Plan Review Details - Permit 17020087
Plan Review Stops For Permit 17020087
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2019-04-04 Cont ID  
Sent By tklarge Date 2019-04-04 Time 09:28 Rev Time 0.00
Received By tklarge Date 2019-04-04 Time 09:28 Sent To  
Notes
2019-04-04 09:28:46REVISED GAS DRAWING & CHANGE OF CONTRACTOR.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-02-13 Cont ID  
Sent By tklarge Date 2017-02-13 Time 10:00 Rev Time 0.00
Received By tklarge Date 2017-02-13 Time 09:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-02-06 Cont ID  
Sent By tklarge Date 2017-02-06 Time 09:21 Rev Time 0.00
Received By tklarge Date 2017-02-06 Time 09:04 Sent To  
Notes
2017-02-06 09:21:261) SHOW THE TYPE OF PIPE AND PIPE SIZE OF THE SUPPLY
 LINE FROM THE METER. THE LINE SHALL BE SIZED FOR THE
 TOTAL BTU LOAD ON THE SYSTEM.
 2) SHOW THE PIPE SIZE OF THE UNDERGROUND PE LINE
 BETWEEN THE METER AND THE BRANCH FOR THE TTANKLESS
 WATER HEATER.
 3) THE PLAN SHOWS A TOTAL BTU LOAD OF 299,000 BTU'S BUT
 I CALCULATE A TOTAL OF 359,000 BTU'S. CLARIFY.
 4) THE FUTURE LINE FOR THE BBQ SHALL BE EQUIPPED WITH A
 VALVE, REGULATOR, NIPPLE AND CAP.
 5) REMOVE THE SPECIFICATIONS FOR THE PIPE FROM THE
 PERMIT PACKAGE. THIS INFORMATION IS NOT REQUIRED AT
 THIS TIME.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-13 Cont ID  
Sent By tklarge Date 2017-02-13 Time 10:00 Rev Time 0.00
Received By tklarge Date 2017-02-07 Time 12:53 Sent To  
Notes
2017-02-08 12:53:39RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-06 Cont ID  
Sent By tklarge Date 2017-02-06 Time 09:21 Rev Time 0.00
Received By tklarge Date 2017-02-02 Time 14:30 Sent To  
Notes
2017-02-03 14:30:30PLUMB -$5000