Plan Review Details - Permit 17010618
Plan Review Stops For Permit 17010618
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2017-10-10 Cont ID  
Sent By jgomez Date 2017-10-10 Time 16:19 Rev Time 0.00
Received By jgomez Date 2017-10-10 Time 16:18 Sent To  
Notes
2017-10-10 16:21:20BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) BALCONY
 DECK UNDERLAYMENT. ARCHITECT TO SPECIFY BALCONY FLOOR
 FINISH. NOTE: PRODUCT APPROVAL TO BE DESIGNED TO BE
 USED W/ SPECIFIED FINISH. MARK ASSEMBLY TO BE USED AND
 PROVIDE SIGNED/SEALED RAS 117 CALCULATIONS IF REQ'D.
 B) SINGLE HUNG WINDOWS FOR LARGE MISSILE IMPACT.
 C) WINDOW MULLIONS AND SPECIFY MULLION SIZE.
 D) FIXED WINDOWS AS SPECIFIED ON PLANS.
 E) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS.
 2- ARCHITECT TO APPROVE ABOVE PRODUCT APPROVALS.
 3- ENGINEER'S RAS 117 CALCULATIONS SUBMITTED NEED
 ORIGINAL SEAL & SIGNATURE (NOT COPY). CHAPTER 471 F.S.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2017-09-29 Cont ID  
Sent By jgomez Date 2017-09-29 Time 12:49 Rev Time 0.00
Received By jgomez Date 2017-09-28 Time 18:28 Sent To  
Notes
2017-09-28 18:29:06BUILDING REVIEW APPROVED WITH PROVISO:
 1- ARCHITECT TO REVISE OVERHEAD GARAGE DOOR DESIGN
 PRESSURES ON SHEET A3.2 TO CORRESPOND TO EXPOSURE "D".
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) BALCONY
 DECK UNDERLAYMENT. ARCHITECT TO SPECIFY BALCONY FLOOR
 FINISH. NOTE: PRODUCT APPROVAL TO BE DESIGNED TO BE
 USED W/ SPECIFIED FINISH. MARK ASSEMBLY TO BE USED AND
 PROVIDE SIGNED/SEALED RAS 117 CALCULATIONS IF REQ'D.
 B) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN
 PRESSURES. COORDINATE WITH ITEM #1 ABOVE.
 C) SINGLE HUNG WINDOWS FOR LARGE MISSILE IMPACT.
 D) WINDOW MULLIONS AND SPECIFY MULLION SIZE.
 E) FIXED WINDOWS AS SPECIFIED ON PLANS.
 F) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS.
 3- ARCHITECT TO APPROVE ABOVE PRODUCT APPROVALS.
 4- ENGINEER'S RAS 117 CALCULATIONS SUBMITTED NEED
 ORIGINAL SEAL & SIGNATURE (NOT COPY). CHAPTER 471 F.S.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date 2017-08-01 Cont ID  
Sent By jgomez Date 2017-08-01 Time 11:14 Rev Time 0.00
Received By jgomez Date 2017-08-01 Time 11:13 Sent To  
Notes
2017-08-01 11:14:2308/01/17 YANIL ESPINAL E-MAILED BACK. THEY ARE GETTING
 THE PRODUCT APPROVALS TO RE-SUBMIT. PLANS IN BACK LARGE
 PLANS SHELF UNDER "J". JG.
  
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- FLAT ROOF NOA 14-0529.02 SUBMITTED: PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQ'D GENERAL
 LIMITATION #7.
  
 2- ARCHITECT TO REVISE THE DESIGN PRESSURES FOR THE
 OVERHEAD GARAGE DOOR TO CORRESPOND TO EXPOSURE "D". SEE
 SHEET A3.1
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) BALCONY DECK UNDERLAYMENT. NOTE: NEED PRODUCT
 APPROVAL THAT IS DESIGNED TO BE USED WITH THE SPECIFIC
 DECK FINISH MATERIAL TO BE INSTALLED IN THIS HOUSE. IN
 ADDITION CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF REQUIRED.
  
 B) ROOF CLAY TILE. NOA 12-0210.01 SUBMITTED EXPIRED ON
 02/01/16.
  
 C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVES.
  
 D) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT OF RECORD. COORDINATE WITH
 ITEM #2 ABOVE.
  
 E) SINGLE HUNG WINDOWS. NEED LARGE MISSILE IMPACT
 RESISTANT PRODUCT APPROVAL. NOA 15-0512.08 SUBMITTED IS
 FOR SMALL MISSILE IMPACT RESISTANT.
  
 F) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY
 MULLION SIZE.
  
 G) FIXED WINDOWS AS SPECIFIED ON PLANS.
  
 H) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS.
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status   Date 2017-08-01 Cont ID  
Sent By jgomez Date 2017-07-31 Time 14:19 Rev Time 0.00
Received By jgomez Date 2017-07-31 Time 09:22 Sent To  
Notes
2017-07-31 09:40:03BUILDING REVIEW APPROVED WITH PROVISO:
 1- FLAT ROOF NOA 14-0529.02 SUBMITTED: PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQ'D GENERAL
 LIMITATION #7.
  
 2- ARCHITECT TO REVISE THE DESIGN PRESSURES FOR THE
 OVERHEAD GARAGE DOOR TO CORRESPOND TO EXPOSURE "D". SEE
 SHEET A3.1
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) BALCONY DECK UNDERLAYMENT. NOTE: NEED PRODUCT
 APPROVAL THAT IS DESIGNED TO BE USED WITH THE SPECIFIC
 DECK FINISH MATERIAL TO BE INSTALLED IN THIS HOUSE. IN
 ADDITION CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF REQUIRED.
  
 B) ROOF CLAY TILE. NOA 12-0210.01 SUBMITTED EXPIRED ON
 02/01/16.
  
 C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVES.
  
 D) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT OF RECORD. COORDINATE WITH
 ITEM #2 ABOVE.
  
 E) SINGLE HUNG WINDOWS. NEED LARGE MISSILE IMPACT
 RESISTANT PRODUCT APPROVAL. NOA 15-0512.08 SUBMITTED IS
 FOR SMALL MISSILE IMPACT RESISTANT.
  
 F) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY
 MULLION SIZE.
  
 G) FIXED WINDOWS AS SPECIFIED ON PLANS.
  
 H) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS.
  
 4- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2017-05-19 Cont ID  
Sent By jgomez Date 2017-05-19 Time 17:08 Rev Time 0.00
Received By jgomez Date 2017-05-19 Time 07:17 Sent To  
Notes
2017-05-18 18:41:32RESIDENTIAL (R3) ADDITIONS/ALTERATIONS SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014)
  
 NOTE:
 OLD PLANS WERE NOT RESUBMITTED AS REQUESTED ON PREVIOUS
 CHECKLIST. THIS DELAYS THE REVIEW PROCESS AND PROVIDES
 NO REFERENCE OF WHAT WAS REVIEWED THE FIRST TIME.
  
  
 ORIGINAL COMMENT:
 1- THERE ARE TWO SEPARATE STRUCTURES IN THIS SUBMITTAL.
 PROVIDE A PERMIT APPLICATION FOR EACH BUILDING. MAIN
 HOUSE AND GUEST HOUSE. SEC. 105.1 CITY AMENDMENTS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. NEED A
 PERMIT APPLICATION FOR EACH STRUCTURE.
  
 2- GUEST HOUSE ORIGINAL COMMENT:
 NEED TO SPECIFY 1 HOUR FIRE RATED ASSEMBLY FOR THE WEST
 WALL WITH FIRE EXPOSURE FROM BOTH SIDES AS REQUIRED BY
 TABLE R302.1(1). ASSEMBLY NEED TO TESTED IN ACCORDANCE
 WITH ASTM E 119 OR UL 263.
 RESPONSE: NEED 1 HOUR FIRE RATED WALL ASSEMBLY THAT
 PROVIDES FIRE PROTECTION FROM BOTH SIDES. THAT'S WHY I
 WROTE BOTH SIDES IN CAPITAL LETTERS TO MAKE SURE PROPER
 ASSEMBLY WAS SPECIFIED. THE SPECIFIED ASSEMBLY DESIGN
 NO. U356 IS FOR FIRE EXPOSURE ON THE INTERIOR FACE
 ONLY. REVISE AS REQUIRED. SPECIFY ASSEMBLY THAT
 PROVIDES PROTECTION ON BOTH SIDES. NOTE: THE 1 HOUR
 PROTECTION FROM BOTH SIDES APPLIES TO FIRST AND SECOND
 FLOOR NOT JUST THE SECOND FLOOR ADDITION. REVISE PLANS
 SHOWING COMPLIANCE FOR FIRST AND SECOND FLOOR.
  
 3- GUEST HOUSE ORIGINAL COMMENT:
 GUEST BEDROOM WINDOW ABOVE GARAGE DOESN'T COMPLY WITH
 THE EGRESS REQUIREMENTS OF SEC. R310 FBC-RESIDENTIAL
 5TH EDITION (2014). NEED TO COMPLY WITH THE MIN. CLEAR
 HEIGHT AND TOTAL CLEAR OPENING. REVISE AS REQUIRED.
 RESPONSE: NONE OF THE WINDOWS ON THE SECOND FLOOR
 BEDROOM COMPLIES WITH THE EGRESS REQUIREMENTS. SINGLE
 HUNG PRODUCT APPROVAL SUBMITTED IS FOR CGI WINDOWS.
 LOOK ON THE INTERNET FOR THE WINDOW SIZE CHART FOR
 SIZES THAT COMPLY FOR EGRESS (SECOND FLOOR) AND REVISE
 SIZE AS REQUIRED.
  
 4- ORIGINAL COMMENT: BUILDING SECTION AT MAIN HOUSE
 2/A2.1 SHOWS A STAIRWAY WITH OPEN RISERS. OPEN RISERS
 ARE NOT ALLOWED UNLESS THEY COMPLY WITH SEC. R311.7.5.1
 FBC-RESIDENTIAL. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE.
 RESPONSE: SECTION 2/A2.1 AND SECTION NEEDS TO BE
 REVISED/CLARIFIED. (1)THE HEADROOM CLEARANCE OF 6'-8"
 AS SHOWN WITH DASHED LINES DOESN'T WORK. (2)SPACING
 BETWEEN PICKETS CAN NOT BE 4" MIN. IT HAS TO BE LESS
 THAN 4" SO AN SPHERE CAN NOT PASS THRU. (3)MATERIALS
 AND DIMENSIONS FOR THE CONSTRUCTION OF STAIRS IS NOT
 SPECIFIED. UNABLE TO VERIFY THE SPACE BETWEEN OPEN
 RISERS FOR COMPLIANCE WITH THE OPEN RISERS EXCEPTION.
 REVISE DETAILS AND SPECIFICATIONS AS REQUIRED. NOTE:
 STAIRS/HANDRAILS SHOP DRAWINGS WILL BE REQUIRED FOR
 REVIEW PRIOR TO CONSTRUCTION TO AVOID CONFLICTS/DELAYS.
 ARCHITECT TO REVIEW AND APPROVE PRIOR TO SUBMITTAL.
  
 5- ORIGINAL COMMENT: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF ALL STAIRS,
 HANDRAILS AND GUARDRAILS (INCLUDING BALCONY GUARDRAILS)
 SHOWING COMPLIANCE WITH THE LIVE LOADS OF TABLE R301.5
 AND ALL THE REQUIREMENTS OF SEC. R311.7.5, SEC.
 R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL.
 RESPONSE: ARCHITECT TO SPECIFY THE LIVE LOADS DESIGN
 CRITERIA REQUIRED BY TABLE R301.5 SO SHOP DRAWINGS ARE
 PRODUCED BASED ON THAT DESIGN CRITERIA. DRAWINGS
 SUBMITTED DON'T PROVIDE THIS INFORMATION.
  
 6- ORIGINAL COMMENT: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE NEW SCREEN
 ENCLOSURE IN THE OPEN LOGGIA. SPECIFY ALL FRAMING
 MEMBERS AND FASTENERS AND PROVIDE MESH SPECIFICATIONS.
 SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: ARCHITECT STATED ON PLANS TO PROVIDE SIGNED
 AND SEALED SHOP DRAWINGS FOR THE SCREEN ENCLOSURE.
 THERE IS NO SHOP DRAWINGS SUBMITTAL FOR SCREEN
 ENCLOSURES. ARCHITECT NEEDS TO PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE SCREEN
 ENCLOSURE OR NEED TO PROVIDE COMPLETE ENGINEERED
 DRAWINGS AND SPECIFICATIONS UNDER A SEPARATE PERMIT.
  
 7- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R16
 SUBMITTED;
 A) ORIGINAL COMMENT: CLEARLY SPECIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH THE DESIGN PRESSURES OF SEC. R301.1
 FC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) ORIGINAL COMMENT: IF SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF ZONES, THEN SIGNED
 AND SEALED RAS 117 CALCULATIONS ARE REQUIRED TO MEET
 THE DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 SEE NOTE #8 ON PAGE 2 OF 58 OF FLORIDA PRODUCT APPROVAL
 SUBMITTED.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ORIGINAL COMMENT: BALCONY DECK UNDERLAYMENT. NOTE:
 NEED PRODUCT APPROVAL THAT IS DESIGNED TO BE USED WITH
 THE SPECIFIC DECK FINISH MATERIAL TO BE INSTALLED IN
 THIS HOUSE. IN ADDITION CLEARLY IDENTIFY SPECIFIC
 ASSEMBLY TO BE INSTALLED AND PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET
 THE DESIGN PRESSURES FOR ALL ROOF DECK ZONES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) ORIGINAL COMMENT: ROOF CLAY TILE. NOA 12-0210.01
 SUBMITTED EXPIRED ON 02/01/16. NEED TO PROVIDE CURRENT
 PRODUCT APPROVAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 C) ORIGINAL COMMENT: ROOF TILE ADHESIVE IF SPECIFIED BY
 THE ARCHITECT OF RECORD. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVES.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 D) ORIGINAL COMMENT: OVERHEAD GARAGE DOOR THAT MEETS
 THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT OF
 RECORD ON SHEET A3.2.
 NOA 16-0617.07 SUBMITTED DOESN'T MEET THOSE DESIGN
 PRESSURES.
 RESPONSE: IT LOOKS LIKE THE DESIGN PRESSURES SHOWN ON
 SHEET A3.2 WERE REVISED. THE REVISED DESIGN PRESSURES
 DON'T SEEM TO COMPLY WITH THE DESIGN PRESSURES FOR A
 TWO STORY STRUCTURE LOCATED IN EXPOSURE "D". REVISE
 DESIGN PRESSURES AS REQUIRED OR PROVIDE COMPLETE
 CALCULATIONS SHOWING HOW THE SPECIFIED DESIGN PRESSURES
 WERE OBTAINED.
  
 E) ORIGINAL COMMENT: SINGLE HUNG WINDOWS. NEED LARGE
 MISSILE IMPACT RESISTANT PRODUCT APPROVAL. NOA
 15-0512.08 SUBMITTED IS FOR SMALL MISSILE IMPACT
 RESISTANT.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 F) ORIGINAL COMMENT: WINDOW MULLIONS AS SHOWN ON PLANS.
 AND, SPECIFY MULLION SIZE TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 G) ORIGINAL COMMENT: FIXED WINDOWS AS SPECIFIED ON
 PLANS.
 RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 H) ORIGINAL COMMENT: GUEST HOUSE EXTERIOR SWING DOOR AS
 SHOWN ON PLANS.
  
 9- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 10- ORIGINAL COMMENT: PROVIDE DETAILS AND
 SPECIFICATIONS FOR THE GARAGE AND DWELLING SEPARATION
 AS REQUIRED BY TABLE R302.6 FBC-RESIDENTIAL.
 RESPONSE: SHEET A1.3 DOESN'T PROVIDE INFORMATION FOR
 THE GARAGE AND DWELLING SEPARATION. THE UL FIRE
 SEPARATION MENTIONED BY THE ARCHITECT ON THE RESPONSE
 LETTER IS FOR THE REQUIRED FIRE RATED EXTERIOR WALL NOT
 FOR THE SEPARATION REQUIRED AT THE GARAGE CEILING.
 PROVIDE COMPLETE INFORMATION.
  
 PLEASE READ THE FOLLOWING:
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 **** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-03-02 Cont ID  
Sent By jgomez Date 2017-03-02 Time 15:07 Rev Time 0.00
Received By jgomez Date 2017-03-01 Time 12:27 Sent To  
Notes
2017-03-01 15:03:57RESIDENTIAL (R3) ADDITIONS/ALTERATIONS BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014)
  
 1- THERE ARE TWO SEPARATE STRUCTURES IN THIS SUBMITTAL.
 PROVIDE A PERMIT APPLICATION FOR EACH BUILDING. MAIN
 HOUSE AND GUEST HOUSE. SEC. 105.1 CITY AMENDMENTS.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 3- GUEST HOUSE:
 A) ACCORDING TO SURVEY SUBMITTED, THE GARAGE SEPARATION
 ON THE WEST SIDE IS 2.0 FEET TO THE PROPERTY LINE.
 TABLE R302.1(1) FBC-RESIDENTIAL DOESN'T ALLOW OPENINGS.
 REVISE ALL WINDOW OPENINGS AND THE PROPOSED OPENING ON
 THE WEST SIDE UNDERNEATH THE NEW STAIRWAY.
  
 B) NEED TO SPECIFY 1 HOUR FIRE RATED ASSEMBLY FOR THE
 WEST WALL WITH FIRE EXPOSURE FROM BOTH SIDES AS
 REQUIRED BY TABLE R302.1(1). ASSEMBLY NEED TO TESTED IN
 ACCORDANCE WITH ASTM E 119 OR UL 263.
  
 C) GUEST BEDROOM WINDOW ABOVE GARAGE DOESN'T COMPLY
 WITH THE EGRESS REQUIREMENTS OF SEC. R310
 FBC-RESIDENTIAL 5TH EDITION (2014). NEED TO COMPLY WITH
 THE MIN. CLEAR HEIGHT AND TOTAL CLEAR OPENING. REVISE
 AS REQUIRED.
  
 4- THE WIDTH OF THE NEW GUEST HOUSE STAIRWAY DOESN'T
 COMPLY WITH SEC. R311.7.1 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
  
 5- PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING
 TO THE GUEST ROOM ABOVE AS REQUIRED BY SEC. R302.5.1
 FBC-RESIDENTIAL. SPECIFY THE DOOR MATERIAL, FIRE RATING
 AND EQUIPPED WITH SELF CLOSING DEVICE.
  
 6- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. IF
 SPECIFYING SCREWS, THEN SPECIFY SIZE AND NUMBER OF
 SCREWS. IF SPECIFYING ROOF TILE ADHESIVE, THEN ROOF
 TILE ADHESIVE PRODUCT APPROVAL IS REQUIRED. SEE ROOF
 TILE PRODUCT APPROVAL FOR LISTED ADHESIVES. NOTE:
 PROVIDE SPECIFIC FASTENING METHOD. PER CODE OR PER
 PRODUCT APPROVAL IS NOT ACCEPTED AS SHOWING COMPLIANCE.
  
 7- BUILDING SECTION AT MAIN HOUSE 2/A2.1 SHOWS A
 STAIRWAY WITH OPEN RISERS. OPEN RISERS ARE NOT ALLOWED
 UNLESS THEY COMPLY WITH SEC. R311.7.5.1
 FBC-RESIDENTIAL. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE.
  
 8- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF ALL STAIRS, HANDRAILS AND GUARDRAILS
 (INCLUDING BALCONY GUARDRAILS) SHOWING COMPLIANCE WITH
 THE LIVE LOADS OF TABLE R301.5 AND ALL THE REQUIREMENTS
 OF SEC. R311.7.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE NEW SCREEN ENCLOSURE IN THE OPEN
 LOGGIA. SPECIFY ALL FRAMING MEMBERS AND FASTENERS AND
 PROVIDE MESH SPECIFICATIONS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 10- REVISE DESIGN CRITERIA SPECIFIED ON THE RIGHT
 BOTTOM OF SHEET A3.1. WINDOW OPENINGS HAVE A TRIBUTARY
 AREA SMALLER THAN 20 SQ.FT. REVISE AS REQUIRED. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 11- TYP WALL SECTION @ NEW ADDITION 3/A4.1:
 A) DOESN'T MATCH PROPOSED CONSTRUCTION. THIS IS WOOD
 FRAMED CONSTRUCTION. THERE IS A LOT OF INFORMATION THAT
 APPLIES ONLY TO CONCRETE BLOCK CONSTRUCTION. REVISE AS
 REQUIRED TO MATCH PROPOSED CONSTRUCTION. SEC. 107.2.1
 CITY AMENDMENTS.
  
 B) CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 SHOW THE LOAD PATH BY SPECIFYING ALL STRUCTURAL
 CONNECTORS FROM TOP TO BOTTOM AS REQUIRED BY SEC.
 R601.2 FBC-RESIDENTIAL.
  
 12- WALL SECTION @ OUTDOOR PORCH & BALCONY 2/A4.1:
 A) REVISE THE ROOF SLOPE SHOWN AT HE BALCONY TO COMPLY
 WITH SEC. R905 FBC-RESIDENTIAL.
  
 B) CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 SHOW THE LOAD PATH BY SPECIFYING ALL STRUCTURAL
 CONNECTORS FROM TOP TO BOTTOM AS REQUIRED BY SEC.
 R601.2 FBC-RESIDENTIAL. ALSO, FRAMING SHOWN AT TOP OF
 THE WINDOW IS NOT CLEAR. REVISE AS REQUIRED.
  
 13- WALL SECTION @ MAIN HOUSE STAIRWELL 1/A4.1:
 A) CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 SHOW THE LOAD PATH BY SPECIFYING ALL STRUCTURAL
 CONNECTORS FROM TOP TO BOTTOM AS REQUIRED BY SEC.
 R601.2 FBC-RESIDENTIAL. ALSO, FRAMING SHOWN AT TOP AND
 BOTTOM OF THE WINDOW IS NOT CLEAR. REVISE AS REQUIRED.
  
 B) ROOF SHEATHING NOTE IS REPEATED 3 TIMES. PROVIDE
 CORRECT INFORMATION. SEC. 107.2.1 CITY AMENDMENTS.
  
 14- WALL SECTIONS @ GARAGE 4/S2 AND 5/S2 ON SHEET S2:
 A) CLEARLY SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 SHOW THE LOAD PATH BY SPECIFYING ALL STRUCTURAL
 CONNECTORS FROM TOP TO BOTTOM AS REQUIRED BY SEC.
 R601.2 FBC-RESIDENTIAL.
  
 B) MISSING THE FOOTING INFORMATION AT ALL BEARING
 WALLS. SEC. R301.1 FBC-RESIDENTIAL. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS. COORDINATE WITH THE
 FOUNDATION PLAN.
  
 15- SIZE OF STEEL BEAM SPECIFIED ON SHEET S3 IS NOT
 CLEAR. DIMENSIONS SPECIFIED ON THE STEEL BEAM SCHEDULE
 AND DETAIL 8E/S3 DON'T MATCH. ALSO, GIVEN DIMENSIONS
 DON'T CORRESPOND TO W10X49 STEEL BEAM. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 16- CLEARLY COORDINATE DETAILS 8A THRU 8E WITH FLOOR
 FRAMING PLANS AND ALL SCHEDULES SHOWN ON SHEET S3. .
 CLEARLY IDENTIFY ALL BEAM TYPES, COLUMN TYPES AND SIZES
 AND COORDINATE WITH ALL L FRAMING PLANS. CLEARLY
 SPECIFY THE WOOD HEADERS AT ALL OPENINGS. SEC. R301.1
 FBC-RESIDENTIAL. NOTE: ALSO VERIFY THICKNESS OF COLUMNS
 SUPPORTING THE STEEL BEAM (SEE COLUMN SCHEDULE AND
 DETAIL 83/S3. ALSO, SPECIFY COLUMNS SUPPORTING THE WB-4
 BEAM ON THE GUEST HOUSE. CLEARLY IDENTIFY EACH COLUMN
 AND BEAM SHOWN ON FRAMING PLANS.
  
 17- PLAN DETAIL AT "OHGD' DETAIL 6/A4 ON SHEET S3:
 CLEARLY SPECIFY ALL FASTENERS AND SIZE OF STRUCTURAL
 BUCK THAT IS GOING TO SUPPORT THE LOADS FROM THE GARAGE
 DOOR. SEC. R301.1 FBC-RESIDENTIAL.
  
 18- DETAIL 8E/S3: CLEARLY SPECIFY THE FRAMING
 CONNECTION FROM ALL STRUCTURAL MEMBERS THAT ARE
 ATTACHED TO THE STEEL BEAM. (FLOOR JOIST, ON BOTH SIDES
 AND WOOD FRAME BEARING WALL-ABOVE). SEC. R301.1
 FBC-RESIDENTIAL.
  
 19- THIS PROJECT IS NOT AN ALTERATION LEVEL 2. THIS IS
 ALTERATION LEVEL 3 AND ADDITION. REVISE INFORMATION ON
 SHEET T1 AS REQUIRED. SEC. 505 AND SEC. 507
 FBC-EXISTING BUILDING.
  
 20- PROPOSED 1ST FLOOR PLAN ON SHEET A1.2: MISSING
 GUARDRAIL INFORMATION BY THE NEW STAIRWAY. PROVIDE
 COMPLETE INFORMATION SHOWING COMPLIANCE WITH SEC.
 R312.1.1 FBC-RESIDENTIAL.
  
 21- FIRST FLOOR FOUNDATION & FRAMING PLAN ON SHEET S1:
 NEW FLOOR JOIST BY THE KITCHEN AREA ADDITION ARE
 RESTING ON THE AIR. PROVIDE COMPLETE INFORMATION
 SHOWING THE BEAMS AND SUPPORTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 22- SECOND FL. FLOOR FRAMING PLAN ON SHEET S1: PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE BEARING
 WALL SHOWN IN THE MIDDLE OF THE NEW MASTER BEDROOM AND
 MASTER BATHROOM. SEC. R301.1 FBC-RESIDENTIAL. NOTE:
 CLARIFY WHY THE SAME WALL (NOT SHOWN AS HATCHED) IS
 SHOWN ON THE ROOF FRAMING PLAN?.
  
 23- PROVIDE COMPLETE SPECIFICATIONS FOR ALL THE FRAMING
 MEMBERS AND CONNECTORS FOR OVERHANG DETAIL/SECTION 6/S2
 ON SHEET S2. SEC. R301.1 FBC-RESIDENTIAL.
  
 24- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R16
 SUBMITTED;
 A) CLEARLY SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FC-RESIDENTIAL.
  
 B) IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. SEE NOTE #8
 ON PAGE 2 OF 58 OF FLORIDA PRODUCT APPROVAL SUBMITTED.
  
 25- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) BALCONY DECK UNDERLAYMENT. NOTE: NEED PRODUCT
 APPROVAL THAT IS DESIGNED TO BE USED WITH THE SPECIFIC
 DECK FINISH MATERIAL TO BE INSTALLED IN THIS HOUSE. IN
 ADDITION CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF DECK ZONES.
  
 B) ROOF CLAY TILE. NOA 12-0210.01 SUBMITTED EXPIRED ON
 02/01/16. NEED TO PROVIDE CURRENT PRODUCT APPROVAL.
  
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  
 D) OVERHEAD GARAGE DOOR THAT MEETS THE DESIGN PRESSURES
 CALCULATED BY THE ARCHITECT OF RECORD ON SHEET A3.2.
 NOA 16-0617.07 SUBMITTED DOESN'T MEET THOSE DESIGN
 PRESSURES.
  
 E) SINGLE HUNG WINDOWS. NEED LARGE MISSILE IMPACT
 RESISTANT PRODUCT APPROVAL. NOA 15-0512.08 SUBMITTED IS
 FOR SMALL MISSILE IMPACT RESISTANT.
  
 F) WINDOW MULLIONS AS SHOWN ON PLANS. AND, SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
  
 G) FIXED WINDOWS AS SPECIFIED ON PLANS.
  
 H) GUEST HOUSE EXTERIOR SWING DOOR AS SHOWN ON PLANS.
  
 26- ARCHITECT OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 27- PROVIDE DETAILS AND SPECIFICATIONS FOR THE GARAGE
 AND DWELLING SEPARATION AS REQUIRED BY TABLE R302.6
 FBC-RESIDENTIAL.
  
 28- ENERGY CALCULATIONS SUBMITTED. THIS IS A
 CONTRIBUTING HISTORIC HOUSE (BOTH BUILDINGS). ENERGY
 CALCULATIONS ARE NOT REQUIRED, BUT IF CONTRACTOR WANTS
 TO SUBMIT THEM, THEN THE FOLLOWING REVISIONS ARE
 REQUIRED (SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014):
 MAIN HOUSE: (A) PROVIDE COMPLETE INFORMATION ON TOP OF
 FORM, INCLUDING OWNER'S NAME, BUILDER'S NAME, ETC. (B)
 THIS IS NOT NEW CONSTRUCTION. (C) CEILING INSULATION
 R-VALUE DOESN'T MATCH PLANS. (D) PROVIDE THE NAME OF
 THE PERSON WHO PREPARED THE CALCULATIONS. (E)REVISE #
 OF OCCUPANTS. (F)REVISE ROOF MATERIAL TO MATCH PLANS.
 (G)REVISE DOOR INFORMATION TO MATCH PLANS AND PRODUCT
 APPROVAL. (H) WINDOWS OVERHANG DEPTH AND SEPARATION
 DON'T MATCH PLANS. (I)BUILDER TO COMPLETE THE EPL
 DISPLAY CARD.
 GUEST HOUSE: (A) PROVIDE COMPLETE INFORMATION ON TOP OF
 FORM, INCLUDING OWNER'S NAME, BUILDER'S NAME, ETC. (B)
 CEILING INSULATION R-VALUE DOESN'T MATCH PLANS. (C)
 PROVIDE THE NAME OF THE PERSON WHO PREPARED THE
 CALCULATIONS. (D) THERE IS NOT KITCHEN IN THE GUEST
 HOUSE. (E) REVISE ROOF MATERIAL TO MATCH PLANS. (F)
 REVISE DOOR INFORMATION TO MATCH PLANS AND PRODUCT
 APPROVAL. (G) WINDOWS INFORMATION DON'T MATCH PLANS.
 (H)WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH
 PLANS. (I)BUILDER TO COMPLETE THE EPL DISPLAY CARD. (J)
 GARAGE AREA DOESN'T MATCH PLANS.
  
 *****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 **** PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. DON'T STAPLE OLD DRAWINGS. SUBMIT OLD
 DRAWIINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-05-22 Cont ID  
Sent By jleahy Date 2017-05-22 Time 08:12 Rev Time 0.00
Received By jleahy Date 2017-05-22 Time 08:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-26 Cont ID  
Sent By rlecky Date 2017-01-26 Time 14:45 Rev Time 0.00
Received By rlecky Date 2017-01-24 Time 14:38 Sent To  
Notes
2017-01-26 14:45:28 
 17010618
 200 GREENWOOD DRIVE
 RESIDENTIAL REMODEL/ADDITION
  
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PLAN SHEET E2:
  
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH
 CIRCUITS SUPPLYING OUTLETS. FBC E3902.12, NEC 210.12
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT THE REAR
 ELEVATION. NEC 210.8
  
 CEILING ELECTRICAL BOXES SUPPORTING PADDLE FANS MUST BE
 LISTED FOR THAT USE. NEC 422.18; FBC R 3905.9
  
 HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES
 NEED TO BE RATED FOR INSULATION CONTACT (IC). NEC
 410.116; FBC R 4004
  
 A RECEPTACLE IS REQUIRED ON ANY WALL SPACE TWO FEET OR
 MORE IN WIDTH (KITCHEN). NEC 210.52(A)(2)
  
 ACCESS TO THE OUTSIDE AIR CONDITION UNIT DISCONNECTS
 MAY NOT BE BLOCKED BY THE UNITS. NEC 110.26
  
 A DEDICATED LAUNDRY BRANCH CIRCUIT IS REQUIRED. NEC
 210.52 (F), FBC R 3703.3
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2014 FBC R314, 315
  
 A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75% OF THE PERMANENTLY INSTALLED LIGHTING
 FIXTURES SHALL CONTAIN HIGH EFFICIENCY LAMPS. FBC
 ER404.1
  
 PLAN SHEET E3:
  
 A RECEPTACLE IS REQUIRED ON ANY WALL SPACE TWO FEET OR
 MORE IN WIDTH (GUEST HOUSE). NEC 210.52(A)(2)
  
 A DEDICATED LAUNDRY BRANCH CIRCUIT IS REQUIRED. NEC
 210.52 (F), FBC R 3703.3
  
  
 AHU #3 REQUIRES AN EQUIPMENT DISCONNECT. NEC 422.30 FBC
 R E4101.5
  
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94; FBC R E3609
  
 PROVIDE A GROUND ROD AND GROUNDING ELECTRODE FOR GUEST
 HOUSE PANEL B. NEC 250.32
  
 VERIFY THAT PANEL B HAS THE REQUIRED SAFETY CLEARANCES
 AND IS RATED FOR A WET LOCATION. NEC 110.26, 110.11
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654(OFFICE)
 561-373-3701(CELL)
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2017-05-18 Cont ID  
Sent By gjohnson Date 2017-05-18 Time 17:05 Rev Time 0.00
Received By gjohnson Date 2017-05-18 Time 17:05 Sent To  
Notes
2017-05-18 17:05:34GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-02-09 Cont ID  
Sent By gjohnson Date 2017-02-09 Time 12:40 Rev Time 0.00
Received By gjohnson Date 2017-02-09 Time 12:40 Sent To  
Notes
2017-02-09 12:41:371ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS: APPLICATION INDICATES GAS WORK .
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL
 CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER
 FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU 402.4(37).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY,
 (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ?
 USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE
 SEC. 402.4.1.
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE
 FBC-2014 FUEL GAS CODE SEC. 304.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2014
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2017-07-31 Cont ID  
Sent By destabro Date 2017-07-31 Time 15:00 Rev Time 0.00
Received By destabro Date 2017-07-31 Time 15:00 Sent To B
Notes
2017-07-31 15:02:017/31/2017 - NO CHANGES TO PLANS - MEETS HPB APPROVAL.
 DLE

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2017-05-12 Cont ID  
Sent By destabro Date 2017-05-12 Time 11:15 Rev Time 0.00
Received By destabro Date 2017-05-12 Time 11:15 Sent To B
Notes
2017-05-12 11:22:365/12/2017 - HISTORIC NOTES THE REMOVAL OF THE WESTERN
 WINDOW ON THE ACCESSORY STRUCTURE DUE TO BUILDING CODE
 CONCERNS, ALONG WITH THE REMOVAL OF THE PAIRED WINDOW
 ON THE GROUND FLOOR OF THE WESTERN ELEVATION DUE TO
 NECESSARY BRACING. HOWEVER, GARAGE DOORS STILL DO NOT
 MEET THE DESIGN GUIDELINES OF THE HISTORIC DISTRICT OR
 THE HPB APPROVAL. SAME COMPANY MANUFACTURES APPROPRIATE
 STYLE DOORS IN THE THERMACORE, CARRIAGE HOUSE, AND
 COURTYARD LINE - REVISE PRODUCT APPROVALS ACCORDINGLY.
 DLE

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2017-02-06 Cont ID  
Sent By destabro Date 2017-02-06 Time 11:00 Rev Time 0.00
Received By destabro Date 2017-02-06 Time 11:00 Sent To B
Notes
2017-02-06 11:05:062/6/2017 - PLAN REFLECTS APPROVED WORK VIA HPB CASE
 16-75 EXCEPT FOR THE GARAGE DOOR. EXISTING
 CONFIGURATION HAS TWO BAYS - PROPOSED REMODEL WILL
 REQUIRE ONE LARGE OPEN BAY. TO SIMULATE THE HISTORIC
 APPEARANCE, PLEASE PROVIDE A TWO-BAY DOOR STYLE AS
 APPLIED TO A SINGLE WIDE-BAY. THE PROPOSED DOOR IS
 MODERN IN STYLE AND DOES NOT MEET DESIGN GUIDELINES FOR
 DISTRICT. PLEASE DIRECT QUESTIONS TO DESIREE ESTABROOK,
 HISTORIC PRESERVATION PLANNER AT 561.822.1428.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-09-29 Cont ID  
Sent By jgomez Date 2017-09-29 Time 16:02 Rev Time 0.00
Received By jgomez Date 2017-09-18 Time 16:18 Sent To  
Notes
2017-09-19 16:18:47JGOMEZ'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-07-31 Cont ID  
Sent By jgomez Date 2017-07-31 Time 15:13 Rev Time 0.00
Received By jgomez Date 2017-07-21 Time 15:48 Sent To  
Notes
2017-07-27 15:31:39R23 TRAVELLING WITH 17070856

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-05-22 Cont ID  
Sent By jleahy Date 2017-05-22 Time 08:12 Rev Time 0.00
Received By jleahy Date 2017-05-01 Time 11:42 Sent To  
Notes
2017-05-02 13:14:25R29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-03-06 Cont ID  
Sent By hmoser Date 2017-03-06 Time 13:16 Rev Time 0.00
Received By hmoser Date 2017-01-18 Time 15:28 Sent To  
Notes
2017-01-19 15:28:56R22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-05-19 Cont ID  
Sent By jgomez Date 2017-05-19 Time 07:42 Rev Time 0.00
Received By jgomez Date 2017-05-19 Time 07:42 Sent To  
Notes
2017-05-19 07:43:17$236.59 PAID. MU-2017-011708.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-03-01 Cont ID  
Sent By jgomez Date 2017-03-01 Time 15:04 Rev Time 0.00
Received By jgomez Date 2017-03-01 Time 15:04 Sent To  
Notes
2017-03-01 15:04:411- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-05-16 Cont ID  
Sent By hmoser Date 2017-05-16 Time 15:55 Rev Time 0.00
Received By hmoser Date 2017-05-16 Time 13:24 Sent To  
Notes
2017-05-16 15:54:58PASS PROVISO
 1) REFER TO SECTION R403.2.1 FLORIDA ENERGY CODE 2014
 SUPPLY DUCT IN ATTIC SHALL BE INSTALLED TO A MINIMUM OF
 R-8
 2) CAN'T READ CONDENSER TIE DOWN DETAIL PROVIDE A NEW
 DETAIL AT FINAL INSPECTION.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-03-06 Cont ID  
Sent By hmoser Date 2017-03-06 Time 13:16 Rev Time 0.00
Received By hmoser Date 2017-03-06 Time 11:18 Sent To  
Notes
2017-03-06 13:15:56PLAN DENIED
 1) PROVIDE THE MANUFACTURER'S INSTALLATION INSTRUCTIONS
 ON THE FIRE PLACE IF NOT EXISTING. 304.1 FBC (M) 2014
 2) A/C #1 PROVIDE DUCT SIZE ON RETURN AIR FROM
 AIR HANDLER TO 24 X18 CAN. 107 FBC 2014
 3) A/C # 1 14 SUPPLY DUCT FROM 2ND FLOOR TO 1ST FL
 IS TIED INTO WHAT SIZE DUCT SECTION 107 FBC 2014
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-05-18 Cont ID  
Sent By gjohnson Date 2017-05-18 Time 17:04 Rev Time 0.00
Received By gjohnson Date 2017-05-18 Time 10:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-02-09 Cont ID  
Sent By gjohnson Date 2017-02-09 Time 12:19 Rev Time 0.00
Received By gjohnson Date 2017-02-09 Time 11:03 Sent To  
Notes
2017-02-09 12:34:321ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. P2 RISER DIAGRAM HAS THE FOLLOWING DEFICIENCY.
 A) THE WASHING MACHINE IS NOT VENTED.
 B) BATHROOM #2 IS NOT VENTED.
 C) THE SHOWER AND WATER CLOSET IN BATHROOM #1 IS NOT
 VENTED.
 D) THE LAVATORY IN BATHROOM #1 IS NOT VENTED.
 E) THE KITCHEN IS NOT VENTED.
 PER FBC RES P3101.2.1
  
 2. CLEAN OUTS ARE REQUIRED AT THE BASE OF ALL SOIL AND
 WASTE STACKS. PER FBC RES P3005.2.6
  
 3. THE WET BAR ABOVE THE GARAGE SHALL CONNECT TO THE
 BUILDING DRAIN DOWN STREAM OF THE BATHROOM GROUP. PER
 FBC RES P3108.1
  
 4. SHOW THE LOCATION OF THE WATER HEATER INDICATE IF
 NEW OR EXISTING. PER WPB AMEND TO FBC 107.2.1
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2017-07-31 Cont ID  
Sent By jgomez Date 2017-07-31 Time 15:14 Rev Time 0.00
Received By jgomez Date 2017-07-31 Time 15:14 Sent To  
Notes
2017-07-31 15:16:00BUILDING REVIEW APPROVED WITH PROVISO:
 1- FLAT ROOF NOA 14-0529.02 SUBMITTED: PROVIDE SIGNED
 AND SEALED RAS 117 CALCULATIONS AS REQ'D GENERAL
 LIMITATION #7.
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) BALCONY DECK UNDERLAYMENT. NOTE: NEED PRODUCT
 APPROVAL THAT IS DESIGNED TO BE USED WITH THE SPECIFIC
 DECK FINISH MATERIAL TO BE INSTALLED IN THIS HOUSE. IN
 ADDITION CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF REQUIRED.
  
 B) ROOF CLAY TILE. NOA 12-0210.01 SUBMITTED EXPIRED ON
 02/01/16.
  
 C) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVES.
  
 3- ARCHITECT OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVALS.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2017-05-19 Cont ID  
Sent By jgomez Date 2017-05-19 Time 18:08 Rev Time 0.00
Received By jgomez Date 2017-05-19 Time 18:07 Sent To  
Notes
2017-05-19 18:08:221- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R16
 SUBMITTED;
 A) CLEARLY SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FC-RESIDENTIAL.
  
 B) IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. SEE NOTE #8
 ON PAGE 2 OF 58 OF FLORIDA PRODUCT APPROVAL SUBMITTED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) BALCONY DECK UNDERLAYMENT. NOTE: NEED PRODUCT
 APPROVAL THAT IS DESIGNED TO BE USED WITH THE SPECIFIC
 DECK FINISH MATERIAL TO BE INSTALLED IN THIS HOUSE. IN
 ADDITION CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF DECK ZONES.
  
 B) ROOF CLAY TILE. NOA 12-0210.01 SUBMITTED EXPIRED ON
 02/01/16. NEED TO PROVIDE CURRENT PRODUCT APPROVAL.
  
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2017-03-02 Cont ID  
Sent By jgomez Date 2017-03-02 Time 18:03 Rev Time 0.00
Received By jgomez Date 2017-03-02 Time 18:03 Sent To  
Notes
2017-03-02 18:19:311- FLAT ROOF FLORIDA PRODUCT APPROVAL FL2533-R16
 SUBMITTED;
 A) CLEARLY SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.1 FC-RESIDENTIAL.
  
 B) IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED TO MEET THE DESIGN
 PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. SEE NOTE #8
 ON PAGE 2 OF 58 OF FLORIDA PRODUCT APPROVAL SUBMITTED.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) BALCONY DECK UNDERLAYMENT. NOTE: NEED PRODUCT
 APPROVAL THAT IS DESIGNED TO BE USED WITH THE SPECIFIC
 DECK FINISH MATERIAL TO BE INSTALLED IN THIS HOUSE. IN
 ADDITION CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE
 INSTALLED AND PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS IF SELECTED ASSEMBLY DOESN'T MEET THE
 DESIGN PRESSURES FOR ALL ROOF DECK ZONES.
  
 B) ROOF CLAY TILE. NOA 12-0210.01 SUBMITTED EXPIRED ON
 02/01/16. NEED TO PROVIDE CURRENT PRODUCT APPROVAL.
  
 C) ROOF TILE ADHESIVE IF SPECIFIED BY THE ARCHITECT OF
 RECORD. SEE ROOF TILE PRODUCT APPROVAL FOR LISTED
 ADHESIVES.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2017-07-31 Cont ID  
Sent By destabro Date 2017-07-31 Time 15:01 Rev Time 0.00
Received By destabro Date 2017-07-31 Time 15:01 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2017-05-12 Cont ID  
Sent By destabro Date 2017-05-12 Time 11:22 Rev Time 0.00
Received By destabro Date 2017-05-12 Time 11:22 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2017-02-06 Cont ID  
Sent By destabro Date 2017-02-06 Time 11:05 Rev Time 0.00
Received By destabro Date 2017-02-06 Time 11:05 Sent To B
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved