Plan Review Details - Permit 17010975
Plan Review Stops For Permit 17010975
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-02-06 Cont ID  
Sent By tklarge Date 2017-02-06 Time 13:23 Rev Time 0.00
Received By tklarge Date 2017-02-06 Time 12:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-01-27 Cont ID  
Sent By tklarge Date 2017-01-27 Time 05:41 Rev Time 0.00
Received By tklarge Date 2017-01-27 Time 05:32 Sent To  
Notes
2017-01-27 05:41:111) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER TO THE MOST REMOTE OUTLET IN THE BUILDING AND /
 OR SYSTEM PER THE 2014 FBC-FUEL GAS SEC.402.4.1. I
 CANNOT REVIEW FOR COMPLIANCE WITHOUT THIS DISTANCE.
 2) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) HAVE
 BEEN USED IN THE DESIGN OF THE GAS SYSTEM. REFER TO THE
 2014 FBC-FUEL GAS SECS.401.8 THRU 402.6.1 AND TABLES
 402.4 (1) THRU 402.4 (37) .
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-06 Cont ID  
Sent By tklarge Date 2017-02-06 Time 13:23 Rev Time 0.00
Received By tklarge Date 2017-02-03 Time 16:12 Sent To  
Notes
2017-02-03 16:12:54TLARGE'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-27 Cont ID  
Sent By tklarge Date 2017-01-27 Time 05:41 Rev Time 0.00
Received By tklarge Date 2017-01-25 Time 11:20 Sent To  
Notes
2017-01-26 11:20:50PLUMB <5K