Plan Review Stops For Permit 17011033 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2017-01-27 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2017-01-27 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2017-01-27 |
Time |
14:12 |
Sent To |
M |
|
Notes |
2017-01-27 14:41:35 | UPDATE ARMOVER DETAIL: 9.2.3.5.2 UNSUPPORTED ARMOVER | | LENGTH WITH MAXIMUM PRESSURE EXCEEDING 100 PSI | | SUPPLYING SPRINKLERS IN A PENDENT POSITION BELOW THE | | CEILING. | | WHERE THE MAXIMUM STATIC OR FLOWING PRESSURE, WHICHEVER | | IS GREATER AT THE SPRINKLER, APPLIED OTHER THAN THROUGH | | THE FIRE DEPARTMENT CONNECTION, EXCEEDS 100 PSI AND A | | BRANCH LINE ABOVE A CEILING SUPPLIES SPRINKLERS IN A | | PENDENT POSITION BELOW THE CEILING, THE CUMULATIVE | | HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER TO A | | SPRINKLER OR SPRINKLER DROP SHALL NOT EXCEED 12-INCHES | | FOR STEEL PIPE. | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-01-31 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2017-01-31 |
Time |
07:57 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2017-01-26 |
Time |
10:50 |
Sent To |
|
|
Notes |
2017-01-27 10:50:34 | ROUTED TO FIRE INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2017-01-30 |
|
|
Cont ID |
|
Sent By |
jvalido |
Date |
2017-01-30 |
Time |
19:00 |
Rev Time |
0.00 |
Received By |
jvalido |
Date |
2017-01-30 |
Time |
18:48 |
Sent To |
|
|
Notes |
|
|
|