Plan Review Details - Permit 17011033
Plan Review Stops For Permit 17011033
Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-27 Cont ID  
Sent By wjolin Date 2017-01-27 Time 14:41 Rev Time 0.00
Received By wjolin Date 2017-01-27 Time 14:12 Sent To M
Notes
2017-01-27 14:41:35UPDATE ARMOVER DETAIL: 9.2.3.5.2 UNSUPPORTED ARMOVER
 LENGTH WITH MAXIMUM PRESSURE EXCEEDING 100 PSI
 SUPPLYING SPRINKLERS IN A PENDENT POSITION BELOW THE
 CEILING.
 WHERE THE MAXIMUM STATIC OR FLOWING PRESSURE, WHICHEVER
 IS GREATER AT THE SPRINKLER, APPLIED OTHER THAN THROUGH
 THE FIRE DEPARTMENT CONNECTION, EXCEEDS 100 PSI AND A
 BRANCH LINE ABOVE A CEILING SUPPLIES SPRINKLERS IN A
 PENDENT POSITION BELOW THE CEILING, THE CUMULATIVE
 HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER TO A
 SPRINKLER OR SPRINKLER DROP SHALL NOT EXCEED 12-INCHES
 FOR STEEL PIPE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-31 Cont ID  
Sent By lmarchan Date 2017-01-31 Time 07:57 Rev Time 0.00
Received By lmarchan Date 2017-01-26 Time 10:50 Sent To  
Notes
2017-01-27 10:50:34ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-01-30 Cont ID  
Sent By jvalido Date 2017-01-30 Time 19:00 Rev Time 0.00
Received By jvalido Date 2017-01-30 Time 18:48 Sent To  
Notes
***NONE***