Plan Review Details - Permit 17010817
Plan Review Stops For Permit 17010817
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-01-27 Cont ID  
Sent By rmcdouga Date 2017-01-27 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2017-01-27 Time 17:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-24 Cont ID  
Sent By rmcdouga Date 2017-01-24 Time 18:05 Rev Time 0.00
Received By rmcdouga Date 2017-01-24 Time 18:05 Sent To  
Notes
2017-01-24 18:04:53REVISION DENIED
  
 1) THE SERVICE LAYOUT DOES NOT SHOW THE LOCATIONS OF
 THE ATS EQUIPMENT. SPECIFY THEIR LOCATIONS ON THE FLOOR
 PLANS. FBC 107.2.1
  
 2) THE TRANSFER SWITCHES ARE REQUIRED TO BE SERVICE
 ENTRANCE RATED. SUBMIT TWO SETS OF SPECIFICATIONS FOR
 THE ATS EQUIPMENT. FBCR-E3404.3
  
 3) A SEPARATE PERMIT, APPLICATION AND REVIEW WILL BE
 REQUIRED FOR THE GENERATOR. FBC 105.1

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-27 Cont ID  
Sent By rmcdouga Date 2017-01-27 Time 17:52 Rev Time 0.00
Received By rmcdouga Date 2017-01-26 Time 11:11 Sent To  
Notes
2017-01-27 11:11:52RESUB OF REVISION ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-24 Cont ID  
Sent By rmcdouga Date 2017-01-24 Time 18:05 Rev Time 0.00
Received By rmcdouga Date 2017-01-23 Time 11:49 Sent To  
Notes
2017-01-24 11:50:26RMCDOUGAL'S DESK