Plan Review Details - Permit 17010580
Plan Review Stops For Permit 17010580
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-14 Cont ID  
Sent By jwitmer Date 2017-03-14 Time 07:38 Rev Time 0.00
Received By jwitmer Date 2017-03-14 Time 07:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2017-01-25 Cont ID  
Sent By jwitmer Date 2017-01-25 Time 13:42 Rev Time  
Received By jwitmer Date 2017-01-25 Time 10:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-03-27 Cont ID  
Sent By vperez Date 2017-03-27 Time 14:07 Rev Time 0.00
Received By vperez Date 2017-03-27 Time 14:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2017-03-16 Cont ID  
Sent By vperez Date 2017-03-16 Time 13:51 Rev Time 0.00
Received By vperez Date 2017-03-16 Time 13:51 Sent To  
Notes
2017-03-16 13:52:35ADDRESS PLUMBING COMMENTS FOR AN ELECTRICA APPROVAL..
  
 V. PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-30 Cont ID  
Sent By vperez Date 2017-01-30 Time 15:48 Rev Time 0.00
Received By vperez Date 2017-01-30 Time 15:40 Sent To  
Notes
2017-01-30 15:49:11PLEASE ADDRESS PLUMBING AND ZONING COMMENTS FOR AN
 ELECTRICAL APPROVAL
  
 V. PEREZ
 *6717

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-23 Cont ID  
Sent By wjolin Date 2017-01-23 Time   Rev Time 0.00
Received By pleduc Date 2017-01-20 Time 16:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-03-16 Cont ID  
Sent By vperez Date 2017-03-16 Time 13:52 Rev Time 0.00
Received By vperez Date 2017-03-16 Time 13:52 Sent To  
Notes
2017-03-06 14:00:03C39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-30 Cont ID  
Sent By vperez Date 2017-01-30 Time 15:49 Rev Time 0.00
Received By vperez Date 2017-01-30 Time 15:49 Sent To  
Notes
2017-01-18 15:57:45C38

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-03-09 Cont ID  
Sent By ccole Date 2017-03-09 Time 08:01 Rev Time 0.00
Received By ccole Date 2017-03-09 Time 07:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By ccole Date 2017-01-25 Time 16:15 Rev Time 0.00
Received By ccole Date 2017-01-25 Time 16:15 Sent To  
Notes
2017-01-25 16:28:511ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010580
 1/25/17
  
 1) THE ENERGYGAUGE COMPLIANCE SUBMITTAL MUST BE SIGNED
 AND DATED BY THE OWNER/AGENT- SEE PAGE #3.
  
 2) THE AC COOLING AND HEATING CALCULATIONS FOR AHU-16
 WERE NOT SUBMITTED- PLEASE PROVIDE.
  
 3) SHEET M-101: THERE IS A O/A WALL CAP FOR AHU'S 2 & 3
 SHOWN IN THE MIDDLE OF THE FOYER, WHICH APPEARS TO BE A
 TYPO. PLEASE INDICATE HOW THE O/A IS BEING SUPPLIED TO
 THE AHU'S AND THE TOTAL AMOUNT OF O/A CFMS SUPPLIED.
  
 4) THE O/A CFMS SHOWN IN THE IAQ PROCEDURE FOR EACH
 AHU, AND THE TOTAL FOR ALL AHU'S DOES NOT MATCH THE O/A
 CFMS LISTED IN THE SCHEDULE ON SHEET M-001, OR THE CFMS
 SHOWN ON THE LAYOUT PLANS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2017-03-27 Cont ID  
Sent By tklarge Date 2017-03-27 Time 11:40 Rev Time 0.00
Received By tklarge Date 2017-03-27 Time 11:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2017-03-15 Cont ID  
Sent By tklarge Date 2017-03-15 Time 09:57 Rev Time 0.00
Received By gjohnson Date 2017-03-14 Time 16:55 Sent To  
Notes
2017-03-15 09:57:381ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: PREVIOUS COMMENTS HAVE NOT BEEN
 COMPLIED WITH SECOND REQUEST.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE INSTANT
 WATER HEATERS.WPB AMEND. TO FBC SEC. 107.2.1.
  
 3) SHT. P-002 - FL. ADMIN. CODE RULE 64E-6.013 (7) (A)
 REQUIRES A MINIMUM 4" OUTLET TEE ON THE GREASE
 INTERCEPTOR THAT EXTENDS TO WITHIN 8 INCHES OF THE
 BOTTOM OF THE TANK. THE DETAIL ON THE PLANS DOES NOT
 SHOW THIS. SUBMIT A CURRENT COPY OF THE STATE APPROVAL
 FOR THIS TANK FROM THE FLORIDA DEPARTMENT OF HEALTH.
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-30 Cont ID  
Sent By gjohnson Date 2017-01-30 Time 10:18 Rev Time 0.00
Received By tklarge Date 2017-01-28 Time 07:31 Sent To  
Notes
2017-01-30 10:18:181) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE INSTANT
 WATER HEATERS.WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. P-002 - WATER HEATER DETAIL - THE RELIEF LINE
 SHALL DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME
 ROOM AS THE WATER HEATER. FBC-PLUMBING SEC.504.6 (2).
 3) SHT. P-002 - FL. ADMIN. CODE RULE 64E-6.013 (7) (A)
 REQUIRES A MINIMUM 4" OUTLET TEE ON THE GREASE
 INTERCEPTOR THAT EXTENDS TO WITHIN 8 INCHES OF THE
 BOTTOM OF THE TANK. THE DETAIL ON THE PLANS DOES NOT
 SHOW THIS. SUBMIT A CURRENT COPY OF THE STATE APPROVAL
 FOR THIS TANK FROM THE FLORIDA DEPARTMENT OF HEALTH.
 4) SHT.P-002 - PENETRATION DETAIL - THERE IS NO FLOOR
 PENETRATION DETAIL ON THE PLANS FOR A 3 INCH PVC PIPE.
 THERE IS CURRENTLY A 3 INCH PVC PIPE INSTALLED IN ROOM
 # 114 THAT PENETRATES THE 2ND FLOOR SLAB FOR A WATER
 CLOSET ON THE 2ND FLOOR IN ROOM #205. THE PVC PIPE IN
 THE FIELD HAS BEEN PAINTED WITH A BLACK FIRE RETARDANT
 PAINT. THERE ARE NO SPECIFICATIONS FOR THIS MATERIAL
 THAT HAS BEEN SUBMITTED TO ME FOR REVIEW NOR ARE THERE
 ANY DETAILS ON THE PLANS FOR THIS MATERIAL. ALSO, I
 HAVE NO DOCUMENTATION THAT THIS MATERIAL HAS BEEN
 REVIEWED AND APPROVED BY THE DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE.SUBMIT A LISTED PENETRATION DETAIL
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD. WPB
 AMEND. TO FBC SEC. 107.21, 107..3.4.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date   Cont ID  
Sent By llouie Date 2017-03-09 Time   Rev Time 0.00
Received By   Date 2017-03-09 Time   Sent To  
Notes
2017-03-09 16:42:04MASTER #16041215

Review Stop Z ZONING
Rev No 1 Status F Date 2017-01-24 Cont ID  
Sent By llouie Date 2017-01-24 Time   Rev Time  
Received By llouie Date 2017-01-24 Time   Sent To  
Notes
2017-01-24 08:18:33** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) ATTACHED THE SITE PLAN FOR THE PROJECT. PREVIOUS
 PLANS VOIDED BY THE CONTRACTOR. ANY CHANGES TO THE SITE
 PLAN WILL REQUIRE AN AMENDMENT TO THE APPROVED SITE
 PLAN THROUGH THE PLANNING DIVISION.
  
 * REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.
  