Review Stop G GAS REVIEW
Rev No 3 Status P Date 2017-06-05 Cont ID  
Sent By tklarge Date 2017-06-05 Time 06:25 Rev Time 0.00
Received By tklarge Date 2017-06-05 Time 06:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2017-06-05 Cont ID  
Sent By tklarge Date 2017-05-19 Time 06:56 Rev Time 0.00
Received By tklarge Date 2017-05-19 Time 06:33 Sent To  
Notes
2017-05-19 06:56:36 
 1.) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. 2ND
 REQUEST.
 2) SHOW THE PIPE SIZE SUPPLYING THE POOL HEATER
 DOWNSTREAM OF THE REGULATOR.
 3) SHOW THE PIPE SIZE SUPPLYING THE TANKLESS WATER
 HEATER.
 4) A SHUTOFF VALVE SHALL BE LOCATED IMMEDIATELY AHEAD
 OF EACH REGULATOR. (SEE POOL HEATER) FBCR SEC.G2420.4.
 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC.107.2.1. PLEASE BE AWARE
 THAT MOST MANUFACTURER'S REQUIRE 4 FEET FROM OPERABLE
 DOORS AND WINDOWS FOR OUTDOOR UNITS. 2ND REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-02-09 Cont ID  
Sent By tklarge Date 2017-02-09 Time 06:28 Rev Time 0.00
Received By tklarge Date 2017-02-09 Time 06:24 Sent To  
Notes
2017-02-08 15:15:04 
 1.)SHOW THE LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014
 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES
 SEC. G2413.
  
 2.) SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3.) SHOW THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS
 SECS.401.8 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4
 (37) OR 2014 FBC-RES. SEC. G2413.
  
 4) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR ) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 5.) INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 6) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 7) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
  
 8) A SHUTOFF VALVE SHALL BE LOCATED IMMEDIATELY AHEAD
 OF EACH REGULATOR.
  
 9) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE
 LOCATION OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE HOUSE
 PLAN CAN BE HAND DRAWN.
  
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-06-05 Cont ID  
Sent By tklarge Date 2017-06-05 Time 06:25 Rev Time 0.00
Received By tklarge Date 2017-05-30 Time 10:59 Sent To  
Notes
2017-05-31 10:59:38RESUB OF REVISION ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-19 Cont ID  
Sent By tklarge Date 2017-05-19 Time 06:56 Rev Time 0.00
Received By tklarge Date 2017-05-17 Time 14:34 Sent To  
Notes
2017-05-18 14:34:58RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-09 Cont ID  
Sent By tklarge Date 2017-02-09 Time 06:57 Rev Time 0.00
Received By tklarge Date 2017-02-06 Time 13:54 Sent To  
Notes
2017-02-07 13:54:36REVISION ROUTED TO TKLARGE