Plan Review Details - Permit 17020362
Plan Review Stops For Permit 17020362
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-02-21 Cont ID  
Sent By jwitmer Date 2017-02-21 Time 16:09 Rev Time 0.00
Received By jwitmer Date 2017-02-17 Time 16:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-03-07 Cont ID  
Sent By jleahy Date 2017-03-07 Time 10:27 Rev Time 0.00
Received By jleahy Date 2017-03-06 Time 16:32 Sent To  
Notes
2017-03-07 10:31:42PROVISO
  
 1) PROVIDE FAULT CURRENT CALCULATION AND SIGNAGE FOR
 THE NEW TRANSFORMER. PER 110.24 (A)(B)
  
 2) PROVIDE INTERIOR POWER ALLOWANCES PER FBC EC 405.5.2
  
 3) PROVIDE THIS INFORMATION PRIOR TO THE FINAL
 INSPECTION.
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-02-22 Cont ID  
Sent By scaldero Date 2017-02-22 Time 13:19 Rev Time 0.00
Received By scaldero Date 2017-02-22 Time 13:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-13 Cont ID  
Sent By ccole Date 2017-03-13 Time 11:48 Rev Time 0.00
Received By ccole Date 2017-03-10 Time 16:40 Sent To  
Notes
2017-03-10 16:40:34CCOLE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-08 Cont ID  
Sent By gjohnson Date 2017-03-08 Time 11:41 Rev Time 0.00
Received By gjohnson Date 2017-02-09 Time 11:56 Sent To  
Notes
2017-02-10 11:56:22C04

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-02-21 Cont ID  
Sent By jwitmer Date 2017-02-21 Time 15:53 Rev Time 0.00
Received By jwitmer Date 2017-02-17 Time 16:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-13 Cont ID  
Sent By ccole Date 2017-03-13 Time 11:48 Rev Time 0.00
Received By ccole Date 2017-03-13 Time 11:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-14 Cont ID  
Sent By ccole Date 2017-02-14 Time 11:13 Rev Time 0.00
Received By ccole Date 2017-02-14 Time 11:13 Sent To  
Notes
2017-02-14 11:42:041ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020362
 2/14/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) M2.1: THE NEW FPT-11-12 APPEARS TO BE SUPPLYING 1400
 CFMS OF AIR, HOWEVER THE SCHEDULE ON M4.1 INDICATES A
 DESIGN AIRFLOW OF 900 CFMS- PLEASE CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-03-08 Cont ID  
Sent By gjohnson Date 2017-03-08 Time 11:40 Rev Time 0.00
Received By gjohnson Date 2017-03-08 Time 10:41 Sent To  
Notes
***NONE***