Plan Review Details - Permit 17010744
Plan Review Stops For Permit 17010744
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-16 Cont ID  
Sent By cthroop Date 2017-03-16 Time 08:06 Rev Time 0.00
Received By cthroop Date 2017-03-16 Time 07:54 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By skennedy Date 2017-02-23 Time 14:43 Rev Time 0.00
Received By skennedy Date 2017-02-23 Time 14:43 Sent To  
Notes
2017-02-23 15:16:551ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
 ALTERATION LEVEL II
  
 1) YOU SHOULD ADD NOTES TO THE PLAN TO INDICATE THE
 CODE IN EFFECT AND THE LEVEL OF ALTERATION AS FOLLOWS:
  
 FBC 2014 5TH ED. RESIDENTIAL
 FBC 2014 EXISTING BUILDING
 ALTERATION LEVEL II
  
 2) PROVIDE AND ENERGY SUBMITTAL PER FBC 107.
  
 3) THE DESIGNER OF RECORD IN REQUIRED TO PRINT HIS/HER
 NAME UPON PLAN AND SIGN THE PLAN. FBC-107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
  
 4) THE SHUTTER PRODUCT DOES NOT SHOW EVIDENCE OF REVIEW
 AND APPROVAL FOR USE BY THE DESIGNER OF RECORD. THIS
 MAY BE RESOLVED BY PROVIDING A SHUTTER INSTALLATION
 SCHEDULE LISTING THE PRODUCT APPROVAL NUMBER IN THE
 SCHEDULE AS HAS BEEN DONE WITH THE WINDOWS AND DOORS
 AND ALSO INCORPORATINNG AN ANCHOR SCHEDULE FOR THE
 SHUTTER TRACKS SPECIFYING THE STRUCTURE TYPE, ANCHOR
 TYPE, AND ANCHOR SPACING CONSISTENT WITH THE PRODUCT
 INFORMATION. FBC 107.3.4 - PROVIDE PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD. SPECIFICALLY, PROVIDE SHUTTER SUBMITTAL.
  
 5) PROVIDE DETAILS TO SHOW EXISTING WALL AND CEILING
 INSULATION AND PROPOSED WALL AND CEILING INSULATION.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-15 Cont ID  
Sent By skennedy Date 2017-03-15 Time 17:37 Rev Time 0.00
Received By skennedy Date 2017-03-15 Time 17:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-13 Cont ID  
Sent By vperez Date 2017-02-13 Time 10:03 Rev Time 0.00
Received By vperez Date 2017-02-13 Time 10:03 Sent To  
Notes
2017-02-13 10:04:49APPLICABLE CODES IN EFFECT:
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PROVIDE AIC CALCULATIONS FOR NEW SERVICE SHOWN AND
 LABEL SERVICE EQUIPMENT AND PANEL BOARDS WITH AIC
 RATINGS. FBC 107.3.5
 2. PROVIDE A NEW ONE-LINE RISER DIAGRAM REFLECTING NEW
 150AMP SERVICE
 3. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE
 PER FBC RES E3609.3
 4. LABEL RECEPTACLE W/P GFCI PROTECTED AT THE HVAC AC
 LOCATION FOR SERVICE PER FBC RES E3901.12 HVAC OUTLET.
  
 5. FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS OR CONCERNS.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-29 Cont ID  
Sent By njwira Date 2017-03-29 Time 11:06 Rev Time 0.00
Received By njwira Date 2017-03-24 Time 15:37 Sent To  
Notes
2017-03-27 15:37:26RESUB ROUTED TO NWJIRA VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-24 Cont ID  
Sent By cpuell Date 2017-03-24 Time 10:49 Rev Time 0.00
Received By cpuell Date 2017-03-10 Time 09:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-23 Cont ID  
Sent By skennedy Date 2017-02-23 Time 14:43 Rev Time 0.00
Received By skennedy Date 2017-01-20 Time 10:03 Sent To  
Notes
2017-01-23 13:09:50R03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-15 Cont ID  
Sent By skennedy Date 2017-03-15 Time 17:37 Rev Time 0.00
Received By skennedy Date 2017-03-15 Time 17:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-02-23 Cont ID  
Sent By skennedy Date 2017-02-23 Time 14:43 Rev Time 0.00
Received By skennedy Date 2017-02-23 Time 14:43 Sent To  
Notes
2017-02-23 15:25:061ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 PROVIDE AN ENERGY SUBMITTAL AND EQUIPMENT SIZING
 CALCULATION AND MECHANICAL EQUIPMENT SCHEDULE PER FBC
 107 AND DEMONSTRATE COMPLIANCE WITH THE SECTIONS BELOW:
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R403.6.1 EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
 R403.6.1.1 COOLING EQUIPMENT CAPACITY.
 COOLING ONLY EQUIPMENT SHALL BE SELECTED SO THAT ITS
 TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED TOTAL
 LOAD, BUT NOT MORE THAN 1.15 TIMES GREATER THAN THE
 TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE
 SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE
 SIZE PROVIDED BY THE MANUFACTURER?S PRODUCT LINES. THE
 CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL
 NOT BE LESS THAN THE CALCULATED LATENT LOAD.
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-03-15 Cont ID  
Sent By skennedy Date 2017-03-15 Time 17:37 Rev Time 0.00
Received By skennedy Date 2017-03-15 Time 17:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2017-02-10 Cont ID  
Sent By gjohnson Date 2017-02-10 Time 10:08 Rev Time 0.00
Received By gjohnson Date 2017-02-09 Time 15:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2017-02-23 Cont ID  
Sent By skennedy Date 2017-02-23 Time 14:25 Rev Time 0.00
Received By skennedy Date 2017-02-23 Time 14:25 Sent To  
Notes
2017-02-23 14:26:23COMPLETED UNDER PERMIT NUMBER 17010745

Review Stop Z ZONING
Rev No 3 Status P Date 2017-03-29 Cont ID  
Sent By njwira Date 2017-03-29 Time 11:06 Rev Time 0.00
Received By njwira Date 2017-03-28 Time 15:03 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2017-03-23 Cont ID  
Sent By njwira Date 2017-03-23 Time 13:45 Rev Time 0.00
Received By njwira Date 2017-03-20 Time 15:17 Sent To I
Notes
2017-03-23 13:45:383/23/17- FAILED
  
 THERE ARE NO COPIES OF A SURVEY SHOWING WHERE THE A/C
 EQUIPMENT IS GOING.
  
  
 PLEASE CONTACT
 NATHAN WIRA- ZONING TECHNICIAN
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING AND ZONING
 DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 OFFICE HOURS: M-F 8AM - 5PM
 (561)822-1442
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2017-01-26 Cont ID  
Sent By njwira Date 2017-01-26 Time 15:44 Rev Time 0.00
Received By njwira Date 2017-01-26 Time 14:09 Sent To  
Notes
2017-01-26 15:46:131/26/17- FAILED
  
 SF-7 SINGLE FAMILY LOW DENSITY RESIDENTIAL
  
 FAILED
 1. 94-305(B)4- MUST PROVIDE A SURVEY SHOWING WHERE THE
 A/C EQUIPMENT IS GOING AND IT CANNOT PROJECT MORE THAN
 4FT. INTO A REQUIRED SETBACK.
  
 PASSED
 1. ONE KITCHEN MAKES THIS ONE UNIT
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  