Plan Review Details - Permit 17010482
Plan Review Stops For Permit 17010482
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-03-23 Cont ID  
Sent By jwitmer Date 2017-03-23 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2017-03-23 Time 11:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-26 Cont ID  
Sent By jwitmer Date 2017-01-26 Time 15:54 Rev Time 0.00
Received By jwitmer Date 2017-01-26 Time 09:35 Sent To  
Notes
2017-01-26 15:54:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17010482
 ADD: 625 N. FLAGLER DR. SUITE # 200
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-615-3903
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 26/ 2017
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET A0.02 SEE 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS: BUILDING/ MINIMUM
 TYPE OF CONSTRUCTION SHALL BE DETERMINED (TABLE 503 OF
 THE 2014 FBC-B).
  
 2) SHEET A1.12 THE FLOOR PLAN DIMENSION SHEET FOR THE
 RESTROOMS 238 AND 257 THE PLANS DO NOT HAVE THE
 DIMENSION FRONT TO BACK FOR CONSTRUCTION. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET A4.21 THERE ARE VARIOUS ELEVATIONS OR VIEWS OF
 THE FRONT COUNTER WITH THE TRANSACTION COUNTER SURFACE
 AT AN ELEVATION OF 3 FT. 6 INCHES. 2014
 FBC-ACCESSIBILITY CODE 904.3.3 CHECK WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3.
 2014 FBC-ACCESS. CODE 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4) SHEET A4.2.2 DETAILS 3 & 4 BOTH SHOW A CUT SECTION
 THROUGH A LAV AND MIRROR ABOVE, DETAIL # 6/ A5.51.
 DISCREPANCY IN PLANS, NOT THE CORRECT DETAIL.
 107.2.1.3. ADDITIONAL INFORMATION REQUIRED.
 2014 FBC-ACCESS. CODE 603.3 40 INCHES TO THE BOTTOM
 EDGE OF THE REFLECTIVE SURFACE.
  
 5) SHEET A4.22 SHOW WALL TILE INSTALLED IN ALL WET
 AREAS. SHEET A0.15 IN ALL WET AREAS THE SCHEDULE
 INDICATES A TILE FOR THE FINISH WALL AND WALL MATERIAL
 TO BE GYPSUM. PLEASE REVIEW SECTIONS 2509.2 BASE FOR
 TILE & 2509.3 LIMITATIONS OF WATER RESISTANT GYPSUM.
 2014 FBC-B.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2017-03-14 Cont ID  
Sent By rlecky Date 2017-03-14 Time 14:29 Rev Time 0.00
Received By rlecky Date 2017-03-14 Time 14:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2017-01-19 Cont ID  
Sent By rlecky Date 2017-01-19 Time 14:01 Rev Time 0.00
Received By rlecky Date 2017-01-19 Time 14:01 Sent To  
Notes
2017-01-19 14:02:11PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 WIRING IN ALL PATIENT CARE AREAS / EXAM ROOMS REQUIRES
 A SPECIFIC ELECTRICAL WIRING METHOD THAT PROVIDES
 REDUNDANT GROUNDING AND INCLUDES AN INSULATED COPPER
 EQUIPMENT GROUND. NEC 517.13
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-805-6654
 561-373-3701
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2017-03-14 Cont ID  
Sent By pleduc Date 2017-03-14 Time   Rev Time 0.00
Received By pleduc Date 2017-03-13 Time 15:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2017-01-20 Cont ID  
Sent By pleduc Date 2017-01-20 Time   Rev Time 0.00
Received By pleduc Date 2017-01-19 Time 15:59 Sent To  
Notes
2017-01-20 14:28:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 1.11 - THERE ARE SEVERAL DOORS THAT ARE
 INDICATED AS OPENING IN THE EGRESS CORRIDORS : 046,
 045, 034, 033, 032, 027, & 028.
  
 PER NFPA 101 CAHPTER 38, NEW BUSINESS OCCUPANCIES.
  
 38.2 MEANS OF EGRESS REQUIREMENTS.
 38.2.1 GENERAL.
 38.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE
 WITH CHAPTER 7 AND THIS CHAPTER.
  
 PER NFPA 101 CHAPTER 7 , MEANS OF EGRESS.
  
 7.2.4.3 DOOR LEAF ENCROACHMENT
  
 7.2.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS OF
 EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING UNOBSTRUCTED AND SHALL PROJECT NOT MORE
 THAN 7 IN. (180 MM) INTO THE REQUIREDWIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED AND
 SHALL PROJECT NOT MORE THAN 7 IN. (180 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING, WHEN FULLY OPEN, UNLESS BOTH OF THE
 FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT THAT LIMITS
 PROJECTION TO NOT MORE THAN 7 IN. (180 MM) INTO THE
 REQUIRED WIDTH OF THE STAIR LANDING WHEN THE DOOR LEAF
 IS FULLY OPEN.
  
 7.2.1.4.3.2 SURFACE-MOUNTED LATCH RELEASE HARDWARE ON
 THE DOOR LEAF SHALL BE EXEMPT FROM BEING INCLUDED IN
 THE MAXIMUM 7 IN. (180 MM) PROJECTION REQUIREMENT OF
 7.2.1.4.3.1, PROVIDED THAT BOTH OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE HARDWARE IS MOUNTED TO THE SIDE OF THE DOOR
 LEAF THAT FACES THE AISLE, CORRIDOR, PASSAGEWAY, OR
 LANDING WHEN THE DOOR LEAF IS IN THE OPEN POSITION.
 (2) THE HARDWARE IS MOUNTED NOT LESS THAN 34 IN. (865
 MM), AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE
 FLOOR.
  
 PLEASE PROVIDE FOR THE REQUIREMENTS NOTED ABOVE.
  
  
  
 2) EMERGENCY LIGHTING APPEARS TO BE PROVIDED GENERALLY
 THROUGHOUT THE PROPOSED PROJECT; HOWEVER, SOME AREAS OF
 THE MEANS OF EGRESS APPEAR TO BE UNDERSERVED.
  
 38.2.9 EMERGENCY LIGHTING.
 38.2.9.1 EMERGENCY LIGHTING SHALL BE PROVIDED IN
 ACCORDANCE WITH SECTION 7.9 IN ANY BUILDING WHERE ANY
 ONE OF THE FOLLOWING CONDITIONS EXISTS:
 (1) THE BUILDING IS THREE OR MORE STORIES IN HEIGHT.
 (2) THE OCCUPANCY IS SUBJECT TO 50 OR MORE OCCUPANTS
 ABOVE OR BELOW THE LEVEL OF EXIT DISCHARGE.
 (3) THE OCCUPANCY IS SUBJECT TO 300 OR MORE TOTAL
 OCCUPANTS.
  
 7.9.2 PERFORMANCE OF SYSTEM.
 7.9.2.1* EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A
 MINIMUM OF 1? HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE (10.8 LUX) AND, AT
 ANY POINT, NOT LESS THAN 0.1 FT-CANDLE (1.1 LUX),
 MEASURED ALONG THE PATH OF EGRESS AT FLOOR LEVEL.
 ILLUMINATION LEVELS SHALL BE PERMITTED TO DECLINE TO
 NOT LESS THAN AN AVERAGE OF 0.6 FT-CANDLE (6.5 LUX)
 AND, AT ANY POINT, NOT LESS THAN 0.06 FT-CANDLE (0.65
 LUX) AT THE END OF 1? HOURS. A MAXIMUM-TO-MINIMUM
 ILLUMINATION UNIFORMITY RATIO OF 40 TO 1 SHALL NOT BE
 EXCEEDED.
  
 7.9.2.3* THE EMERGENCY LIGHTING SYSTEM SHALL BE
 ARRANGED TO PROVIDE THE REQUIRED ILLUMINATION
 AUTOMATICALLY IN THE EVENT OF ANY INTERRUPTION OF
 NORMAL LIGHTING DUE TO ANY OF THE FOLLOWING:
 (1) FAILURE OF A PUBLIC UTILITY OR OTHER OUTSIDE
 ELECTRICAL POWER SUPPLY
 (2) OPENING OF A CIRCUIT BREAKER OR FUSE
 (3) MANUAL ACT(S), INCLUDING ACCIDENTAL OPENING OF A
 SWITCH CONTROLLING NORMAL LIGHTING FACILITIES
  
 PLEASE PROVIDE AND/OR ENSURE COMPLIANCE WITH THE
 REQUIRMENTS.
  
  
  
 3) SHEET 0.02 - THERE IS NO INDICATIONS OF FIRE ALARM
 SYSTEM WORK.
  
 ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE
 UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-04-04 Cont ID  
Sent By gjohnson Date 2017-04-04 Time 14:17 Rev Time 0.00
Received By gjohnson Date 2017-03-08 Time 11:10 Sent To  
Notes
2017-03-09 11:11:12C09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-27 Cont ID  
Sent By tklarge Date 2017-01-27 Time 12:57 Rev Time 0.00
Received By tklarge Date 2017-01-13 Time 14:46 Sent To  
Notes
2017-01-17 14:46:36C14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2017-01-26 Cont ID  
Sent By jwitmer Date 2017-01-26 Time 15:54 Rev Time 0.00
Received By jwitmer Date 2017-01-26 Time 09:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2017-01-18 Cont ID  
Sent By jvalido Date 2017-01-18 Time 17:21 Rev Time 0.00
Received By jvalido Date 2017-01-18 Time 16:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-04-04 Cont ID  
Sent By gjohnson Date 2017-04-04 Time 14:16 Rev Time 0.00
Received By gjohnson Date 2017-04-04 Time 10:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-27 Cont ID  
Sent By tklarge Date 2017-01-27 Time 12:57 Rev Time 0.00
Received By tklarge Date 2017-01-27 Time 11:03 Sent To  
Notes
2017-01-27 12:22:381) TOILET ROOMS #204 AND #205 SHALL HAVE HANDICAPPED
 ACCESSIBLE TOILET COMPARTMENTS LOCATED WITHIN THE
 RESTROOMS PER THE 2014 FBC- ACCESSIBILITY SEC.213.3.1.
 THE TOILET COMPARTMENT DIMENSIONS SHALL COMPLY WITH
 2014 FBC - ACCESS. SECS. 305, 604.
 2) A LAVATORY SHALL BE LOCATED WITHIN EACH REQUIRED
 TOILET COMPARTMENT PER THE 2014 FBC SEC.604.8.1.6.
 3) SHOW THE CLEAR INSIDE DIMENSIONS OF ALL TOILET
 ROOMS. ACCESSIBLE TOILET ROOMS SHALL COMPLY WITH 2014
 FBC-ACCESSIBILITY SECS. 604.3 FOR WATER CLOSETS AND
 SEC.606.2 FOR LAVATORIES.
 4) A 30 INCH WIDE BY 48 INCH LONG CLEAR FLOOR SPACE
 CENTERED ON THE FIXTURE IS REQUIRED FOR THE BREAK ROOM
 SINK. COMPLY WITH FBC-ACCESS. SEC.606.2.
 5) THE ACCESSIBLE DRINKING FOUNTAIN LOCATED IN CORRIDOR
 # 206 SHALL COMPLY WITH 2014 FBC- ACCESS. SEC.307.2 FOR
 PROTRUSION LIMITS.
 6) SHT. A4.22 - REFERENCED IS MADE TO THE 2010 FBCA.
 THE CODEE IN EFFECT IS THE 2014 FBC.
 7) SHT. A4.23 - THE HEIGHT OF THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2014
 FBC SEC.609.4.
 8) THE MAXXIMUM REACH RANGE HEIGHT FOR THE PAPER TOWEL
 DISPENSER SHALL COMPLY WITH 2014 FBC - ACCESS. SEC.308.
 9) SHOW THE CAPACITY OF THE EXPANSION TANK ON THE WATER
 HEATER. WPB AMEND. TO FBC SEC. 107.2.1.
 10) SHT. P5.1 - SIZE ALL VENTS ON THE SANITARY RISER.
 COMPLY WITH 2014 FBC-PLUMBING SEC.906.1.
 11) THE VENT FOR THE TWO MOST UPSTREAM WATER CLOSETS ON
 THE SANITARY RISER ( TOILET ROOMS 204 & 205 ) SHALL BE
 TAKEN OFF BETWEEN THE WATER CLOSETS . 2014 FBC-PLUMBING
 SEC.901.2, 905.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  