Plan Review Details - Permit 17020058
Plan Review Stops For Permit 17020058
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-05-12 Cont ID  
Sent By shill Date 2017-05-12 Time 07:30 Rev Time 0.00
Received By shill Date 2017-05-12 Time 07:25 Sent To  
Notes
2017-05-12 07:40:39****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020058
 ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2
 CONT: BRANCH CONSTRUCTION
 TEL: 561-833-6206
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 SHEET 02-A SHOWS THE BREAKROOM DOOR # 06 DOES NOT
 COMPLY WITH 2014 ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES. MINIMUM MANEUVERING CLEARANCES AT DOORS AND
 GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES
 SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE
 REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 3RD REVIEW - APPLICANT HAS PROPOSED A RESOLUTION VIA
 EMAIL. THIS PERMIT IS ISSUED WITH PROVISO - REVISE
 SHEET 03-A AND OTHER AFFECTED SHEETS, BREAK ROOM 05
 DOOR TO COMPLY WITH FBC A 404.2.4 PRIOR TO FINAL
 INSPECTION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-04-25 Cont ID  
Sent By shill Date 2017-04-25 Time 15:09 Rev Time 0.00
Received By shill Date 2017-04-25 Time 15:09 Sent To  
Notes
2017-04-25 15:33:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020058
 ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2
 CONT: BRANCH CONSTRUCTION
 TEL: 561-833-6206
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1-4) OK
  
 5) SHEET 02-A SHOWS THE BREAKROOM DOOR # 06 DOES NOT
 COMPLY WITH 2014 ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES. MINIMUM MANEUVERING CLEARANCES AT DOORS AND
 GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES
 SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE
 REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 2ND REVIEW, THE BREAK ROOM DOOR LACKS THE REQUIRED 18"
 MANEUVERING CLEARANCE, PULL SIDE.
  
 6-7) OK
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-03 Cont ID  
Sent By jwitmer Date 2017-02-03 Time 16:13 Rev Time 0.00
Received By jwitmer Date 2017-02-03 Time 14:36 Sent To  
Notes
2017-02-03 16:13:32BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17020058
 ADD: 550 OKEECHOBEE BLVD. SUITE # CU-2
 CONT: BRANCH CONSTRUCTION
 TEL: 561-833-6206
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 03/ 2017
 ACTION: DENIED
  
 1) SHEET 01-A THE COVERSHEET LIST THIS BUILDING AS A
 BUILDING TYPE III-B. PLEASE NOTE THIS IS A 20 STORY
 HIGH RISE BUILDING. PLEASE CORRECT TO A MINIMUM
 BUILDING TYPE I-A CONSTRUCTION, SEE 2014 FBC-B TABLE
 503.
  
 2) SHEET 01-A THE COVERSHEET ALSO LIST THE OCCUPANCY
 TYPE AS A-2 ASSEMBLY AND B OCCUPANCY. THE OCCUPANCY
 TYPE PER SECTION 304.1 IS A B/ BUSINESS OCCUPANCY.
  
 3) SHEET 01-A THE COVERSHEET ALSO LIST THE BUILDING
 FIRE PROTECTION AS UNPROTECTED / SPRINKLERED NEW
 SYSTEM. PLEASE PROVIDE THE MEANING OF UNPROTECTED. IN
 THE 2014 FBC-B TABLE 601 THE BUILDING ELEMENT TABLE
 REQUIRES ALL STRUCTURAL ELEMENTS TO BE FIRE RATED IN
 HOURS.
  
 4) SHEET 01-A THE COVERSHEET ALSO LIST THE OCCUPANT
 LOAD AS 10 IN THE UPPER RIGHT HAND CORNER OF THE SHEET,
 BUT IN THE LOWER RIGHT CORNER OF THE SHEET THE HEADING
 OF BUILDING DATA AND A/C CALCULATIONS BOTH INDICATE THE
 SQUARE FOOTAGE OF THE TENANT SPACE AS 1,182 SQUARE
 FEET. 1,182/100= 12 OCCUPANTS TABLE 1004.1.2.
  
 5) SHEET 02-A SHOWS THE BREAKROOM DOOR # 06 DOES NOT
 COMPLY WITH 2014 ACCESS. CODE 404.2.4 MANEUVERING
 CLEARANCES. MINIMUM MANEUVERING CLEARANCES AT DOORS AND
 GATES SHALL COMPLY WITH 404.2.4. MANEUVERING CLEARANCES
 SHALL EXTEND THE FULL WIDTH OF THE DOORWAY AND THE
 REQUIRED LATCH SIDE OR HINGE SIDE CLEARANCE.
  
 6) SHEET 02/A DOES NOT SHOW COMPLIANCE FOR THE BREAK
 ROOM SINK, COMPLIANCE WITH 2014 ACCESS. CODE
 606.3 HEIGHT.
 606.2 CLEAR FLOOR SPACE.
 606.4 FAUCETS.
 606.5 EXPOSED PIPES AND SURFACES.
  
 7) SHEET 02/A THE RECEPTION DESK DOES NOT INDICATE
 COMPLIANCE WITH 2014 FBC-ACCESS. CODE 902.3 HEIGHT. THE
 TOPS WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-11 Cont ID  
Sent By jleahy Date 2017-05-11 Time 10:57 Rev Time 0.00
Received By jleahy Date 2017-05-11 Time 10:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-02-06 Cont ID  
Sent By albarran Date 2017-02-06 Time 14:16 Rev Time 0.00
Received By albarran Date 2017-02-06 Time 13:47 Sent To  
Notes
2017-02-06 14:20:14TODAY I SPOKE W/DONNIE OF BRANCH CONSTRUCTION AND
 DISCUSSED THE MISSING SOW WINDOW AND SIGN OUTLETS. WE
 AGREED TO HAVE THE PLANS RED LINED AND THEY WILL BE
 ADDED IN THE FIELD.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-04-28 Cont ID  
Sent By pleduc Date 2017-04-28 Time   Rev Time 0.00
Received By pleduc Date 2017-04-28 Time 09:20 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-09 Cont ID  
Sent By pleduc Date 2017-02-09 Time   Rev Time 0.00
Received By pleduc Date 2017-02-08 Time 12:05 Sent To  
Notes
2017-02-09 10:12:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET O2 A - THE RESTROOM DOOR OPENS INTO THE EXIT
 CORRIDOR.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL NOT PROJECT NOT
 MORE THAN 7 IN. INTO THE REQUIRED WIDTH OF AN AISLE, A
 CORRIDOR, A PASSAGE WAY, OR A LANDING, WHEN FULLY OPEN,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENTS THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. INTO THE REQUIRED
 WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF IS FULLY
 OPEN.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 2) SHEET O2 A - THERE IS A PIECE OF FURNITURE LOCATED
 IN FRONT OF A SET OF DOUBLE DOORS THAT ARE INDICATED AS
 OPEN. THOUGH THE OTHER SET OF DOORS ARE INDICATED AS
 THE EXIT DOORS, PLEASE INDICATE IF THESE WILL BE LOCKED
 AND CLEARLY MARKED AS NOT EXIT DOORS.
  
 PLEASE REVIEW, CLARIFY AAAAAND CORRECT.
  
  
  
  
 3) SHEET O3 A - THERE IS AN EXIT SIGN IN THE CORRIDOR
 LEADING INTO TREATMENT ROOM 7; HOWEVER, THERE IS NO
 EXIT SIGN INDICATED ON SHEET E 1.
  
 HOWEVER, PER NFPA 101, CHAPTER 7, MEANS OF EGRESS -
 7.5.2 IMPEDIMENTS TO EGRESS. SEE ALSO 7.1.9 AND
 7.2.1.5.
 7.5.2.1* ACCESS TO AN EXIT SHALL NOT BE THROUGH
 KITCHENS, STOREROOMS OTHER THAN AS PROVIDED IN CHAPTERS
 36 AND 37, RESTROOMS, WORKROOMS, CLOSETS, BEDROOMS OR
 SIMILAR SPACES, OR OTHER ROOMS OR SPACES SUBJECT TO
 LOCKING, UNLESS PASSAGE THROUGH SUCH ROOMS OR SPACES IS
 PERMITTED FOR THE OCCUPANCY BY CHAPTER18, 19, 22, OR
 23.
  
 TREATMENT ROOM 7 DOOR CAN NOT BE MARKED AS AN EXIT.
  
 PLEASE CORRECT SHEET O3 A AND ENSURE AN EXIT SIGN IS
 NOT PALCED ABOVE THAT DOOR.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-12 Cont ID  
Sent By shill Date 2017-05-12 Time 07:41 Rev Time 0.00
Received By shill Date 2017-05-12 Time 07:25 Sent To  
Notes
2017-05-12 07:42:00ACCEPTED RESUBMITTAL VIA EMAIL PER AGREEMENT W/OWNER
 PROVISO; REVISION REQUIRED
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-11 Cont ID  
Sent By jleahy Date 2017-05-11 Time 10:58 Rev Time 0.00
Received By jleahy Date 2017-04-20 Time 11:49 Sent To  
Notes
2017-04-21 11:49:21B33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-15 Cont ID  
Sent By gjohnson Date 2017-02-15 Time 15:55 Rev Time 0.00
Received By gjohnson Date 2017-02-02 Time 14:38 Sent To  
Notes
2017-02-02 14:39:09B12

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-02-03 Cont ID  
Sent By jwitmer Date 2017-02-03 Time 14:36 Rev Time 0.00
Received By jwitmer Date 2017-02-03 Time 14:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-04-25 Cont ID  
Sent By ccole Date 2017-04-25 Time 12:52 Rev Time 0.00
Received By ccole Date 2017-04-25 Time 12:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-06 Cont ID  
Sent By ccole Date 2017-02-06 Time 12:35 Rev Time 0.00
Received By ccole Date 2017-02-06 Time 12:34 Sent To  
Notes
2017-02-06 12:55:061ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17020058
 2/6/17
  
 1) PROVIDE A DUCT SMOKE DETECTOR IN THE RETURN AIR
 SYSTEM OF THE NEW HEAT PUMP- SECTION 606.2.1.
  
 2) PROVIDE AN AUTOMATIC SHUTOFF DAMPER FOR THE O/A
 INTAKE DUCT- SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-04-27 Cont ID  
Sent By gjohnson Date 2017-04-27 Time 11:32 Rev Time 0.00
Received By gjohnson Date 2017-04-27 Time 11:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-15 Cont ID  
Sent By gjohnson Date 2017-02-15 Time 15:32 Rev Time 0.00
Received By gjohnson Date 2017-02-15 Time 15:32 Sent To  
Notes
2017-02-15 15:54:591ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. THE TOILET PAPER DISPENSER SHOW 0'-8' OFF THE FRONT
 OF TOILET IT SHALL BE 7 "- 9" MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. PER 604.7
  
 2. GRAB BARS SHALL BE MEASURED FROM FINISHED FLOOR TO
 TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
  
 3. SHOW CLEARANCE AROUND A WATER CLOSET SHALL BE 60
 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL. PER FBC ACC 604.3.1
  
 4. SHOW CLEAR FLOOR SPACE FOR LAV 30" X 48". PER FBC
 ACC 606.2
  
 5. SHT P-2 THE DETAIL FOR THE WATER HEATER SHOWS T+P
 DRAIN AND PAN DRAIN TERMINATING ABOVE A MOP SINK THERE
 IS NO MOP SINK SHOWN ON PLAN PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2017-05-08 Cont ID  
Sent By eschneid Date 2017-05-08 Time 16:25 Rev Time 0.50
Received By eschneid Date 2017-05-08 Time 15:50 Sent To  
Notes
2017-05-08 16:26:57COUNTS AS 1,185 SF FEET OF OFFICE PER THE ARCHITECTS
 PLAN SUBMITTED AS PART OF THE MINOR PD AMENDMENT.

Review Stop Z ZONING
Rev No 1 Status F Date 2017-02-06 Cont ID  
Sent By eschneid Date 2017-02-06 Time 16:22 Rev Time 0.25
Received By eschneid Date 2017-02-06 Time 16:22 Sent To  
Notes
2017-02-06 16:40:56FAILED
  
 1) THE COMMERCIAL UNITS ON THE GROUND FLOOR OF THE
 CITYPLACE SOUTH TOWER WERE APPROVED FOR RETAIL
 COMMERCIAL USES, NOT OFFICE. PRIOR TO ZONING APPROVAL
 OF ANY PERMITS FOR OFFICE BUILD-OUT, THE SQUARE FOOTAGE
 WOULD FIRST NEED TO BE CONVERTED FROM RETAIL TO OFFICE
 ON THE CITYPLACE DRI USE CHART, BY THE APPROVAL OF A
 MINOR PLANNED DEVELOPMENT AMENDMENT. THE MINOR PLANNED
 DEVELOPMENT AMENDMENT APPLICATION IS AVAILABLE FOR THE
 CITY'S PLANNING DIVISION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]