Plan Review Details - Permit 17010898
Plan Review Stops For Permit 17010898
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-01-23 Cont ID  
Sent By cthroop Date 2018-01-23 Time 16:38 Rev Time 0.00
Received By cthroop Date 2018-01-23 Time 16:38 Sent To M
Notes
2018-01-23 16:39:02ROOFING PERMIT 17100750

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-12-22 Cont ID  
Sent By cthroop Date 2017-12-22 Time 14:58 Rev Time 0.00
Received By cthroop Date 2017-12-22 Time 13:34 Sent To  
Notes
2017-12-22 14:59:34BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE PRODUCT APPROVALS FOR PROPOSED ROOF MSYSTEM.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING SUBMITTALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-08-21 Cont ID  
Sent By cthroop Date 2017-08-21 Time 16:30 Rev Time 0.00
Received By cthroop Date 2017-08-21 Time 16:12 Sent To P
Notes
2017-08-21 16:33:14BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 2ND REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. MECHANICAL PLAN REQUIRED. PROVIDE ENERGY SUBMITTAL.
 2. ROOFING PERMIT REQUIRED. PROVIDE PRODUCT APPROVALS
 FOR NEW ROOFING SYSTEM.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW, AND DOOR
 SUBMITTALS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By cthroop Date 2017-02-23 Time 14:38 Rev Time 0.00
Received By cthroop Date 2017-02-23 Time 14:37 Sent To  
Notes
2017-02-23 14:43:21BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. SELECT WHICH PRODUCT WILL BE INSTALLED FROM PRODUCT
 APPROVALS SUBMITTED. IF NON-IMPACT DEVICES ARE
 SELECTED, PROVIDE SHUTTER SCHEDULE WITH PRODUCT
 APPROVALS.
 2. PRODUCT APPROVALS TO BE REVIEWED AND APPROVED BY
 DESIGNER.
 3. YOU MAY PROVIDE A DOOR AND WINDOW SCHEDULE WITH
 LOCATIONS ON PLANS FOR EACH DEVICE, ROUGH OPENINGS,
 DESIGN WIND LOADS AND PRODUCT APPROVAL NUMBER.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
 SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY
 FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW, AND
 DOOR SUBMITTALS.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-12-07 Cont ID  
Sent By jpearson Date 2017-12-07 Time 07:58 Rev Time 0.00
Received By jpearson Date 2017-12-07 Time 07:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-08-14 Cont ID  
Sent By jleahy Date 2017-08-14 Time 17:23 Rev Time 0.00
Received By jleahy Date 2017-08-14 Time 17:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By mvaldes Date 2017-02-02 Time 14:33 Rev Time 0.00
Received By mvaldes Date 2017-02-02 Time 10:56 Sent To  
Notes
2017-02-02 14:41:471ST REVIEW
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] CORRECT ELECTRICAL NOTE TO THE CURRENT APPPLICABLE
 CODE NEC 2011 ( FBC-R 2014 )
  
 2] AFCI PROTECTION ISN'T LIMITED TO THE BEDROOMS BUT IN
 ACCORDANCE NEC 210.12(B) ( FBC-R E3902.13 ) SEE
 PROVISIONS.
  
 3] PROVIDE A GFCI SERVICE RECEPTACLE OUTLET WITHIN 25'
 OF THE C/U. NEC 210.63 ( FBC-R E3901.11 )
  
 4] ADD A NOTE THAT 75% OF LUMINAIRES SHALL BE HIGH
 EFFICIENT PER FBC-E R404.1.
  
 5] THE MAIN DISCONNECT SHALL BE FUSIBLE FOR
 OVER-CURRENT PROTECTION PER NEC 230.90 ( FBC-R E3606.3
 ).
  
 6] WASHER ( LAUNDRY) CIRCUIT SHALL BE INCLUDED IN LOAD
 CALCS IN ACCORDANCE WITH NEC 220.52(B) ( FBC-R E3704.2
 ).
  
 7] SHOW DRYER BREAKER & WIRE SIZE ON PANEL SCHEDULE.
 FBC 107
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-12-22 Cont ID  
Sent By cthroop Date 2017-12-22 Time 14:59 Rev Time 0.00
Received By cthroop Date 2017-12-01 Time 12:42 Sent To I
Notes
2017-12-04 12:43:05R01

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-08-22 Cont ID  
Sent By gjohnson Date 2017-08-22 Time 09:41 Rev Time 0.00
Received By gjohnson Date 2017-08-08 Time 11:13 Sent To  
Notes
2017-08-09 11:13:44R19

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-23 Cont ID  
Sent By cthroop Date 2017-02-23 Time 14:37 Rev Time 0.00
Received By cthroop Date 2017-01-25 Time 10:35 Sent To  
Notes
2017-01-27 10:36:03R08

Review Stop M MECHANICAL (A/C)
Rev No 4 Status N Date 2018-01-24 Cont ID  
Sent By ccole Date 2018-01-24 Time 08:17 Rev Time 0.00
Received By ccole Date 2018-01-24 Time 08:17 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-12-22 Cont ID  
Sent By ccole Date 2017-12-22 Time 12:31 Rev Time 0.00
Received By ccole Date 2017-12-22 Time 12:28 Sent To  
Notes
2017-12-22 12:33:043RD REVIEW FBC-2014 RESIDENTIAL.
 PERMIT #17010898
 8/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 SOME OF THE 1ST REVIEW COMMENTS STILL EXIST. I HAVE
 REPRINTED THEM BELOW WITH ADDITIONAL COMMENTS AND
 CLARIFICATIONS.
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 WITH CORRESPONDING DRAWINGS AND DETAILS ON THE PLAN.
  
 NEW COMMENT: THE REVISED PLAN IS INDICATING A REPLACED
 AIR HANDLER. PLEASE PROVIDE ON THE PLAN AN AC EQUIPMENT
 SCHEDULE THAT INCLUDES THE AIR HANDLER AND THE
 CONDENSER, AND SUBMIT AN AHRI CERTIFICATE FOR THE
 SYSTEM- SECTION R101.4.7 FBC-14 ENERGY CONSERVATION.
  
 NEW COMMENT: THE LOCATION OF THE AIR HANDLER APPEARS TO
 HAVE CHANGED. PLEASE SHOW ALL ALTERATIONS TO THE
 EXISTING SUPPLY AND RETURN SYSTEM, AND INDICATE THE
 REQUIRED CLEARANCES FOR THE AIR HANDLER IN THE CLOSET
 AS REQUIRED BY SECTION M1305.1.1.
  
 NEW COMMENT: THE LOCATION OF THE CONDENSER APPEARS TO
 HAVE CHANGED. PLEASE PROVIDE STRUCTURAL DETAILS FOR
 INSTALLATION OF THE PAD AND MOUNTING OF THE CONDENSER
 TO THE PAD- SECTION M1305.1.4.1 & M1307.2 FBC-14
 RESIDENTIAL.
  
 2) SUBMIT DOCUMENTATION OF ENERGY CONSERVATION
 COMPLIANCE AS REQUIRED BY SECTIONS R101.4.3, R101.5.1
 FBC-14 ENERGY CONSERVATION CODE.
  
 3) SUBMIT TWO COPIES OF WPB BUILDING DEPARTMENT AC
 CHANGE OUT FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2017-08-17 Cont ID  
Sent By ccole Date 2017-08-17 Time 16:27 Rev Time 0.00
Received By ccole Date 2017-08-17 Time 16:27 Sent To  
Notes
2017-08-17 16:51:342ND REVIEW FBC-2014 RESIDENTIAL.
 PERMIT #17010898
 8/17/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 SOME OF THE 1ST REVIEW COMMENTS STILL EXIST. I HAVE
 REPRINTED THEM BELOW WITH ADDITIONAL COMMENTS AND
 CLARIFICATIONS.
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 WITH CORRESPONDING DRAWINGS AND DETAILS ON THE PLAN.
  
 NEW COMMENT: THE REVISED PLAN IS INDICATING A REPLACED
 AIR HANDLER. PLEASE PROVIDE ON THE PLAN AN AC EQUIPMENT
 SCHEDULE THAT INCLUDES THE AIR HANDLER AND THE
 CONDENSER, AND SUBMIT AN AHRI CERTIFICATE FOR THE
 SYSTEM- SECTION R101.4.7 FBC-14 ENERGY CONSERVATION.
  
 NEW COMMENT: THE LOCATION OF THE AIR HANDLER APPEARS TO
 HAVE CHANGED. PLEASE SHOW ALL ALTERATIONS TO THE
 EXISTING SUPPLY AND RETURN SYSTEM, AND INDICATE THE
 REQUIRED CLEARANCES FOR THE AIR HANDLER IN THE CLOSET
 AS REQUIRED BY SECTION M1305.1.1.
  
 NEW COMMENT: THE LOCATION OF THE CONDENSER APPEARS TO
 HAVE CHANGED. PLEASE PROVIDE STRUCTURAL DETAILS FOR
 INSTALLATION OF THE PAD AND MOUNTING OF THE CONDENSER
 TO THE PAD- SECTION M1305.1.4.1 & M1307.2 FBC-14
 RESIDENTIAL.
  
 2) SUBMIT DOCUMENTATION OF ENERGY CONSERVATION
 COMPLIANCE AS REQUIRED BY SECTIONS R101.4.3, R101.5.1
 FBC-14 ENERGY CONSERVATION CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-09 Cont ID  
Sent By ccole Date 2017-02-09 Time 07:27 Rev Time 0.00
Received By ccole Date 2017-02-09 Time 07:24 Sent To B
Notes
2017-02-09 07:43:441ST REVIEW FBC-2014 RESIDENTIAL.
 PERMIT #17010898
 2/9/17
  
 1) PROVIDE A SCOPE OF WORK FOR MECHANICAL ALTERATIONS
 WITH CORRESPONDING DRAWINGS AND DETAILS ON THE PLAN.
 CLARIFY IF THE EXISTING AC SYSTEM WILL BE REPLACED OR
 ALTERED AS PART OF THE RENOVATION.
  
 2) INDICATE HOW THE BATHROOMS WILL BE VENTILATED USING
 EITHER OPERABLE OPENINGS TO THE OUTDOORS PER SECTION
 R303.3, OR MECHANICALLY PER M1507.4.
  
 3) PROVIDE EXHAUST VENTILATION FOR THE KITCHEN- SEE
 SECTIONS M1503- M1507 FOR COMPLIANCE METHODS.
  
 4) THE PLAN INDICATES A FIREPLACE THAT APPEARS TO BE A
 NEW INSTALLATION. PLEASE PROVIDE AN EQUIPMENT SCHEDULE
 ON THE PLAN THAT LISTS THE MAKE AND MODEL OF THE UNIT,
 AND TYPE- GAS-FIRED, WOOD BURNING, ELECTRIC ETC. A)
 SUBMIT MANUIFACTURER'S SPECIFICATIONS FOR THE UNIT AND
 THE VENT SYSTEM. B) PROVIDE A VENTING DIAGRAM THAT
 INDICATES THE TYPE AND SIZE OF VENT MATERIAL, LENGTH OF
 VENT
  
 RUN AND LOCATION OF VENT TERMIANTION CAP.
  
 5) SUBMIT DOCUMENTATION OF ENERGY CONSERVATION
 COMPLIANCE AS REQUIRED BY SECTIONS R101.4.3, R101.5.1
 FBC-14 ENERGY CONSERVATION CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-12-19 Cont ID  
Sent By gjohnson Date 2017-12-19 Time 19:00 Rev Time 0.00
Received By gjohnson Date 2017-12-19 Time 14:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-08-22 Cont ID  
Sent By gjohnson Date 2017-08-22 Time 09:37 Rev Time 0.00
Received By gjohnson Date 2017-08-22 Time 08:09 Sent To  
Notes
2017-08-22 09:40:18 
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By gjohnson Date 2017-02-02 Time 16:56 Rev Time 0.00
Received By gjohnson Date 2017-02-02 Time 15:27 Sent To  
Notes
2017-02-02 17:02:081ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. IT IS UNCLEAR WHICH BATHROOM IS BEING REPLACED THE
 BATH ON THE RISER NEXT TO THE WASHER SHOWS A TUB BUT
 THE FLOW PLAN SHOWS A TUB NEXT TO WASHER PLEASE CLARIFY
 WHAT WORK IS BEING DONE IN EACH BATHROOM. PER WPB AMEND
 TO FBC 107.2.1
  
 2. IS THE WATER HEATER EXISTING TO REMAIN OR WILL IT BE
 REPLACED. PER WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  