2017-01-25 10:33:30 | 1ST REVIEW |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER LL |
| CITY OF WEST PALM BEACH |
| DEVELOPMENT SERVICES |
| BUILDING DIVISION |
| 561-805-6711 |
| [email protected] |
| |
| GAS COMMENTS: |
| |
| 1. PROVIDE LONGEST LENGTH FROM METER TO REGULATOR #4. |
| PER WPB AMEND. TO FBC 107.2.1 |
| |
| 2. PROVIDE TABLE USED TO SIZE 2PSI SYSTEM ON THE PE AND |
| SCH 40 MET. PIPE. PER WPB AMEND. TO FBC 107.2.1 |
| |
| 3. PLEASE PROVIDE BTU LOAD ON THE RISER FOR THE FIRE |
| PIT BRANCH'S. PER WPB AMEND. TO FBC 107.2.1 |
| |
| 4. THE SECTION OF PE PIPE FROM REG. #3 TO THE COOK TOP |
| TEE IS UNDER SIZED SHALL BE 1". PER FBC GAS TABLE |
| 402.4(21) |
| |
| 5. THE SECTION OF PE PIPE FROM COOK TOP TEE TO DRYER |
| BRANCH IS UNDER SIZED SHALL BE 3/4". PER FBC GAS TABLE |
| 402.4(21) |
| |
| 6. THE SECTION OF PE PIPE FROM REG. #4 FIST TEE IS |
| UNDER SIZED SHALL BE 11/2". PER FBC GAS TABLE 402.4(21) |
| |
| 7. THE SECTION OF PE PIPE FROM REG. #4 FIST TEE TO |
| PIZZA OVEN AND BBQ IS UNDER SIZED SHALL BE 11/4". PER |
| FBC GAS TABLE 402.4(21) |
| |
| 8. THE SECTION OF PE PIPE FROM REG. #4 FIST TEE TO FIST |
| FIRE PIT IS UNDER SIZED SHALL BE 1". PER FBC GAS TABLE |
| 402.4(21) |
| |
| 9. THE SECTION OF PE PIPE BETWEEN FIRE PITS ON POOL |
| DECK IS UNDER SIZED SHALL BE 3/4". PER FBC GAS TABLE |
| 402.4(21) |
| |
| 10. THE SECTION OF PE PIPE.TO FIRE PIT ON SECOND FLOORR |
| IS UNDER SIZED SHALL BE 3/4". PER FBC GAS TABLE |
| 402.4(21) |
| |
| 11. THE BRANCH PIPE TO FIRE PITS ON POOL DECK IS UNDER |
| SIZED SHALL BE 3/4". PER FBC GAS TABLE 402.4(21) |
| |
| 12. THE CSST TO FIRE PIT ON SECOND FLOO IS UNDERSIZED |
| SHALL BE 1" EHD 30 . PER FBC GAS TABLE 402.4(15) |
| |
| 13. THE CSST TO COOK TOP IS UNDERSIZED SHALL BE 1" EHD |
| 30 . PER FBC GAS TABLE 402.4(15) |
| |
| 14. PLEASE PROVIDE EHD SIZE ON ALL CSST PIPING. PER WPB |
| AMEND. TO FBC 107.2.1 |
| |
| |
| |