Plan Review Stops For Permit 17010633 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2017-03-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-03-27 |
Time |
16:03 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-03-27 |
Time |
16:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2017-02-14 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2017-02-14 |
Time |
16:02 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2017-02-14 |
Time |
13:23 |
Sent To |
|
|
Notes |
2017-02-14 16:02:02 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 17010633 | | ADD: 4395 EASLEY DR. / ADDITION OF A AERATION BLOWER | | NO. 10 | | CONT: TBD / TO BE DETERMINED | | TEL: 561-997-8070 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: TUES. FEB. 14/ 2017 | | ACTION: DENIED | | | | 1) SHEET S01 PAD FOR MOUNTING TYP PUMP OR EQUIP. BASE | | SEEMS TO BE GENERIC, NO EQUIPMENT SPECS HAVE BEEN | | PROVIDED FOR THE NEW AERATION BLOWER # 10, NOR HAVE | | THEY BEEN REVIEWED BY THE DESIGNER OF RECORD TO SEE IF | | THE EQUIPMENT PAD IS SIZED CORRECTLY, THE OTHER UNKNOWN | | IS THE ANCHOR LOCATION TO ANCHOR THE NEW AERATION | | BLOWER. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. | | | | 2) THE STRUCTURAL SHEET DOES NOT HAVE ANY SEAL OR | | SIGNATURE. 61G15-23.005 PROCEDURES FOR SIGNING AND | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES | | DEPARTMENT | | 401 CLEMATIS ST. | | WEST PALM BEACH. FL 33402 | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2017-03-23 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2017-03-23 |
Time |
10:02 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2017-03-23 |
Time |
10:03 |
Sent To |
|
|
Notes |
2017-03-23 10:04:49 | 2ND ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. PLEASE HAVE DESIGNER OF RECORD SIGN AND SEAL | | ELECTRONIC PLANS SUBMITTED. | | 2. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | THIS PROJECT. | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2017-03-06 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2017-03-06 |
Time |
07:50 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2017-03-06 |
Time |
07:50 |
Sent To |
|
|
Notes |
2017-03-06 08:00:49 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 | | COMMENTS: | | | | 1. PLEASE HAVE DESIGNER OF RECORD SIGN AND SEAL | | ELECTRONIC PLANS SUBMITTED. | | 2. ADDRESS MECHANICAL COMMENTS REGARDING BLOWER UNIT | | SPECS. FBC 107.3.5 | | 3. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING | | THIS PROJECT. | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2017-03-06 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2017-03-06 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2017-02-10 |
Time |
13:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2017-03-27 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-03-27 |
Time |
16:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-03-15 |
Time |
08:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2017-03-06 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2017-03-06 |
Time |
09:25 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2017-01-26 |
Time |
11:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2017-03-24 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-03-24 |
Time |
17:01 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-03-24 |
Time |
17:01 |
Sent To |
|
|
Notes |
2017-03-24 17:03:20 | MECHANICAL PROVISO: | | 3/24/2017 | | | | APPROVED SHOP DRAWINGS AND INSTALLATION DETAILS SHALL | | BE SUBMITTED TO THE BUILDING DEPARTMENT PRIOR TO | | INSPECTION./CCOLE |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2017-02-09 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2017-02-09 |
Time |
08:31 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2017-02-08 |
Time |
15:51 |
Sent To |
|
|
Notes |
2017-02-09 08:36:23 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #17010633 | | 2/9/17 | | | | 1) SUBMIT MANUFACTURER'S SPECIFCATIONS FOR THE BLOWER | | UNIT WITH REVIEW AND APPROVAL STAMP BY THE ENGINEER OF | | RECORD. | | | | 2) PROVIDE A DETAIL FOR MOUNTING THE BLOWER TO THE PAD- | | SECTION 304.1 | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2017-02-27 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2017-02-27 |
Time |
12:21 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2017-02-27 |
Time |
12:21 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2017-05-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2017-03-27 |
Time |
08:14 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2017-05-11 |
Time |
08:14 |
Sent To |
|
|
Notes |
2017-03-24 17:05:37 | MECHANICAL PLAN SHEETS ARE NOT ELECTRONICALL SIGNED AND | | SEALED. | | CCOLE | | 3/24/17 | 2017-02-14 13:25:20 | STRUCTURAL SHEET IS NOT SIGNED ELECTRONICALLY. | | 61G15-23.005 PROCEDURES FOR SIGNING AND SEALING | | ELECTRONICALLY TRANSMITTED PLANS, SPECIFICATIONS, | | REPORTS OR OTHER DOCUMENTS. | | JAMES A. WITMER BN, PX, CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | 2017-02-09 09:01:39 | MECHANICAL PLANS ARE NOT ELECTRONICALLY SIGNED AND | | SEALED BY THE ENGINEER. | | CCOLE- 2/9/17 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2017-03-02 |
|
|
Cont ID |
|
Sent By |
jroach |
Date |
2017-03-02 |
Time |
14:41 |
Rev Time |
0.00 |
Received By |
jroach |
Date |
2017-03-02 |
Time |
14:41 |
Sent To |
|
|
Notes |
|
|