Plan Review Details - Permit 17010634
Plan Review Stops For Permit 17010634
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2017-03-15 Cont ID  
Sent By jwitmer Date 2017-03-15 Time 14:21 Rev Time 0.00
Received By jwitmer Date 2017-03-15 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-02-17 Cont ID  
Sent By jwitmer Date 2017-02-17 Time 13:30 Rev Time 0.00
Received By jwitmer Date 2017-02-17 Time 12:01 Sent To  
Notes
2017-02-17 13:28:52BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010634
 W. P. B. MASTER: 16080300
 ADD: 5016 S. DIXIE HWY.
 CONT: THERMA SEAL ROOF SYSTEMS LLC
 TEL: 561-223-2096
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. FEB. 17/2017
 ACTION: DENIED
  
 1A) THE DESIGNER OF RECORD HAS NOT REVIEWED THE ROOFING
 PRODUCT APPROVAL NOR APPLIED THEIR SHOP DRAWING STAMP
 OF APPROVAL. 2014 FLORIDA BUILDING CODE W 2014 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
 PLEASE CIRCLE WHICH PRODUCT THAT WILL BE APPLIED ON
 THIS ROOF:
 A3100R ACRYLIC TOP COAT
 S C1000 TOP COAT
 S-2000 SOLVENTLESS SILICONE BASECOAT/ TOP COAT
 S1600 BASE COAT/ TOP COAT
  
 1B) THE DESIGNER OF RECORD WILL NEED TO INVESTIGATE THE
 EXISTING ROOF TYPE AND CONDITION TO SEE IF THIS SYSTEM
 CAN BE APPLIED TO THE EXISTING ROOF COVERING AS A ROOF
 OVER. SEE NOA 12-0426.06 LIMITATION# 4.
 MIAMI-DADE NOA 12-0426.06 GACO WESTERN ROOF COATING
 SYSTEMS, LIMITATION # 4.
 1C)2014 FBC-B 1510.3 RECOVERING VERSUS REPLACEMENT. NEW
 ROOF COVERINGS SHALL NOT BE INSTALLED WITHOUT FIRST
 REMOVING ALL EXISTING LAYERS OF ROOF COVERINGS DOWN TO
 THE ROOF DECK WHERE ANY OF THE FOLLOWING CONDITIONS
 OCCUR:
 1. WHERE THE EXISTING ROOF OR ROOF COVERING IS WATER
 SOAKED OR HAS DETERIORATED TO THE POINT THAT THE
 EXISTING ROOF OR ROOF COVERING IS NOT ADEQUATE AS A
 BASE FOR ADDITIONAL ROOFING.
 2. WHERE THE EXISTING ROOF COVERING IS WOOD SHAKE,
 SLATE, CLAY, CEMENT OR ASBESTOS-CEMENT TILE.
 3. WHERE THE EXISTING ROOF HAS TWO OR MORE APPLICATIONS
 OF ANY TYPE OF ROOF COVERING.
 4. WHEN BLISTERS EXIST IN ANY ROOFING, UNLESS BLISTERS
 ARE CUT OR SCRAPED OPEN AND REMAINING MATERIALS SECURED
 DOWN BEFORE APPLYING ADDITIONAL ROOFING.
 5. WHERE THE EXISTING ROOF IS TO BE USED FOR ATTACHMENT
 FOR A NEW ROOF SYSTEM AND COMPLIANCE WITH THE
 SECUREMENT PROVISIONS OF SECTION 1504.1 CANNOT BE MET.
  
 1D) LIMITATION # 8, SHOW COMPLIANCE WITH: GACO WESTERN
 ROOF COATING SYSTEMS SHALL ONLY BE APPLIED BY A
 FACTORY TRAINED AND CERTIFIED APPLICATORS!!!
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-20 Cont ID  
Sent By jwitmer Date 2017-01-20 Time 09:25 Rev Time  
Received By jwitmer Date 2017-01-20 Time 08:00 Sent To  
Notes
2017-01-20 09:25:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010634
 W. P. B. MASTER: 16080300
 ADD: 5016 S. DIXIE HWY.
 CONT: THERMA SEAL ROOF SYSTEMS LLC
 TEL: 561-223-2096
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 20/2017
 ACTION: DENIED
  
 1) THE DESIGNER OF RECORD HAS NOT REVIEWED THE ROOFING
 PRODUCT APPROVAL NOR APPLIED THEIR SHOP DRAWING STAMP
 OF APPROVAL.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 2) THE CONTRACTOR OF RECORD FAILED TO PRODUCE THE
 NECESSARY SHEETS OF THE PRODUCT APPROVAL NECESSARY FOR
 A THOROUGH REVIEW. MISSING SHEETS FROM ROOFING APPROVAL
 FL16440-R9 APPENDIX SHEETS 2-3. ADDITIONAL INFORMATION
 REQUIRED. 107.2.1.3, MISSING DOCUMENTS.
  
 3) THE SUB-SYSTEMS FROM APPENDIX 1, PAGES 45 OF 46
 SYSTEM NUMBER R-53 IS CIRCLED. EXISTING ROOF SYSTEM
 WITH GRANULE-SURFACED MODIFIED BITUMEN CAP SHEET
 INSTALLED OVER TECTUM ROOF DECK. APPENDIX SHEETS 2-3
 USE AND LIMITATION OF THE VARIOUS SUB-SYSTEMS NOTE
 NUMBER 12 THE EXISTING ROOF SYSTEM SHALL BE CAPABLE OF
 RESISTING PROJECT DESIGN PRESSURES ON ITS OWN MERIT TO
 THE SATISFACTION OF THE AHJ, AS DOCUMENTATION THROUGH
 FIELD UPLIFT TESTING IN ACCORDANCE WITH TAS 124.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED
 BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL
 ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING
 SYSTEM, MATERIALS, FASTENING
 REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE
 RATING THAT ARE REQUIRED TO BE INSTALLED. PRODUCT
 EVALUATION AND INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND CRITERIA REQUIRED FOR THE SPECIFIC SITE
 OR A STATEMENT BY AN ARCHITECT OR ENGINEER FOR THE
 SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION
 DOCUMENTS.
  
 4) UNDER THE ISSUED PERMIT SET OF PLANS THE WIND DESIGN
 CRITERIA IS FOUND ON SHEET S-2.
 170 VULT
 131.75 VASD
 EXPOSURE C
 WINDOW AND DOOR PRESSURES FOR REPLACED UNITS.
 THE MEAN ROOF HEIGHT NOT PROVIDED, NOR THE ROOF
 PRESSURES AT 10 SQ. FT. FOR ROOF ZONES 1, 2 OR 3.
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 (3.) WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 (5.) DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 NOTE IF THE DESIGN CRITERIA IS BY ANOTHER DESIGN
 PROFESSIONAL (ENGINEER OF RECORD) A DELEGATE ENGINEER
 THEN THE ROOF TOP DESIGN PRESSURES MUST BE REVIEWED BY
 THE ENGINEER OF RECORD.
 61G15-30.003 ENGINEERING DOCUMENT CLASSIFICATION. FL
 61G-15-30.006 (3) THE DELEGATED ENGINEER SHALL FORWARD
 THE DELEGATED ENGINEERING DOCUMENTS TO THE ENGINEER OF
 RECORD FOR REVIEW.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-03-15 Cont ID  
Sent By   Date 2017-03-15 Time   Rev Time 0.00
Received By lmarchan Date 2017-03-14 Time 11:00 Sent To  
Notes
2017-03-15 11:00:28RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-17 Cont ID  
Sent By   Date 2017-02-17 Time   Rev Time 0.00
Received By lmarchan Date 2017-02-15 Time 13:27 Sent To  
Notes
2017-02-16 13:27:22RESUB ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-20 Cont ID  
Sent By jwitmer Date 2017-01-20 Time 09:25 Rev Time 0.00
Received By jwitmer Date 2017-01-18 Time 09:54 Sent To  
Notes
2017-01-19 09:54:53JWITMER