Plan Review Details - Permit 17010802
Plan Review Stops For Permit 17010802
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-24 Cont ID  
Sent By jwitmer Date 2017-02-24 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2017-02-24 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-30 Cont ID  
Sent By jwitmer Date 2017-01-30 Time 15:47 Rev Time 0.00
Received By jwitmer Date 2017-01-30 Time 14:41 Sent To  
Notes
2017-01-30 15:47:30BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010802
 ADD: 2 HARVARD CIR. SUITE # 500
 CONT: FISHER CONTRACTING
 TEL: 561-691-4716
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JAN. 30/ 2014
 ACTION: DENIED
  
 1) SHEET 3.1 SHOWS A NEW DOOR WAY BETWEEN SUITE 500 AND
 SUITE 450. THE WALL BETWEEN THE (2) UNITS IS DRAWN
 THICKER THAN THE OTHER WALLS. THE WALL IS DRAWN IN
 WIDTH JUST AS AN 8 INCH CBS BLOCK WALL, IS THIS A 8
 INCH BLOCK WALL REQUIRING A LINTEL AND COLUMNS?
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 2) SHEET 3.1 INDICATES THE NEW OFFICE SPACE TO HAVE AN
 OPEN OFFICE CONCEPT. PLEASE PROVIDE A LIFE SAFETY PLAN
 THAT SHOWS THE FURNATURE/ CUBICAL LAYOUT AND EXIT
 ACCESS FOR COMPLIANCE WITH:
 2014 FBC-B TABLE 1014.3.
  
 3) SHEET 3.1 WAITING ROOM # 100 FOR SUITE 450 SHOWS A
 PASS THROUGH WINDOW, IT APPEARS THERE IS A COUNTER, THE
 PLANS DO NOT PROVIDE IF THIS AREA IS FOR A SECOND
 RECEPTIONIST, IF THE COUNTER IS FOR CHECK WRITING, MAY
 NEED TO COMPLY WITH SECTION 904.3.3 CHECK WRITING
 SURFACES OF THE 2014 ACCESSIBILITY CODE. WHERE
 PROVIDED, CHECK WRITING SURFACES SHALL COMPLY WITH
 902.3.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-27 Cont ID  
Sent By vperez Date 2017-02-27 Time 14:52 Rev Time 0.00
Received By vperez Date 2017-02-27 Time 14:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-01 Cont ID  
Sent By vperez Date 2017-02-01 Time 10:53 Rev Time 0.00
Received By vperez Date 2017-02-01 Time 10:53 Sent To  
Notes
2017-02-01 10:54:24INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS CARD READERS, PHONE AND DATA,
 WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 AND COMPLETIONS DOCUMENTS.
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS FOR
 MODIFICATIONS; SEE VERBIAGE IN CODE.
 4. FUTURE GENERATOR NOT PART OF SCOPE. CLARIFICATION
 REQUIRED
 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-27 Cont ID  
Sent By pleduc Date 2017-01-27 Time   Rev Time 0.00
Received By pleduc Date 2017-01-27 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-27 Cont ID  
Sent By vperez Date 2017-02-27 Time 14:53 Rev Time 0.00
Received By vperez Date 2017-02-27 Time 14:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-21 Cont ID  
Sent By lmarchan Date 2017-02-21 Time 13:20 Rev Time 0.00
Received By lmarchan Date 2017-01-23 Time 14:28 Sent To  
Notes
2017-01-24 14:28:16B19

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-02-24 Cont ID  
Sent By jwitmer Date 2017-02-24 Time 07:13 Rev Time 0.00
Received By jwitmer Date 2017-01-30 Time 14:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-02-22 Cont ID  
Sent By ccole Date 2017-02-22 Time 16:39 Rev Time 0.00
Received By ccole Date 2017-02-22 Time 16:02 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-31 Cont ID  
Sent By ccole Date 2017-01-31 Time 08:11 Rev Time 0.00
Received By ccole Date 2017-01-31 Time 07:11 Sent To  
Notes
2017-01-31 08:21:101ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010802
 1/31/17
  
 1) PROVIDE O/A CALCULATIONS FOR THE STORAGE ROOM.
  
 2) CLARIFY THE PURPOSE OF EF-2 IN THE STORAGE ROOM AND
 PROVIDE AN EXHAUST VENTILATION CALCULATION. PLEASE NOTE
 AN INDEPENDENT EXHAUST SYSTEM MAY BE REQUIRED PER
 COMMENT #3 BELOW.
  
 3) CLARIFY WHAT MATERIALS OR CHEMICALS WILL BE STORED
 IN THE STORAGE ROOM. REFER TO SECTION 414.1.3 FBC-14
 BUILDING AND, IF APPLICABLE, PROVIDE A REPORT
 IDENTIFYING THE MAXIMUM EXPECTED QUANTITIES OF
 HAZARDOUS MATERIALS TO BE STORED, USED IN A CLOSED
 AND/OR OPEN SYSTEM AND SUBDIVIED TO SEAPARATELY ADDRESS
 HAZARDOUS MATERIALS CLASSIFICATION CATEGORIES BASED ON
 TABLE 307.1(1) AND 307.1(2).
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-02-16 Cont ID  
Sent By gjohnson Date 2017-02-16 Time 12:21 Rev Time 0.00
Received By gjohnson Date 2017-02-16 Time 12:21 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved