Plan Review Details - Permit 17020091
Plan Review Stops For Permit 17020091
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-02-06 Cont ID  
Sent By cpuell Date 2017-02-08 Time 10:56 Rev Time 0.00
Received By vperez Date 2017-02-06 Time 08:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-15 Cont ID  
Sent By lmarchan Date 2017-02-15 Time 07:51 Rev Time 0.00
Received By lmarchan Date 2017-02-14 Time 15:37 Sent To  
Notes
2017-02-14 15:38:07REVISION ROUTED TO JVALIDO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-08 Cont ID  
Sent By cpuell Date 2017-02-08 Time 10:56 Rev Time 0.00
Received By cpuell Date 2017-02-02 Time 14:57 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-02-14 Cont ID  
Sent By jvalido Date 2017-02-14 Time 17:50 Rev Time 0.00
Received By jvalido Date 2017-02-14 Time 17:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-07 Cont ID  
Sent By jvalido Date 2017-02-07 Time 17:32 Rev Time 0.00
Received By jvalido Date 2017-02-07 Time 16:45 Sent To  
Notes
2017-02-07 17:17:28CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 606.2.1 RETURN AIR SYSTEMS.
 SMOKE DETECTORS SHALL BE INSTALLED IN RETURN AIR
 SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM
 (0.9 M3/S) IN THE RETURN AIR DUCT OR PLENUM UPSTREAM OF
 ANY FILTERS, EXHAUST AIR CONNECTIONS, OUTDOOR AIR
 CONNECTIONS, OR DECONTAMINATION EQUIPMENT AND
 APPLIANCES.
  
 (1) MANUFACTURER SPECIFICATIONS OF THE RTU SPECIFIED ON
 THE PLANS ( ALLIED ZCA060S4BNX32330) HAVE A DESIGN
 CAPABILITY OF 2400 CFM MAXIMUM. AS PER 606.2.1 FBC
 MECHANICAL 2014 SMOKE DUCT DETECTORS ARE REQUIRED IN
 THE RETURN AIR.
  
 (2) PROVIDE APPROVED TIE DOWN DETAILS FOR ROOF CURB TO
 ROOF AND RTU TO CURB.
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  