Plan Review Details - Permit 17020045
Plan Review Stops For Permit 17020045
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-03-09 Cont ID  
Sent By rmcdouga Date 2017-03-09 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2017-03-08 Time 18:03 Sent To  
Notes
2017-03-09 10:43:38APPROVED WITH EXCEPTIONS
  
 FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR
 THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001
 PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA
 NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM
 DESIGN PRESSURES FOR EACH OF THE STRUCTURAL MULLIONS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2017-02-17 Cont ID  
Sent By vperez Date 2017-02-17 Time 10:49 Rev Time 0.00
Received By vperez Date 2017-02-17 Time 10:40 Sent To  
Notes
2017-02-17 10:49:37SEE PROVISO ON PLANS

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-02-17 Cont ID  
Sent By gjohnson Date 2017-02-17 Time 13:10 Rev Time 0.00
Received By gjohnson Date 2017-02-17 Time 13:10 Sent To  
Notes
2017-02-17 13:16:081ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SHOW SHUT OF VALVES AND DRIP LEGAS AND REGULATORS ON
 RISER DIAGRAM. PER WPB AMEND TO FBC 107.2.1
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. PROVIDE TABLE USED FOR SIZING SYSTEM.PER WPB AMEND
 TO FBC 107.2.1
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2017-02-08 Cont ID  
Sent By fmittner Date 2017-02-08 Time 08:54 Rev Time 0.00
Received By fmittner Date 2017-02-08 Time 08:54 Sent To  
Notes
2017-02-08 08:55:35REQUIRES SUBMITTAL OF COA FOR WINDOW REPLACEMENT.
 QUESTIONS CONTACT FRIEDERIKE MITTNER, CITY HISTORIC
 PRESERVATION PLANNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-09 Cont ID  
Sent By rmcdouga Date 2017-03-09 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2017-02-01 Time 10:09 Sent To  
Notes
2017-02-02 10:10:48R01

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-08 Cont ID  
Sent By rmcdouga Date 2017-03-08 Time 18:03 Rev Time 0.00
Received By rmcdouga Date 2017-03-08 Time 17:10 Sent To  
Notes
2017-03-08 18:03:25PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 2) SHOW COMPLIANCE WITH FBC-R - M 1602.4 FOR BALANCED
 RETURN AIR.
  
 3) FBC-R - M1305.1.3 AIR-HANDLING UNITS.
 2014 FBC ENERGY CONSERVATION R403.2.4
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
  
 A PART OF YOUR AIR CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIR CONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING:
  
 1)A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION
 DRAIN IS NOT WORKING PROPERLY OR
  
 2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE
 CONDENSATION DRAIN IS NOT WORKING. TO LIMIT POTENTIAL
 DAMAGE TO YOUR HOME, AND TO AVOID DISRUPTION OF
 SERVICE, IT IS RECOMMENDED THAT YOU ENSURE PROPER
 WORKING ORDER OF THESE DEVICES BEFORE EACH SEASON OF
 PEAK OPERATION.
  
 4) SHOW THE RETURN LOCATION AND SIZE ON THE PLANS. FBC
 107.2.1
  
 5) SHOW THE LOCATION AND SIZE OF THE ATTIC ACCESS
 OPENING ON THE PLANS. FBCR-M1305.1.3
  
 6) SHOW THE CLOTHES DRYER EXHAUST DUCT AND THE BATHROOM
 EXHAUST DUCTS ON THE PLANS. FBCR - M1502, M1507 &
 FBC-R303.3
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-17 Cont ID  
Sent By gjohnson Date 2017-02-17 Time 12:45 Rev Time 0.00
Received By gjohnson Date 2017-02-17 Time 12:13 Sent To  
Notes
2017-02-17 13:10:141ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. P101 SANITARY RISER.
 A) THE DISHWASHER CAN NOT CONNECT TO A SEPARATE TRAP IT
 SHALL COMPLY WITH FBC RES P2717.2 OR P2717.3
 B) THE BRANCH DRAINS FOR BOTH WATER CLOSETS SHALL BE A
 MIN OF 3". PER FBC RES P3005.1.4
  
 2. SHUT OFF VALVES FOR THE STACKABLE WASHING MACHINE
 SHALL BE ACCESSIBLE. PER FBCRES P2903.9.3
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2017-02-08 Cont ID  
Sent By fmittner Date 2017-02-08 Time 08:54 Rev Time 0.00
Received By fmittner Date 2017-02-08 Time 08:54 Sent To  
Notes
***NONE***