2017-02-16 04:51:09 | 1) THE POOL HEATER SHALL COMPLY WITH THE 2014 |
| FBC-ENERGY CODE SEC. R403.9, R403.9.1, R403.9. SUBMIT |
| POOL HEATER SPECIFICATIONS THAT SHOW THE HEATER |
| COMPLIES WITH THESE CODE REQUIREMENTS. 2ND REQUEST. |
| 2) HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH A VAPOR |
| - RETARDANT COVER ON OR AT THE WATER SURFACE OR A |
| LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT |
| LOSS.FBC-ENERGY 403.9.3. |
| 3) THE TOTAL BTU LOAD SHOWN ON THE GAS PLAN IS 204,000 |
| BTU'S BUT I CALCULATE 429,000 BTU'S. CLARIFY. |
| 4) THE SIZING OF THE GAS PIPING SHALL COMPLY WITH 2014 |
| FBC-FUEL GAS SEC.402.4 USING THE LONGEST LENGTH OF |
| PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE BTU LOAD OF THE SECTION. THE MINIMUM |
| PIPE SIZE OF THE GALVANIZED LINE ON THE HOUSE SIDE OF |
| THE GAS METER SHALL BE A MINIMUM OF 1 1/4 INCHES. SHOW |
| THIS ON THE GAS DRAWING.WHERE ARE YOU GETTING THE 10 |
| FEET FROM? THE "LENGTH IN FEET" COLUMN ON THE GAS TABLE |
| MUST BE USED FOR SIZING ALL SECTIONS OF THE GAS SYSTEM. |
| SINCE THE PLANS SHOW THE LONGEST RUN AS 32 FEET, THE 40 |
| FEET COLUMN MUST BE USED FOR SIZING ALL SECTIONS OF |
| PIPE. |
| 5) HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH A VAPOR |
| - RETARDANT COVER ON OR AT THE WATER SURFACE OR A |
| LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT |
| LOSS.FBC-ENERGY 403.9.3. I REALIZE THIS IS THE |
| RESPONSIBILITY OF THE POOL CONTRACTOR AND I WILL PLACE |
| THIS NOTE ON YOUR PLANS. YOU DO NOT NEED TO RESPOND TO |
| THIS COMMENT. |
| |
| PLEASE CALL ME TO DISCUSS THESE COMMENTS SO WE CAN TRY |
| TO GET THIS PERMIT ISSUED. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| [email protected] |
| |