Plan Review Details - Permit 17011146
Plan Review Stops For Permit 17011146
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-02-08 Cont ID  
Sent By jwitmer Date 2017-02-08 Time 06:29 Rev Time 0.00
Received By jwitmer Date 2017-02-08 Time 06:01 Sent To  
Notes
2017-02-07 17:25:05 
 ADVISORY: 2014 FBC-B 305.1.1 LIBRARY AND READING ROOMS
 THAT ARE FOR RELIGIOUS EDUCATIONAL ROOMS AND RELIGIOUS
 AUDITORIUMS, WHICH ARE ACCESSORY TO PLACES OF RELIGIOUS
 WORSHIP IN ACCORDANCE WITH SECTION 303.1.4 AND HAVE
 OCCUPANT LOADS OF LESS THAN 100, SHALL BE CLASSIFIED AS
 GROUP A-3 OCCUPANCIES.
 IF THE LIBRARY AND READING ROOM ARE TO BE USED FOR
 OTHER THAN RELIGIOUS TEACHING AND INSTRUCTION THEN THE
 ROOM WILL NEED TO BE RECLASSIFIED AS EDUCATIONAL AND A
 CHANGE OF OCCUPANCY.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-06 Cont ID  
Sent By albarran Date 2017-02-06 Time 14:44 Rev Time 0.00
Received By albarran Date 2017-02-06 Time 14:36 Sent To  
Notes
2017-02-06 14:58:39ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 PROJECT NAME:
 JOB ADDRESS: 515 PALM STREET
 DESCRIPTION: ADDITION ON EXISTING SPACE
 MASTER PERMIT: 17011146
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
  
 1. THOUGH YOU ALLEGE NOT TO BE DOING ANY ELECTRICAL
 WORK, ON SHEET A1 YOU MENTION THE REMOVAL OF ALL
 ELECTRIC IN A WALL THAT IS TO BE DEMOLISHED.
 2. THE EXISTING LIGHTING SHALL BE COMPLIANT WITH CODE
 REQUIREMENTS. A LIGHT DENSITY ALLOWANCE CHART AS
 PROVIDED IN FBC-EC 405.5.2.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-02-02 Cont ID  
Sent By pleduc Date 2017-02-02 Time 14:44 Rev Time 0.00
Received By pleduc Date 2017-02-02 Time 12:05 Sent To  
Notes
2017-02-02 14:43:39THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: PARENTHESIS
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) FIRE INSPECTOR SHALL VERIFY FIRE ALARM AND FIRE
 SPRINKLER FUNCTION ON FIRE INSPECTION.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-08 Cont ID  
Sent By   Date 2017-02-08 Time   Rev Time 0.00
Received By lmarchan Date 2017-01-30 Time 10:48 Sent To  
Notes
2017-02-01 10:48:16B18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-02-07 Cont ID  
Sent By   Date 2017-02-07 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-06 Cont ID  
Sent By ccole Date 2017-02-06 Time 13:47 Rev Time 0.00
Received By ccole Date 2017-02-06 Time 13:47 Sent To  
Notes
2017-02-06 13:54:521ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17011146
 2/6/17
  
 1) PLEASE PROVIDE A SCOPE OF WORK FOR MECHANICAL WITH
 CORRESPONDING DRAWINGS, DETAILS, AND SPECIFICATIONS.
 PLEASE INCLUDE:
  
 A) MINIMUM VENTILATION CALCULATIONS- TABLE 403.3
  
 B) AC COOLING AND HEATING CALCULATIONS- C403.2.1 FBC-14
 ENERGY CONSERVATION CODE
  
 C) ENERGY COMPLIANCE SUBMITTAL DOCUMENTS- C101.4.3
  
 D) DUCTWORK LAYOUT PLANS AND DETAILS- SECTION 601.1
  
 E) MECHANICAL EQUIPMENT SCHEDULES.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  