR IS BEING SUPPLIED TO
 AHU-1.
  
 6) M1.02: CLARIFY THE PURPOSE OF EF-1 IN THE WALL BY
 THE ELEVATOR AND INDICATE HOW THE FAN WAS SIZED-
 PROVIDE A CALCULATION.
  
 7) PLEASE CLARIFY WHAT TYPE OF "TREATMENT" IS PERFORMED
 IN THE VARIOUS ROOMS SHOWN ON THE PLAN SO A COMPLETE
 MECHANICAL REVIEW CAN BE ACCOMPLISHED.
  
 8) PROVIDE AN AIR BALANCE CALCULATION.
  
 9) PROVIDE CHILLED WATER AND CONDENSATE PIPING DETAILS-
 TYPE OF PIPING, TYPE OF INSULATION AND INSULATION
 THICKNESSES,
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-06-28 Cont ID  
Sent By gjohnson Date 2017-06-28 Time 14:31 Rev Time 0.00
Received By gjohnson Date 2017-06-28 Time 14:16 Sent To  
Notes
2017-06-28 14:42:402ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 2ND REQUEST NOT COMPLIED
  
 1. GRAB BARS SHALL BE INSTALLED ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE,PER FBC ACC
 609.4
  
 2. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. PER FBC ACC 604.7
  
 3. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION, PER FBC
 ACC 604.2
  
 4. PROVIDE DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH
 FBC ACC 608 PER FBC ACC 213.3.6
 A) 608.2.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS SHALL BE 30
 INCHES (760 MM) WIDE MINIMUM BY 60 INCHES (1525 MM)
 DEEP MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES
 (1525 MM) WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT.
 B) 608.2.2.1 CLEARANCE.
 A 30 INCH (760 MM) WIDE MINIMUM BY 60 INCH (1525 MM)
 LONG MINIMUM CLEARANCE SHALL BE PROVIDED ADJACENT TO
 THE OPEN FACE OF THE SHOWER COMPARTMENT.
 C) 608.3.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 WHERE A SEAT IS PROVIDED IN STANDARD ROLL-IN TYPE
 SHOWER COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THE
 BACK WALL AND THE SIDE WALL OPPOSITE THE SEAT. GRAB
 BARS SHALL NOT BE PROVIDED ABOVE THE SEAT. WHERE A SEAT
 IS NOT PROVIDED IN STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS, GRAB BARS SHALL BE PROVIDED ON THREE
 WALLS. GRAB BARS SHALL BE INSTALLED 6 INCHES (150 MM)
 MAXIMUM FROM ADJACENT WALLS.
 D) 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR. WHERE A SEAT
 IS PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY
 UNIT SHALL BE INSTALLED ON THE BACK WALL ADJACENT TO
 THE SEAT WALL AND SHALL BE LOCATED 27 INCHES (685 MM)
 MAXIMUM FROM THE SEAT WALL.
  
  
 5. PROVIDE SANITARY AND WATER RISER DIAGRAM . PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 5. PROVIDE MANUFACTURE SPECS FOR SUMP PUMP AND OIL
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-17 Cont ID  
Sent By gjohnson Date 2017-02-17 Time 16:17 Rev Time 0.00
Received By gjohnson Date 2017-02-17 Time 14:42 Sent To  
Notes
2017-02-17 16:33:541ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE INSTALLED ABOVE THE FINISH FLOOR
 MEASURED TO THE TOP OF THE GRIPPING SURFACE,PER FBC ACC
 609.4
  
 2. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. PER FBC ACC 604.7
  
 3. THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION, PER FBC
 ACC 604.2
  
 4. PROVIDE DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH
 FBC ACC 608 PER FBC ACC 213.3.6
  
 5. PROVIDE SANITARY AND WATER RISER DIAGRAM . PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 5. PROVIDE MANUFACTURE SPECS FOR SUMP PUMP AND OIL
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2017-06-26 Cont ID  
Sent By jwitmer Date 2017-06-26 Time 06:34 Rev Time 0.00
Received By jwitmer Date 2017-06-26 Time 06:34 Sent To  
Notes
2017-06-26 06:34:41SEE BUILDING COMMENTS.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2017-02-15 Cont ID  
Sent By jwitmer Date 2017-02-15 Time 11:33 Rev Time 0.00
Received By jwitmer Date 2017-02-15 Time 11:31 Sent To  
Notes
2017-02-15 11:33:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020366
 ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2(A)
 CONT: TBD
 TEL: 561-358-9909
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. FEB. 15/ 2017
 ACTION: DENIED
  
 1) SHEET A-0.01 UNDER THE HEADING LIST THIS BUILDING
 TYPE TO BE A BUILDING TYPE IIA. PLEASE NOTE ABOVE THE
 1ST FLOOR LEVEL THIS HIGH RISE IS A R2 OCCUPANCY TYPE.
 PLEASE NOTE THIS IS A 20 STORY HIGH RISE, THE MINIMUM
 BUILDING TYPE REQUIRED WOULD BE TYPE IA SEE 2014 FBC-B
 TABLE 503.
  
 2) SINCE THERE IS STRUCTURAL WORK BEING COMPLETED UNDER
 THIS PERMIT AND THIS BUILDING IS A 20 STORY HIGHRISE IT
 QUALIFIES AS A THRESHOLD BUILDING. THRESHOLD BUILDING /
 FL S. S. 553.71(7) ?THRESHOLD BUILDING" MEANING ANY
 BUILDING WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN
 HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 FORMS E-MAILED TO: [email protected] 02/15/2017
 11:29AM
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2017-07-17 Cont ID  
Sent By eschneid Date 2017-07-17 Time 12:48 Rev Time 0.50
Received By eschneid Date 2017-07-17 Time 12:48 Sent To  
Notes
2017-07-17 13:38:12FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) REPEAT COMMENT: PLEASE CLARIFY WHAT THIS USE OF THIS
 SPACE WILL BE. THERE ARE TREATMENT ROOMS LISTED ON THE
 PLANS. MEDICAL OFFICE IS NOT PERMITTED AS THE SOUTH
 TOWER COMMERCIAL SPACES ARE ESTABLISHED FOR RETAIL. A
 CHANGE OF USE FROM RETAIL TO MEDICAL OFFICE REQUIRES
 THE APPROVAL OF A MINOR PLANNED DEVELOPMENT AMENDMENT
 AND MAY REQUIRE AN INCREASE IN THE NUMBER OF REQUIRED
 PARKING SPACES. PLEASE NOTE THAT A SALON/SPA (NO
 MEDICAL TREATMENTS) IS CLASSIFIED AS RETAIL WITHIN THE
 CITYPLACE DEVELOPMENT AND WOULD NOT BE A CHANGE OF USE
 FOR THE GROUND FLOOR SPACE. IN A PHONE DISCUSSION WITH
 THE APPLICANT, THIS WAS SAID TO BE A SPA NOT MEDICAL.
 THIS NEEDS TO BE CLEARLY INDICATED ON THE PLANS, TO
 INCLUDE THE CHARTS CALLING OUT "TREATMENT" ROOMS.
  
 2) REPEAT COMMENT: COMMERCIAL BAY CU-1 WAS APPROVED AS
 A 1,903 SQUARE FOOT GROUND FLOOR RETAIL BAY. THE
 MEZZANINE SPACE IS NOT INCLUDED IN THE RETAIL
 CALCULATION FOR REQUIRED PARKING. IT MAY ONLY BE USED
 FOR STORAGE. A CHANGE IN USE FROM STORAGE TO ANOTHER
 USE REQUIRES THE APPROVAL OF A MINOR PLANNED
 DEVELOPMENT AMENDMENT AND MAY REQUIRE AN INCREASE IN
 THE NUMBER OF REQUIRED PARKING SPACES. THE PARKING FOR
 THE COMMERCIAL SPACES WAS APPROVED AT ONE PARKING SPACE
 PER 250 SQUARE FEET. CHANGING THIS AREA TO RETAIL
 REQUIRES 1.316 ADDITIONAL PARKING SPACES.
  
 3) REPEAT COMMENT: THE PLANS SHOW THE EXPANSION OF THE
 MEZZANINE AREAS. THE ADDITIONAL 299 SQUARE FEET
 REQUIRES THE APPROVAL OF A MINOR PLANNED DEVELOPMENT
 AMENDMENT AND DOES REQUIRE AN INCREASE IN THE NUMBER OF
 REQUIRED PARKING SPACES DEPENDING ON WHAT THE USE IS
 CLASSIFIED AS. THE ADDITION OF THIS AREA AS RETAIL
 REQUIRES AN ADDITIONAL 1.196 PARKING SPACES. TOTAL
 PARKING SPACES FOR ALL OF THE PROPOSED SQUARE FOOTAGE
 (IF RETAIL) IS 2.512 ROUNDED TO 3 ADDITIONAL REQUIRED
 PARKING SPACES.
  
 4) REPEAT COMMENT: THE BUILDING PLANS ON RECORD WITH
 THE CITY DO NOT SHOW A DOOR FROM THE HALLWAY TO THE
 MEZZANINE. THIS NEEDS TO BE SHOWN AS NEW CONSTRUCTION
 ON THE PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
2017-07-05 09:36:11ROUTED TO ERIC SCHNEIDER

Review Stop Z ZONING
Rev No 1 Status F Date 2017-03-06 Cont ID  
Sent By eschneid Date 2017-03-06 Time 16:25 Rev Time 1.00
Received By eschneid Date 2017-03-03 Time 16:55 Sent To  
Notes
2017-03-06 16:25:36PLEASE PROVIDE WRITTEN RESPONSES.
  
 1) PLEASE CLARIFY WHAT THIS USE OF THIS SPACE WILL BE.
 THERE ARE TREATMENT ROOMS LISTED ON THE PLANS. MEDICAL
 OFFICE IS NOT PERMITTED AS THE SOUTH TOWER COMMERCIAL
 SPACES ARE ESTABLISHED FOR RETAIL. A CHANGE OF USE FROM
 RETAIL TO MEDICAL OFFICE REQUIRES THE APPROVAL OF A
 MINOR PLANNED DEVELOPMENT AMENDMENT AND MAY REQUIRE AN
 INCREASE IN THE NUMBER OF REQUIRED PARKING SPACES.
 PLEASE NOTE THAT A SALON/SPA (NO MEDICAL TREATMENTS) IS
 CLASSIFIED AS RETAIL WITHIN THE CITYPLACE DEVELOPMENT
 AND WOULD NOT BE A CHANGE OF USE FOR THE GROUND FLOOR
 SPACE.
  
 2) COMMERCIAL BAY CU-1 WAS APPROVED AS A 1,903 SQUARE
 FOOT GROUND FLOOR RETAIL BAY. THE MEZZANINE SPACE IS
 NOT INCLUDED IN THE RETAIL CALCULATION FOR REQUIRED
 PARKING. IT MAY ONLY BE USED FOR STORAGE. A CHANGE IN
 USE FROM STORAGE TO ANOTHER USE REQUIRES THE APPROVAL
 OF A MINOR PLANNED DEVELOPMENT AMENDMENT AND MAY
 REQUIRE AN INCREASE IN THE NUMBER OF REQUIRED PARKING
 SPACES.
  
 3) THE PLANS SHOW THE EXPANSION OF THE MEZZANINE AREAS.
 THE ADDITIONAL 299 SQUARE FEET REQUIRES THE APPROVAL OF
 A MINOR PLANNED DEVELOPMENT AMENDMENT AND DOES REQUIRE
 AN INCREASE IN THE NUMBER OF REQUIRED PARKING SPACES
 DEPENDING ON WHAT THE USE IS CLASSIFIED AS.
  
 4) THE BUILDING PLANS ON RECORD WITH THE CITY DO NOT
 SHOW A DOOR FROM THE HALLWAY TO THE MEZZANINE. THIS
 NEEDS TO BE SHOWN AS NEW CONSTRUCTION ON THE PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  