Plan Review Details - Permit 17010976
Plan Review Stops For Permit 17010976
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-05-26 Cont ID  
Sent By cthroop Date 2017-05-26 Time 12:52 Rev Time 0.00
Received By cthroop Date 2017-05-26 Time 12:52 Sent To  
Notes
2017-05-26 12:52:264X FEE PAID

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-05-12 Cont ID  
Sent By cthroop Date 2017-05-12 Time 10:19 Rev Time 0.00
Received By cthroop Date 2017-05-12 Time 09:51 Sent To P
Notes
2017-05-12 10:23:42BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 3RD REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. BUILDING REVIEW ON HOLD UNTIL $750 FEE PAID PER RB.
 PAY 4X FEE AND RE-SUBMIT.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-03-17 Cont ID  
Sent By cthroop Date 2017-03-17 Time 09:15 Rev Time 0.00
Received By cthroop Date 2017-03-17 Time 08:43 Sent To E
Notes
2017-03-17 09:18:04BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 REVISION # 17010976 TO MASTER PERMIT # 16040624
  
 1. 4 X FEE SHALL REMAIN IN EFFECT UNTIL RESINDED BY
 ROBERT BROWN, BO. REF. LETTER DATED 2/8/17 IN THIS
 SUBMITTAL.
 STOP WORK ORDER ISSUED ON 12/7/16. CODE VIOLATION #
 CE16120280 FOR INSTALLATION OF DOORS AND WINDOWS
 WITHOUT PERMIT.
  
 2. PLAN PAGES DATED 1/9/17 AND 3/9/17 (WINDOW SCHEDULE)
 HAVE RESTROOMS 1 & 2 REVERSED. PLEASE CLARIFY.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-30 Cont ID  
Sent By cthroop Date 2017-01-30 Time 11:45 Rev Time 0.00
Received By cthroop Date 2017-01-30 Time 11:08 Sent To  
Notes
2017-01-30 11:57:42BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ORIGINAL PRIVATE PROVIDER SCOPE OF WORK LIMITED TO
 STRUCTURAL ELEMENTS ONLY PER ROBERT BROWN, CBO. PRIVATE
 PROVIDER TO RE-SUBMIT CREDITIALS FOR INCREASED SCOPE OF
 WORK, (PLUMBING)
 2. PROVIDE PRODUCT APPROVALS FOR WINDOW MULLIONS.
 3. PROVIDE VALUE FOR NEW SCOPE OF WORK.
 4. 4 X FEE WILL BE IMPOSED ON NEW VALUE.
 5. REVISION IS FOR INCREASED SCOPE OF WORK (WINDOWS AND
 DOORS). REMOVE STATEMENT FROM PLAN "EXTERIOR DOORS AND
 WINDOWS ON EXISTING. INTERIOR DOORS NOT INSTALLED".
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW
 MULLION SUBMITTALS.
  
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 PLEASE INCREASE THE VALUATION ACCORDINGLY.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-10 Cont ID  
Sent By jleahy Date 2017-05-10 Time 07:20 Rev Time 0.00
Received By jleahy Date   Time   Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-03-17 Cont ID  
Sent By jleahy Date 2017-03-17 Time 15:21 Rev Time 0.00
Received By jleahy Date 2017-03-17 Time 15:21 Sent To  
Notes
2017-03-17 15:26:05PLAN REVIEW FAILED
  
 1) NEED FAULT CURRENT CALCULATION FOR THE SERVICE PER
 110.24 (A,B)
 2) MAIN CIRCUIT BREAKER IS RATED AT 130 AMPERES? NOT A
 STANDARD SIZE 240.6
 3) CIRCUIT 11,15,17,19, AS SHOWN SHALL BE GFCI
 PROTECTED 210.8
 4) CIRCUIT #18 SHOWS 3 - 3WAY SWITCHES, NEEDS TO BE 2 -
 3WAYS AND A 4 WAY
 5) PANEL IN STORAGE ROOM NEEDS AT LEAST 36" OF FRONTAL
 CLEARANCE 110.26
 6) NO EXIT OR EMERGENCY LIGHTS SHOWN ON DRAWINGS
  
 JAKE LEAHY 561-805-6713

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-05-12 Cont ID  
Sent By cthroop Date 2017-05-12 Time 10:31 Rev Time 0.00
Received By cthroop Date 2017-05-08 Time 10:48 Sent To  
Notes
2017-05-09 10:48:33RESUB OF REVISION ROUTED TO JLEAHY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-09 Cont ID  
Sent By lmarchan Date 2017-05-09 Time 10:43 Rev Time 0.00
Received By lmarchan Date 2017-03-15 Time 10:11 Sent To  
Notes
2017-03-16 10:11:16RESUB OF REVISION ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-30 Cont ID  
Sent By cthroop Date 2017-01-30 Time 11:08 Rev Time 0.00
Received By cthroop Date 2017-01-26 Time 17:37 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-05-12 Cont ID  
Sent By tklarge Date 2017-05-12 Time 10:29 Rev Time 0.00
Received By gjohnson Date 2017-05-11 Time 15:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-03-17 Cont ID  
Sent By tklarge Date 2017-03-17 Time 06:51 Rev Time 0.00
Received By tklarge Date 2017-03-17 Time 06:10 Sent To  
Notes
2017-03-17 06:16:421) THE SCOPE OF WORK LISTED IN THE DOCUMENT FROM ALL
 FLORIDA STRUCTURES DATED 1/19/2017 INDICATES THAT BOTH
 OF THESE TOILET ROOMS ARE EXISTING HANDICAPPED (ADA)
 TOILET ROOMS BUT THE REVISED PLANS FROM GENTRY
 ENGINEERING NOTES THAT ONLY ONE TOILET ROOM IS
 HANDICAPPED ACCESSIBLE. AT THIS POINT I HAVE NO IDEA
 WHICH IS WHICH DUE TO THE CONFLICTING INFORMATION THAT
 HAS BEEN SUBMITTED AND VAGUE INFORMATION ON THE PLANS..
 SUBMIT A REVISED SCOPE OF WORK DOCUMENT FROM FLORIDA
 STRUCTURES THAT CLEARLY REFLECTS THE EXISTING
 CONDITIONS AND THE ENTIRE SCOPE OF WORK TO BE DONE TO
 THE TOILET ROOMS. WPB AMEND. TO FBC SEC. 107.2.1. 2ND
 REQUEST.
 2) THE SCOPE OF WORK FROM ALL FLORIDA STRUCTURES DATED
 1/19/17 NOTES THAT ALL PLUMBING IS EXISTING AND ONLY
 REPLACING SUPPLY LINES & STOPS YET YOU HAVE LISTED
 REPLACEMENT OF KITCHEN SINK, VANITIES, WATER HEATER,
 TOILETS, ETC.CLARIFY.AGAIN, SHOW THE SCOPE OF THE
 PLUMBING WORK ON THE PLANS. WPB AMEND. TO FBC 107.2.1.
 3) ARE THESE TOILET ROOMS EXISTING HANDICAPPED
 ACCESSIBLE TOILET ROOMS OR ARE THEY BEING MADE INTO
 HANDICAPPED ACCESSIBLE TOILET ROOMS. INDICATE THIS ON
 THE PLANS.WPB AMEND. TO FBC SEC.107.2.1.
 4) THE SCOPE OF WORK DATED 1/19/17 REFERS TO REPLACING
 SHOWER TRIM AND NEW GLASS DOOR YET THERE IS NO SHOWER
 SHOWN ON THE PLANS. THE PLANS ARE VAGUE AND DO NOT
 REFLECT THE SCOPE OF WORK OR EXISTING
 CONDITIONS.CLARIFY.
 5) IF THESE ARE CURRENTLY BOTH HANDICAPPED ACCESSIBLE
 TOILET ROOMS THEY HAVE TO REMAIN HANDICAPPED ACCESSIBLE
 TOILET ROOMS. YOU CANNOT REDUCE THE LEVEL OF
 ACCESSIBILITY BY ONLY HAVING ONE ACCESSIBLE TOILET
 ROOM. CLARIFY.
 6) GRAB BARS SHALL COMPLY WITH FBC ACCESSIBILITY
 SEC.604.5,609. 2ND REQUEST.
 7) ACCESSIBLE LAVATORIES IN HANDICAPPED ACCESSIBLE
 TOILET ROOMS SHALL COMPLY WITH FBC-ACCESS. SEC.606,
 606.2, 606.3, 606.4,606.5..SHOW COMPLIANCE ON THE
 PLANS.
 8) SHOW THE REQUIRED CLEAR FLOOR SPACES REQUIRED FOR
 THE HANDICAPPED ACCESSIBLE FIXTURES PER
 FBC-ACCESSIBILITY SECS. 604.3,606.
 9) VOID ALL OLD DOCUMENTS IN THE SUBMITTAL PACKAGE.WPB
 AMEND. TO FBC SEC. 107.2.1.
 10) IS THE WASHER ATTACHING TO EXISTING LINES/OUTLETS
 OR TO NEW SANITARY/ WATER LINES? IF NEW, SUBMIT A
 SANITARY AND WATER RISER FOR REVIEW. IF CONNECTING TO
 EXISTING, NOTE SUCH ON THE PLANS.
 11) THE HEIGHT OF THE KITCHEN COUNTER SHALL COMPLY WITH
 THE FBC-ACCESS. SECS.606.2,606.3, 606.4,606.5.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-27 Cont ID  
Sent By cthroop Date 2017-01-30 Time 11:08 Rev Time 0.00
Received By tklarge Date 2017-01-27 Time 08:59 Sent To  
Notes
2017-01-27 09:11:141)THE WORK DESCRIPTION DOCUMENT INDICATES THAT THESE
 ARE ADA TOILET ROOMS.THE REVISED PLANS DO NOT CLEARLY
 REFLECT THE SCOPE OF WORK AS OUTLINED IN THE WORK
 DESCRIPTION DOCUMENT. SHOW THE LOCATION OF THE EXISTING
 PLUMBING FIXTURES IN RESTROOMS #1 & #2 AND THE FIXTURE
 CLEARANCES FOR THE FIXTURES TO ENSURE CONTINUED
 COMPLIANCE WITH THE FL. ACCESSIBILITY CODE.
 2) SHOW THE LOCATION OF THE GRAB BARS ON THE PLAN.
 INSTALLATION OF GRAB BARS SHALL COMPLY WITH THE
 FBC-ACCESSIBILITY SECS. 604.5, 609.
 3) LAVATORIES SHALL COMPLY WITH FBC-ACCESSIBILITY
 SEC.606.
 4) INDICATE THE CAPACITY (GALS.) OF THE WATER HEATER ON
 THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop REV REVISIONS
Rev No 2 Status P Date 2017-05-26 Cont ID  
Sent By cthroop Date 2017-05-26 Time 12:51 Rev Time 0.00
Received By cthroop Date 2017-05-26 Time 12:51 Sent To  
Notes
2017-05-26 12:51:414X FEE PAID

Review Stop REV REVISIONS
Rev No 1 Status F Date 2017-03-29 Cont ID  
Sent By rbrown Date 2017-03-29 Time 20:36 Rev Time 0.00
Received By rbrown Date 2017-03-29 Time 20:35 Sent To  
Notes
2017-03-29 20:41:07DO NOT PASS THIS REVIEW STOP OR ISSUE STAMPED REVISED
 PLANS UNTIL THE OUTSTANDING $750 IS PAID UNDER THIS
 REVISION TRACKING # TO COVER THE FACT THAT THIS WORK
 SCOPE WAS DONE WITHOUT PERMIT. THE CONTRACTOR ONLY
 SUBMITTED THIS REVISION, TO ADD THIS ADDITIONAL WORK
 SCOPE TO MASTER PERMIT # 16040624, AS A RESULT OF THE
 STOP WORK ORDER ISSUED ON 12/7/16.