Plan Review Details - Permit 17010775
Plan Review Stops For Permit 17010775
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-04-04 Cont ID  
Sent By jwitmer Date 2017-04-04 Time 07:14 Rev Time 0.00
Received By jwitmer Date 2017-04-04 Time 06:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-01 Cont ID  
Sent By jwitmer Date 2017-02-01 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2017-02-01 Time 05:57 Sent To  
Notes
2017-02-01 06:58:39BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010775
 ADD: 224 DATURA ST. SUITE NUMBER???????
 CONT: GERARD CONTRACTING
 TEL: 561-832-9785
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB.01/2017
 ACTION: DENIED
  
 1) PLEASE PROVIDE THE CORRECT SITE ADDRESS AND TENANT
 SUITE NUMBER ON THE PERMIT APPLICATION. THE SITE
 ADDRESS ASSIGNED TO THE PCN NUMBER
 74-43-43-21-01-006-0061 IS 224 DATURA ST. PLEASE
 CORRECT AND PROVIDE THE TENANT SUITE NUMBER AS WELL.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE
 PROPOSED WORK TO BE ACCOMPLISHED UNDER THIS PERMIT.
  
 2) SHEET D1.0 UNDER THE HEADING PROJECT DATA THE TYPE
 OF CONSTRUCTION IS LISTED AS IB. PLEASE NOTE THE
 COUNTYWIDE GIS SHOWS THIS BUILDING TO BE 14 STORIES
 TALL. A IB TYPE OF CONSTRUCTION WILL ONLY ALLOW A 11
 STORY BUILDING FOR BUSINESS OCCUPANCY AND ONLY (1)
 STORY INCREASE FOR AN NFPA 13 FIRE SPRINKLER SYSTEM,
 SEE 2014 FBC-B TABLE 503. THIS BUILDING TYPE OF
 CONSTRUCTION HAS TO BE LISTED AS AN IA TYPE OF
 CONSTRUCTION, TABLE 503, PLEASE CORRECT.
  
 3) SHEET D1.0 UNDER THE HEADING PROJECT DATA THE TYPE
 OF CONSTRUCTION IB- UNPROTECTED.
 PLEASE REFER TO FBC-B TABLE 601FOR TYPE IA CONSTRUCTION
 ALL BUILDING ELEMENTS SHOW A FIRE RATING WITH THE
 EXCEPTION OF NON-BEARING WALLS AND PARTITIONS.
  
 4) C1 THE COVERSHEET LIST THE MEAN ROOF HEIGHT AS 15
 FEET. THIS IS A 14 STORY HIGHRISE BUILDING? PLEASE
 CORRECT. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) SHEET D10 INDICATES AN OVER OCCUPANT LOAD OF 58
 OCCUPANTS. 2014 FBC-B TABLE 1015.1 WHEN MORE THAN 49
 OCCUPANTS, (2) EXIT OR EXIT ACCESS DOORS ARE REQUIRED.
 SECTION 1015.2.1EXCEPTION # 2 ALLOWS THE EXIT DOORS TO
 BE 1/3RD THE DISTANCE APART OF THE OVERALL DIAGONAL
 DISTANCE. THE EXISTING LAYOUT DOES NOT MEET THE 1/3RD
 THE OVERALL DISTANCE OF THE TENANT SPACE. PLEASE REVIEW
 THE OCCUPANT LOADS AND WHEN NET CAN BE USED FOR
 DEDUCTING SQUARE FOOT AREA. FLOOR AREA, NET. THE AREAS
 USED FOR PERMANENT BUILDING COMPONENTS, SUCH AS SHAFTS,
 FIXED EQUIPMENT, THICKNESS OF WALLS, CORRIDORS
 STAIRWAYS, TOILET ROOMS, MECHANICAL ROOMS, AND CLOSETS
 ARE NOT INCLUDED IN
 NET FLOOR AREA.
  
 6) SHEET A1 PLEASE SHOW COMPLIANCE WITH 2014
 FBC-ACCESSIBILITY CODE SECTION 226.1 5% OF DINING
 SURFACES MET THE REQUIREMENTS OF 902.
  
 7) SHEET A1 PLEASE SHOW COMPLIANCE WITH 2014 ACCESS.
 CODE FOR DISPERSION DINING SURFACES.
  
 8) SHEET A1 SHOW COMPLIANCE WITH 2014 ACCESS. CODE
 902.3 HEIGHT OF ACCESSIBLE DINING TABLES.
  
 9) PLEASE SHOW WHERE THE POINT OF SERVICE WILL BE AND
 COMPLIANCE WITH: 2014 ACCESS. CODE 904.4.
  
 10) SHEET A1.0 RESTROOM ELEVATIONS, PLEASE SEE WHERE
 THE ELEVATION IS TAKEN ON THE ACCESSIBLE MIRROR.
 MIRRORS 603.340 INCHES TO THE EDGE OF THE REFLECTIVE
 SURFACE NOT THE BOTTOM OF THE FRAME.
  
 11) THE PERMIT APPLICATION INDICATES A VALUE OF
 $32,800.00 IN VALUE. PLEASE SHOW WHERE
 UP TO 20% OF THE ASSESSED VALUE FOR ACCESSIBILITY WILL
 BE SPENT, PROVIDE AN ITEMIZED LIST ON EITHER THE
 CONTRACTORS OR THE DESIGNER OF RECORD LETTER HEAD. 2014
 ACCESS. CODE 202.4.1 DISPROPORTIONATE COST.
  
 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-05-24 Cont ID  
Sent By jleahy Date 2017-05-24 Time 19:13 Rev Time 0.00
Received By jleahy Date 2017-05-24 Time 18:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-04-04 Cont ID  
Sent By vperez Date 2017-04-04 Time 15:47 Rev Time 0.00
Received By vperez Date 2017-04-04 Time 15:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-03 Cont ID  
Sent By vperez Date 2017-02-03 Time 07:44 Rev Time 0.00
Received By vperez Date 2017-02-03 Time 07:44 Sent To  
Notes
2017-02-03 07:49:29INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO PHONE
 AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PLEASE ADDRESS MECHANICAL COMMENTS REGARDING E/FANS
 3. CLARIFY PANEL SCHEDULE PANEL2 SHOWN AS A SINGLE
 PHASE BUT RISER INDICATES A 3PHASE PANEL. FBC 107.3.5
 4. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-30 Cont ID  
Sent By pleduc Date 2017-03-30 Time   Rev Time 0.00
Received By pleduc Date 2017-03-30 Time 12:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-27 Cont ID  
Sent By pleduc Date 2017-01-27 Time   Rev Time 0.00
Received By pleduc Date 2017-01-27 Time 09:02 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-05-23 Cont ID  
Sent By gjohnson Date 2017-05-23 Time 09:20 Rev Time 0.00
Received By gjohnson Date 2017-05-23 Time 09:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-04-24 Cont ID  
Sent By gjohnson Date 2017-04-24 Time 15:37 Rev Time 0.00
Received By gjohnson Date 2017-04-24 Time 15:37 Sent To  
Notes
2017-04-24 16:27:091ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE SIZE OF EXISTING PIPING FROM METER TO NEW
 BRANCH PIPING TO WATER HEATER IN ORDER TO INSURE THAT
 THERE IS AN ADEQUATE SUPPLY OF GAS FOR THE SYSTEM. PER
 FBC FG 402.1
  
 2. THE NOTE ABOVE GAS RISER REFERENCES 2010 FBC FUEL
 GAS WE ARE UNDER 2014 5TH EDITION PLEASE CLARIFY. PER
 WPB AMEND TO FBC
  
 3. NUMBER 6 ON THE RISER IS SHOWN ON THE BRANCH FOR THE
 HEATER IF THIS IS THE EXISTING MANUAL RESET SOLENOID
 VALVE FOR INTERLOCKED WITH THE FIRE SUPPRESSION SYSTEM
 IT SHALL BE SHOWN ON THE EXISTING BRANCH TO RANGE. PER
 WPB AMEND TO FBC
  
 4. THE SEDIMENT TRAP SHALL NOT BE INSTALL ON HE
 HORIZONTAL RUN LIKE IT IS SHOWN ON THE RISER IT SHALL
 COMPLY WITH FBC FG 408.4 SEDIMENT TRAP.
 WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF
 THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED
 DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO
 THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT
 TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED
 NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE
 BOTTOMMOST OPENING OF THE TEE AS ILLUSTRATED IN FIGURE
 408.4 OR OTHER DEVICE APPROVED AS AN EFFECTIVE SEDIMENT
 TRAP. ILLUMINATING APPLIANCES, RANGES, CLOTHES DRYERS,
 DECORATIVE VENTED APPLIANCES FOR INSTALLATION IN VENTED
 FIREPLACES, GAS FIREPLACES, AND OUTDOOR GRILLS NEED NOT
 BE SO EQUIPPED.
  
 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 6. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
  
  
  
  
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status P Date 2017-05-24 Cont ID  
Sent By jleahy Date 2017-05-24 Time 19:14 Rev Time 0.00
Received By jleahy Date 2017-05-12 Time 13:25 Sent To I
Notes
2017-05-15 13:25:40B20

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-24 Cont ID  
Sent By gjohnson Date 2017-04-24 Time 15:27 Rev Time 0.00
Received By gjohnson Date 2017-03-28 Time 16:12 Sent To  
Notes
2017-03-29 16:13:00B20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-17 Cont ID  
Sent By gjohnson Date 2017-02-17 Time 11:06 Rev Time 0.00
Received By gjohnson Date 2017-01-23 Time 15:27 Sent To  
Notes
2017-01-24 15:27:21B20

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-02-01 Cont ID  
Sent By jwitmer Date 2017-02-01 Time 06:58 Rev Time 0.00
Received By jwitmer Date 2017-02-01 Time 06:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2017-05-18 Cont ID  
Sent By ccole Date 2017-05-18 Time 16:41 Rev Time 0.00
Received By ccole Date 2017-05-18 Time 16:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-31 Cont ID  
Sent By ccole Date 2017-03-31 Time 16:44 Rev Time 0.00
Received By ccole Date 2017-03-31 Time 16:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-01 Cont ID  
Sent By ccole Date 2017-02-01 Time 10:10 Rev Time 0.00
Received By ccole Date 2017-02-01 Time 10:03 Sent To  
Notes
2017-02-01 10:34:021ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010775
 2/1/17
  
 1) SHEET M-1: PROVIDE EQUIPMENT SCHEDULES FOR EF-1 & 2.
  
 2) M-1: SOME OF THE REQUIRED DATA IS MISSING FROM THE
 HEAT LOAD SUMMARY- SEE SECTION C403.2.1 EXCEPTION
 FBC-14 ENERGY CONSERVATION AND PROVIDE THE AREA IN
 SQUARE FEET, GRAINS WATER (DIFFERENCE), RELATIVE
 HUMIDITY, AND TOTAL LATENT GAIN.
  
 3) M-1: AHU-2 REQUIRES HEAT PER THE CALCULATIONS AND
 SECTION 309.1.
  
 4) M-2: THE DUCT LAYOUT FOR AHU-1 DOES NOT SHOW SUPPLY
 AND RETURN CFMS AT EACH DIFFUSER AND GRILL LOCATION.
  
 5) M-2: BASED ON THE DRAWING, IT DOES NOT APPEAR THAT
 THE REQUIRED CFMS OF O/A WILL BE PROVIDED TO THE DINING
 ROOM AREA.
  
 6) M-2: PROVIDE STRUCTURAL ENGINEERING FOR INSTALLATION
 OF THE NEW CONDENSER RACK AND MOUNTING OF THE UNIT TO
 THE RACK- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-05-23 Cont ID  
Sent By gjohnson Date 2017-05-23 Time 09:08 Rev Time 0.00
Received By gjohnson Date 2017-05-23 Time 08:57 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-04-24 Cont ID  
Sent By gjohnson Date 2017-04-24 Time 14:48 Rev Time 0.00
Received By gjohnson Date 2017-04-24 Time 14:48 Sent To  
Notes
2017-04-24 14:59:472ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. YOUR RESPONSE TO PREVIOUS COMMENT #6 STATES THERE IS
 NO GARBAGE DISPOSAL USED BUT ON P-1 ON THE PLUMBING
 FIXTURE SCHEDULE P-4 LIST A GARBAGE DISPOSAL. PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
 PREVIOUS COMMENT 6. IF YOUR USING A GARBAGE DISPOSAL ON
 P-4 IT SHALL COMPLY WITH FBC PL 1003.3.2 FOOD WASTE
 GRINDERS.
 WHERE FOOD WASTE GRINDERS CONNECT TO GREASE
 INTERCEPTORS, A SOLIDS INTERCEPTOR SHALL SEPARATE THE
 DISCHARGE BEFORE CONNECTING TO THE GREASE INTERCEPTOR.
 SOLIDS INTERCEPTORS AND GREASE INTERCEPTORS SHALL BE
 SIZED AND RATED FOR THE DISCHARGE OF THE FOOD WASTE
 GRINDER. EMULSIFIERS, CHEMICALS, ENZYMES AND BACTERIA
 SHALL NOT DISCHARGE INTO THE FOOD WASTE GRINDER.
  
 2. PROVIDE THE SIZE OF EXISTING GREASE TRAP YOU
 PROVIDED SIZING CALCULATIONS BUT I NEED TO KNOW THE
 SIZE OF THE EXTSITING TRAP TO VERIFY THAT IT IS LARGE
 ENOUGH . PER FBC PL 1003.3.4.1
  
 PREVIOUS COMMENT 10. THE EXISTING GREASE TRAP SHALL BE
 INSPECTED AND VERIFIED TO BE STRUCTURALLY SOUND AND IN
 GOOD WORKING ORDER BY A SIGNED AND SEALED LETTER FROM
 THE ENGINEER. PER WPB AMEND TO FBC 107.2.1
 I AGREE THAT THE INSPECTION AND CERTIFICATION IS NOT
 REQUIRED TO BE DONE BY AN ENGINEER, PLEASE INDICATE ON
 THE PLAN THAT AN INSPECTION SHALL BE COMPLETED AND
 CERTIFIED BY UTILITIES PRIOR TO FINAL PLUMBING
 INSPECTION, THE OWNER CAN CONNTACT JEFF ODOMS AT
 822-2172 OR [email protected] TO SCHEDULE AN INPECTION
 WITH UTILITIES.
  
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-17 Cont ID  
Sent By gjohnson Date 2017-02-17 Time 10:20 Rev Time 0.00
Received By gjohnson Date 2017-02-17 Time 10:20 Sent To  
Notes
2017-02-17 11:05:421ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.PER FBC PL 403.2 SEPARATE FACILITIES ARE REQUIRED FOR
 BOTH SEX SO BOTH BATHROOMS SHALL BE ACCESSIBLE. PER FBC
 ACC 213.2 TOILET ROOMS AND BATHING ROOMS.
 WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL
 COMPLY WITH 603
  
 2. THE ADA BATHROOM LAYOUT ON THE MEP PAGES DOES NOT
 MATCH SHT A1.0 PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 3. SHT. P-3 THE GREASE WASTE RISER THE HORIZONTAL VENT
 FOR P-7 IS NOT ALLOWED IT SHALL CONNECT ABOVE THE
 CENTERLINE OF THE HORIZONTAL DRAIN PIPE. PER FBC PL
 905.3
  
 4. SHOW TRAPS ON RISER DIAGRAM FOR P-7, FS-1, FD-1. PER
 WPB AMEND TO FBC 107.2.1
  
 5. TRAP PRIMERS ARE REQUIRED ON ALL FLOOR DRAINS. PER
 FBC PL 1002.4
  
 6. IF YOUR USING A GARBAGE DISPOSAL ON P-4 IT SHALL
 COMPLY WITH FBC PL 1003.3.2 FOOD WASTE GRINDERS.
 WHERE FOOD WASTE GRINDERS CONNECT TO GREASE
 INTERCEPTORS, A SOLIDS INTERCEPTOR SHALL SEPARATE THE
 DISCHARGE BEFORE CONNECTING TO THE GREASE INTERCEPTOR.
 SOLIDS INTERCEPTORS AND GREASE INTERCEPTORS SHALL BE
 SIZED AND RATED FOR THE DISCHARGE OF THE FOOD WASTE
 GRINDER. EMULSIFIERS, CHEMICALS, ENZYMES AND BACTERIA
 SHALL NOT DISCHARGE INTO THE FOOD WASTE GRINDER.
  
 7. DRAIN FOR THREE COMP SINK NOT SHOWN ON RISER PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 8. EXISTING HAND SINK NEXT6T TO MOP SINK IS NOT SHOWN
 ON RISER PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 9. PROVIDE THE SIZE AND SIZING CALCULATIONS FOR
 EXISTING GREASE TRAP. PER WPB AMEND TO FBC 107.2.1
  
 10. THE EXISTING GREASE TRAP SHALL BE INSPECTED AND
 VERIFIED TO BE STRUCTURALLY SOUND AND IN GOOD WORKING
 ORDER BY A SIGNED AND SEALED LETTER FROM THE ENGINEER.
 PER WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  