Plan Review Details - Permit 17010635
Plan Review Stops For Permit 17010635
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-08 Cont ID  
Sent By hmoser Date 2017-02-08 Time 10:35 Rev Time 0.00
Received By hmoser Date 2017-02-06 Time 12:54 Sent To  
Notes
2017-02-07 12:54:19RESUB ROUTED TO HMOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-24 Cont ID  
Sent By hmoser Date 2017-01-24 Time 10:59 Rev Time 0.00
Received By hmoser Date 2017-01-18 Time 09:58 Sent To  
Notes
2017-01-19 09:58:40MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-02-08 Cont ID  
Sent By hmoser Date 2017-02-08 Time 10:35 Rev Time 0.00
Received By hmoser Date 2017-02-08 Time 10:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-24 Cont ID  
Sent By hmoser Date 2017-01-24 Time 10:46 Rev Time 0.00
Received By hmoser Date 2017-01-24 Time 10:46 Sent To  
Notes
2017-01-24 10:51:01PLAN DENIED
 1) PROVIDE WIND LOAD CALCULATIONS FOR THE COOLER
 WITH THE PLAN. PER SECTION 301.15 WIND RESISTANCE 2014
 (M)
 2) ADD VALUE OF COOLER TO THE APPLICATION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676