Plan Review Details - Permit 17010528
Plan Review Stops For Permit 17010528
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2017-02-10 Cont ID  
Sent By gjohnson Date 2017-02-10 Time 10:27 Rev Time 0.00
Received By gjohnson Date 2017-02-10 Time 10:12 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2017-01-25 Cont ID  
Sent By gjohnson Date 2017-01-25 Time 10:01 Rev Time 0.00
Received By gjohnson Date 2017-01-25 Time 10:01 Sent To  
Notes
2017-01-25 10:33:301ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. PROVIDE LONGEST LENGTH FROM METER TO REGULATOR #4.
 PER WPB AMEND. TO FBC 107.2.1
  
 2. PROVIDE TABLE USED TO SIZE 2PSI SYSTEM ON THE PE AND
 SCH 40 MET. PIPE. PER WPB AMEND. TO FBC 107.2.1
  
 3. PLEASE PROVIDE BTU LOAD ON THE RISER FOR THE FIRE
 PIT BRANCH'S. PER WPB AMEND. TO FBC 107.2.1
  
 4. THE SECTION OF PE PIPE FROM REG. #3 TO THE COOK TOP
 TEE IS UNDER SIZED SHALL BE 1". PER FBC GAS TABLE
 402.4(21)
  
 5. THE SECTION OF PE PIPE FROM COOK TOP TEE TO DRYER
 BRANCH IS UNDER SIZED SHALL BE 3/4". PER FBC GAS TABLE
 402.4(21)
  
 6. THE SECTION OF PE PIPE FROM REG. #4 FIST TEE IS
 UNDER SIZED SHALL BE 11/2". PER FBC GAS TABLE 402.4(21)
  
 7. THE SECTION OF PE PIPE FROM REG. #4 FIST TEE TO
 PIZZA OVEN AND BBQ IS UNDER SIZED SHALL BE 11/4". PER
 FBC GAS TABLE 402.4(21)
  
 8. THE SECTION OF PE PIPE FROM REG. #4 FIST TEE TO FIST
 FIRE PIT IS UNDER SIZED SHALL BE 1". PER FBC GAS TABLE
 402.4(21)
  
 9. THE SECTION OF PE PIPE BETWEEN FIRE PITS ON POOL
 DECK IS UNDER SIZED SHALL BE 3/4". PER FBC GAS TABLE
 402.4(21)
  
 10. THE SECTION OF PE PIPE.TO FIRE PIT ON SECOND FLOORR
 IS UNDER SIZED SHALL BE 3/4". PER FBC GAS TABLE
 402.4(21)
  
 11. THE BRANCH PIPE TO FIRE PITS ON POOL DECK IS UNDER
 SIZED SHALL BE 3/4". PER FBC GAS TABLE 402.4(21)
  
 12. THE CSST TO FIRE PIT ON SECOND FLOO IS UNDERSIZED
 SHALL BE 1" EHD 30 . PER FBC GAS TABLE 402.4(15)
  
 13. THE CSST TO COOK TOP IS UNDERSIZED SHALL BE 1" EHD
 30 . PER FBC GAS TABLE 402.4(15)
  
 14. PLEASE PROVIDE EHD SIZE ON ALL CSST PIPING. PER WPB
 AMEND. TO FBC 107.2.1
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-10 Cont ID  
Sent By gjohnson Date 2017-02-10 Time 10:28 Rev Time 0.00
Received By gjohnson Date 2017-02-03 Time 15:58 Sent To  
Notes
2017-02-03 15:58:26GJOHNSON'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-25 Cont ID  
Sent By gjohnson Date 2017-01-25 Time 10:33 Rev Time 0.00
Received By gjohnson Date 2017-01-17 Time 16:18 Sent To  
Notes
2017-01-17 16:18:49GJOHNSON'S DESK


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved