Plan Review Details - Permit 17010460
Plan Review Stops For Permit 17010460
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2017-02-06 Cont ID  
Sent By tklarge Date 2017-02-06 Time 13:45 Rev Time 0.00
Received By tklarge Date 2017-02-06 Time 13:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-02-06 Cont ID  
Sent By tklarge Date 2017-02-06 Time 13:45 Rev Time 0.00
Received By tklarge Date 2017-02-02 Time 14:12 Sent To  
Notes
2017-02-02 14:12:22RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-30 Cont ID  
Sent By tklarge Date 2017-01-30 Time 06:31 Rev Time 0.00
Received By tklarge Date 2017-01-13 Time 15:49 Sent To  
Notes
2017-01-27 15:49:46PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-02-06 Cont ID  
Sent By tklarge Date 2017-02-06 Time 13:45 Rev Time 0.00
Received By tklarge Date 2017-02-03 Time 04:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-30 Cont ID  
Sent By tklarge Date 2017-01-30 Time 06:31 Rev Time 0.00
Received By tklarge Date 2017-01-30 Time 05:35 Sent To  
Notes
2017-01-30 06:12:431) INDICATE THE SIZE AND THE CORRESPONDING EHD OF THE
 CSST BEING INSTALLED. WPB AMENDMENTS TO FBC
 SEC.107.2.1.
 2) SHOW THE LOCATION OF THE MEDIUM PRESSURE GAS
 REGULATOR. A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. FBC-FUEL GAS
 SEC.409.4.
 3) INDICATE ON THE PLAN IF THE EXISTING TANK TYPE WATER
 HEATER WAS GAS OR ELECTRIC. IF IT WAS ELECTRIC, THEN A
 SEPARATE ELECTRIC PERMIT WILL BE REQUIRED.
 4) SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-RES.
 SEC.G2426.
 5) A PLAN HAS BEEN SUBMITTED SHOWING AND EN ELECTRIC
 OUTLET AND SOME ADDITIONAL WRITING THAT IS ILLEGIBLE.
 IS THIS ELECTRIC OUTLET NEW OR EXISTING? CLARIFY THE
 ADDITIONAL WRITING ON THE PLAN THAT CANNOT BE READ. WPB
 AMEND. TO FBC SEC. 107.2.1.
 6) INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER IS
 THE ONLY GAS APPLIANCE ON THIS SYSTEM? IF NOT, SUBMIT A
 COMPLETE GAS RISER SHOWING ALL PIPE SIZES, TYPE OF
 PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS OUTLET,
 THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE SYSTEM,
 THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE SYSTEM.
 THESE REQUIREMENTS ALSO APPLY TO A NEW GAS SYSTEM.
 7) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 OF ANY OPERABLE DOORS OR WINDOWS. THE LOCATION OF THE
 WATER HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. IN ADDITION, SUBMIT TWO COPIES OF THE PAGE FROM
 THE MANUFACTURER'S INSTALLATION MANUAL THAT SHOWS THE
 REQUIRED CLEARANCES FROM OPERABLE WINDOWS AND DOORS.
 8) SUBMIT TWO COPIES OF THE SIZING TABLES USED IN THE
 DESIGN FOR THIS GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM. FGC SEC.402.3, FBCR SEC. G 2413.3.
 9) SOME OF THE INFORMATION ON THE PLAN IS CUT OFF THE
 PAGE. SUBMIT A PLAN WITH ALL NOTES.WPB AMEND. TO FBC
 SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  