Plan Review Details - Permit 17010390
Plan Review Stops For Permit 17010390
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-26 Cont ID  
Sent By tklarge Date 2017-01-26 Time 04:55 Rev Time 0.00
Received By tklarge Date 2017-01-23 Time 11:30 Sent To  
Notes
2017-01-24 11:30:51RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-18 Cont ID  
Sent By tklarge Date 2017-01-18 Time 05:48 Rev Time 0.00
Received By tklarge Date 2017-01-12 Time 11:08 Sent To  
Notes
2017-01-13 11:08:46PLUMB <5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2017-01-26 Cont ID  
Sent By tklarge Date 2017-01-26 Time 04:55 Rev Time 0.00
Received By tklarge Date 2017-01-26 Time 04:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2017-01-18 Cont ID  
Sent By tklarge Date 2017-01-18 Time 05:47 Rev Time 0.00
Received By tklarge Date 2017-01-18 Time 05:36 Sent To  
Notes
2017-01-18 05:47:50AN AIR ADMITTANCE CANNOT BE USED IN A PLUMBING SYSTEM
 WITHOUT A MINIMUM OF ONE STACK VENT OR VENT STACK
 EXTENDED TO THE OUTDOORS TO THE OPEN AIR PER 2014
 FBC-PLUMBING SEC. 918.7.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  