Plan Review Stops For Permit 17010817 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2017-01-27 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2017-01-27 |
Time |
17:52 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2017-01-27 |
Time |
17:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-01-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2017-01-24 |
Time |
18:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2017-01-24 |
Time |
18:05 |
Sent To |
|
|
Notes |
2017-01-24 18:04:53 | REVISION DENIED | | | | 1) THE SERVICE LAYOUT DOES NOT SHOW THE LOCATIONS OF | | THE ATS EQUIPMENT. SPECIFY THEIR LOCATIONS ON THE FLOOR | | PLANS. FBC 107.2.1 | | | | 2) THE TRANSFER SWITCHES ARE REQUIRED TO BE SERVICE | | ENTRANCE RATED. SUBMIT TWO SETS OF SPECIFICATIONS FOR | | THE ATS EQUIPMENT. FBCR-E3404.3 | | | | 3) A SEPARATE PERMIT, APPLICATION AND REVIEW WILL BE | | REQUIRED FOR THE GENERATOR. FBC 105.1 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-01-27 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2017-01-27 |
Time |
17:52 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2017-01-26 |
Time |
11:11 |
Sent To |
|
|
Notes |
2017-01-27 11:11:52 | RESUB OF REVISION ROUTED TO RMCDOUGAL |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-01-24 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2017-01-24 |
Time |
18:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2017-01-23 |
Time |
11:49 |
Sent To |
|
|
Notes |
2017-01-24 11:50:26 | RMCDOUGAL'S DESK |
|
|
|