2017-02-01 06:50:53 | 1) THERE IS AN EXISTING GAS SYSTEM AT THIS ADDRESS THAT |
| WAS SIZED AS A LESS THAN 2 PSI SYSTEM AND THE SUBMITTED |
| PLAN NOTES IT WILL NOW BE A 2 PSI SYTEM. REGULATORS |
| WILL BE REQUIRED ON EACH EXISTING APPLIANCE. SUBMIT |
| MANUF. SPECIFICATIONS FOR THE STEP DOWN REGULATORS THAT |
| WILL BE INSTALLED. |
| 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE |
| ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, |
| THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| OPERATING SYSTEM. FGC SECS. 401.4, 401.8, 402.1, 402.2, |
| 402.3 OR FBCR SECS.G2412.4, G2412.8, G2413.1, G2413.2, |
| G2413.3. |
| 3) SHOW THE SIZE OF THE GAS SUPPLY LINE ON THE OUTLET |
| AT THE GAS METER. THE SUPPLY LINE SHALL BE BASED ON THE |
| TYPE OF MATERIAL, THE DISTANCE TO THE FURTHEST OUTLET |
| AND THE TOTAL BTU LOAD ON THE SYSTEM. |
| 4) SHOW THE TYPE OF PIPE MATERIAL AND THE SIZE OF THE |
| PIPE THAT IS DOWNSTREAM OF THE 2 PSI REGULATOR FOR THE |
| POOL HEATER. |
| 5) SUBMIT 2 COPIES OF THE MANUFACTURERR'S |
| SPECIFICATIONS FOR THE POOL HEATER. THE POOL HEATER |
| SHALL BE LISTED AND LABELED AND COMPLY WITH THE 2014 |
| FBC-ENERGY CODE. |
| 6) A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| IMMEDIATELY AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS |
| SEC.409.4, FBC-RESIDENTIAL SEC. G 2420.4. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |