Plan Review Details - Permit 17010523
Plan Review Stops For Permit 17010523
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-02-16 Cont ID  
Sent By shill Date 2017-02-16 Time 12:06 Rev Time 0.00
Received By shill Date 2017-02-16 Time 11:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-27 Cont ID  
Sent By shill Date 2017-01-27 Time 15:52 Rev Time 0.00
Received By shill Date 2017-01-26 Time 18:18 Sent To  
Notes
2017-01-27 15:54:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY. THE
 PREVIOUS TENANT WAS A RESTAURANT. REVISE PLAN TO
 INCLUDE THIS INFORMATION (CHANGE OF OCCUPANCY FROM A2
 TO B) AND CONFIRM COMPLIANCE WITH ALL REQUIREMENTS OF
 FBC EB CHAPTER 10.
  
 2. REVISE PLAN TO INCLUDE OCCUPANT LOAD, FBC 107, FBC
 CHAPTER 10.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-02-14 Cont ID  
Sent By rlecky Date 2017-02-14 Time 14:12 Rev Time 0.00
Received By rlecky Date 2017-02-14 Time 12:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By rlecky Date 2017-02-02 Time 11:24 Rev Time 0.00
Received By rlecky Date 2017-01-31 Time 14:41 Sent To  
Notes
2017-02-02 11:26:33PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE INTERIOR LIGHTING CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION REQUIREMENTS. FBC C405
  
 ELECTRIC RISER PLAN DETAISL ARE INCOMPLETE ON THE PLANS
 AND REQUIRE CLARIFICATION. FOUR NEW PANEL BOARDS ARE
 SHOWN ONLY TWO HAVE BEEN IDENTIFIED. PANEL A ON THE
 RISER PLAN IS IDENTIFIED AS EXISTING BUT DRAWN AS NEW
 AND WITHOUT FEEDER DETAILS. DETAILS AND LOCATION FOR
 PANEL ELP SEEM TO BE MISSING. FEEDER AND OVERCURRENT
 DETAILS FOR THE EXISTING PANELS ARE MISSING. NEC 215.5
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654
 561-373-3701
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-02-24 Cont ID  
Sent By scaldero Date 2017-02-24 Time 13:00 Rev Time 0.00
Received By scaldero Date 2017-02-24 Time 13:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2017-01-23 Cont ID  
Sent By scaldero Date 2017-01-23 Time 10:43 Rev Time 0.00
Received By scaldero Date 2017-01-23 Time 10:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-24 Cont ID  
Sent By skennedy Date 2017-02-24 Time 15:13 Rev Time 0.00
Received By skennedy Date 2017-02-10 Time 14:10 Sent To  
Notes
2017-02-13 14:10:47C10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-02-02 Cont ID  
Sent By rlecky Date 2017-02-02 Time 11:38 Rev Time 0.00
Received By rlecky Date 2017-01-17 Time 11:36 Sent To  
Notes
2017-01-18 11:36:12C10

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2017-02-28 Cont ID  
Sent By skennedy Date 2017-02-28 Time 12:08 Rev Time 0.00
Received By skennedy Date 2017-02-28 Time 12:08 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2017-02-02 Cont ID  
Sent By rlecky Date 2017-02-02 Time 11:38 Rev Time 0.00
Received By rlecky Date 2017-02-02 Time 11:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2017-02-15 Cont ID  
Sent By ccole Date 2017-02-15 Time 10:01 Rev Time 0.00
Received By ccole Date 2017-02-15 Time 10:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2017-01-31 Cont ID  
Sent By ccole Date 2017-01-31 Time 09:56 Rev Time 0.00
Received By ccole Date 2017-01-31 Time 08:39 Sent To  
Notes
2017-01-31 10:15:151ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17010523
 1/31/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) REFER TO SECTION C403.2.4.4 FBC-14 ENERGY
 CONSERVATION AND PROVIDE MOTORIZED DAMPERS FOR EACH O/A
 DUCT SUPPLYING THE HEAT PUMPS.
  
 3) PROVIDE A SEQUENCE OF OPERATION FOR THE DS
 DETECTORS. CLARIFY IF ALL FANS ARE LINKED TOGETHER FOR
 SIMULTANEOUS FAN SHUTDOWN UPON ANY ONE DETECTOR
 ACTIVATING.
  
 4) THE MIAMI-DADE NOA #13-1017.09 CALLED OUT ON M&-2
 HAS BEEN SUPERSEDED BY NOA #15-0902.05. PLEASE SUBMIT
 TWO COPIES WITH ALL APPLICABLE INSTALLATION DETAILS
 MARKED OR HIGHLIGHTED, AND SHOP DRAWING APPROVAL STAMPS
 BY THE EOR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-22 Cont ID  
Sent By gjohnson Date 2017-02-22 Time 14:30 Rev Time 0.00
Received By gjohnson Date 2017-02-22 Time 14:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-31 Cont ID  
Sent By tklarge Date 2017-01-31 Time 06:00 Rev Time 0.00
Received By tklarge Date 2017-01-31 Time 05:23 Sent To  
Notes
2017-01-31 05:59:221) INDICATE THE OCCUPANT LOAD ON THE PLANS IN
 COMPLIANCE WITH FBC-BUILDING TABLE 1004.1.
 2) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS,
 URINALS AND WATER CLOSETS SHALL COMPLY WITH 2014
 FBC-BUILDING SEC.1210.2.2.
 3) SHT. A1.4 - D6 - THE GRAB BARS SHALL BE MEASURED TO
 THE TOP OF THE GRIPPING SURFACE. 2014 FBC-ACCESSIBILITY
 SEC. 609.4.
 4) SHT.A1.4- DETAIL 6 - THE KNEE AND TOE CLEARANCE
 SPACE UNDER THE ACCESSIBLE LAVATORY SHALL CCOMPLY WITH
 2014 FBC-ACCESSIBILITY SEC. 306.
 5) SUBMIT MANUFACT. SPECIFICATIONS FOR THE CONDENSATE
 PUMP. WPB AMEND. TO FBC SEC. 107.2.1.
 6) SHT. P2.1 - KEYNOTE #2 NOTES THE CONDENSATE BRANCH
 AS 1 1/2 INCH AND THE CONDENSATE PUMP LAYOUT SHOWS A 2
 INCH HEADER. CLARIFY. THE PLAN DOES NOT SHOW THE 2 INCH
 HEADER.
 7) ALL COFFEE MAKERS & ICE MAKERS SHALL BE EQUIPPED
 WITH BACKFFLOW PREVENTERS PER 2014 FBC-PLUMBING
 SEC.608.3, 608.16.10.
 8) SHT.P5.1 - SHOWS A SINK ON A WET VENT WHICH IS NOT
 PERMITTED PER 2014 FBC-PLUMBING SEC.912.1. AN
 INDIVIDUAL VENT ON THE MOP SINK WWILL CORRECT THIS
 ISSUE.
 9) SHT. P5.1 - WATER RISER - MEN'S RESTROOM #135 - IT
 APPEARS THAT ONLY ONE WC-1 IS SHOWN ON THE WATER RISER.
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  