Plan Review Details - Permit 17010879
Plan Review Stops For Permit 17010879
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-28 Cont ID  
Sent By jwitmer Date 2017-01-28 Time 08:12 Rev Time 0.00
Received By jwitmer Date 2017-01-28 Time 07:45 Sent To  
Notes
2017-01-28 08:35:16BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010879
 ADD: 4047 OKEECHOBEE BLVD. SUITE # 110
 CONT: MOSS DEVCO INC.
 TEL:561-876-4570
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JAN. 28/2017
 ACTION: DENIED
  
 1) SHEET S-1 DISCREPANCY IN PLANS. 107.2.1.3 ADDIONAL
 INFORMATION REQUIRED. 2014 FBC-B TABLE 603 RATINGS ON
 THE ROOF FRAMING MEMBERS. THE SHEET S-1 INDICATES THE
 TYPE OF CONSTRUCTION AS A BUILDING TYPE I-A REQUIRING 1
 1/2 HOUR FIRE RATING. UNDER THE HEADING OF CONSTRUCTION
 LISTED: 1 STORY CBS WITH METAL JOIST TYPE IIB NOT
 REQUIRING ANY FIRE PROTECTION ON THE ROOF FRAMING
 MEMBERS OR SECONDARY MEMBERS. PLEASE IDENTIFY THE TYPE
 OF CONSTRUCTION AND CORRECT THE PLANS ACCORDINGLY.
  
 2)
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2017-02-06 Cont ID  
Sent By albarran Date 2017-02-06 Time 15:55 Rev Time 0.00
Received By albarran Date 2017-02-06 Time 15:45 Sent To I
Notes
2017-02-06 15:55:10ACCORDING TO THE NOTES ON THE PLANS, THERE WILL BE NO
 ELECTRIC AS PART OF THIS PERMIT. A NOTE TO SAME WAS
 PLACED ON THE PLANS FOR THE INSPECTOR'S REVIEW.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-02-01 Cont ID  
Sent By scaldero Date 2017-02-01 Time 09:43 Rev Time 0.00
Received By scaldero Date 2017-02-01 Time 09:43 Sent To  
Notes
2017-02-01 09:43:33PERMIT # 17010879
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAIL COMMENTS:
  
 1) SEE COMMENTS LISTED UNDER BUILDING REVIEW.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-06 Cont ID  
Sent By albarran Date 2017-02-06 Time 15:58 Rev Time 0.00
Received By albarran Date 2017-01-24 Time 11:03 Sent To  
Notes
2017-02-06 15:58:51IN LIEU OF A MISSING EMAIL ADDRESS I CALLED AND SPOKE
 W/JOE OF MOSS DEVCO TO INFORM HIM THAT THE FILE REVIEWS
 HAD BEEN COMPLETED AND WAS READY FOR CORRECTIONS. SENT
 FILE TO SMALL DENIED DRAWER "NM". MA
2017-01-26 11:03:16B06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-01-28 Cont ID  
Sent By jwitmer Date 2017-01-28 Time   Rev Time  
Received By jwitmer Date 2017-01-28 Time 07:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By ccole Date 2017-02-02 Time 10:20 Rev Time 0.00
Received By ccole Date 2017-02-02 Time 10:20 Sent To  
Notes
2017-02-02 10:22:031ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010879
 2/217
  
 1) THE PROPOSED PROJECT HAS BEEN CLASSIFIED AS A LEVEL
 2 ALTERATION ON SHEET S-1. REFER TO SECTION 809.1
 FBC-14 EXISTING BUILDING CODE AND PROVIDE MINIMUM
 VENTILATION CALCULATIONS FOR ALL ROOMS AND SPACES PER
 TABLE 403.3 FBC-14 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2017-02-02 Cont ID  
Sent By gjohnson Date 2017-02-02 Time 09:00 Rev Time 0.00
Received By gjohnson Date 2017-02-01 Time 16:46 Sent To  
Notes
***NONE***