2017-02-22 11:04:32 | BUILDING PLAN REVIEW |
| W. P. B. REVISION: 17020270 |
| W. P. B. PERMIT: 16090562 |
| ADD: 600 OKEECHOBEE BLVD./RENOVATION SOUTH POOL BAR |
| CONT: HEDRICK BROTHERS |
| TEL: 561-267-1309 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. FEB. 22/ 2017 |
| ACTION: DENIED |
| |
| 1) SHEET A1.0; |
| |
| 1A) THE PLANS INDICATE A REVISION # 3 A 72 INCH TALL |
| WOOD STORAGE UNIT THAT IS NEXT TO A GRILL. PLEASE |
| SUBMIT THE MANUFACTURERS SPECIFICATIONS FOR THE GRILL |
| HOW CLOSE COMBUSTIBLES CAN BE LOCATED TO THE GRILL. |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 1B) THE NORTH SIDE OF THE BAR SHOWS A REVISION A NEW |
| BAR AT THE HEIGHT OF 48 INCHES THERE IS A NOTE SEE |
| STRUCTURALS. NO STRUCTURAL PLANS WERE SUBMITTED, THERE |
| IS NO CUT SECTION THROUGH THIS PORTION OF THE BAR TO |
| REFERENCE WHICH SECTION TO USE. IN THE ORIGINAL |
| PERMITED PLANS THERE ARE (2) SECTIONS THROUGH THE WALL |
| IN QUESTION DETAIL 2 & 4 / S5.1 NEITHER OF THESE |
| DETAILS SHOW THE STEEL IN THE BOND BEAM. DETAIL # 1 |
| SHEET S5.1 DOES SHOW THE REQUIRED VERTICAL STEEL AND |
| BOND BEAM STEEL AS WELL. PLEASE ADD CUT SECTION TO |
| CLARIFY THE DETAILS. 107.2.1.3 ADDITIONAL INFORMATION |
| IS REQUIED. |
| |
| 1C) THE DESIGNER OF RECORD DOES NOT STATE WHAT THE BAR |
| TOPS WILL BE MADE. NOR DOES THE PLANS INDICATE THAT THE |
| TRELLIS WORK AND COLUMN HAS TO GO IN BEFORE THE BAR TOP |
| IS INSTALLED. NOTE SHEET S5.1 DETAIL 1 SHOWS THE |
| TRELLIS COLUMN MOUNTED DIRECTLY TO THE BLOCK WALL, THE |
| ANCHOR NOT SPECIFIED, NOR IS THE WIND DESIGN CRITERIA |
| NEEDED FOR THE DELEGATE ENGINEERING OF THE TRELLIS. THE |
| PLANS DO NOT PROVIDE WHAT MATERIALS THE TRELLIS WORK |
| HAS TO BE MADE FROM, THIS IS PART OF A TYPE IA |
| BUILDING. SEE TABLE 601. THE PLANS ARE ALSO SILENT IF |
| THERE IS TO BE ANY CANOPY TO KEEP THE RAIN OUT? |
| 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 1D) SECTION LINE 5/ A1.1 IS THROUGH THE ACCESSIBLE |
| COUNTERTOP BUT WHEN YOU VIEW DETAIL # 5 ON SHEET A1.1 |
| THE HEIGHT OF THE BAR TOP IS 3 FOOT 7 INCHES OR THE NEW |
| COUNTER TOP IS AT 43 INCHES? 2014 FBC-ACCESSIBILITY |
| CODE 902.3 HEIGHT. THE TOPS OF DINING SURFACES SURFACES |
| SHALL BE 28 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE |
| THE FINISH FLOOR OR GROUND. |
| |
| 1E) BUILDING PROVISO: THE NEW TRELLIS AND COLUMNS BY |
| DELEGATE ENGINEER. 61G15-30.003 ENGINEERING DOCUMENT |
| CLASSIFICATION. FL 61G-15-30.006 (3) THE DELEGATED |
| ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING |
| DOCUMENTS TO THE ENGINEER OF RECORD FOR REVIEW. |
| |
| 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES |
| DEPARTMENT |