2017-02-01 14:53:26 | BUILDING PLAN REVIEW |
| 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE COPY OF EXISTING FLOOR PLAN. IDENTIFY EACH |
| ROOM. |
| 2. PROVIDE COPY OF PROPOSED FLOOR PLAN, SHOW LOCATION |
| OF PROPOSED NEW BATH. |
| 3. NEW WOOD FRAMED WALL INSULATION SHALL BE A MINIMUM |
| OF R-13 PER TABLE R402.1.1 |
| 4. PROVIDE PRODUCT APPROVALS FOR NEW WINDOW. |
| 5. PROVIDE MANUFACTURER'S SPECIFICATIONS FOR PROPOSED |
| DUROCK. DEMONSTRATE DUROCK IS AN APPROVED SUBSTRATE FOR |
| THE APPLICATION OF PORTLAND CEMENT BASED WALL VENEER. |
| (STUCCO) |
| 6. PARTIAL FLOOR PLAN IDENTIFIES EXISTING DOOR AS 3" X |
| 6". PLEASE CLARIFY. |
| 7. PROVIDE ATTACHMENT DETAIL AND FASTENER SCHEDULE FOR |
| NEW WOOD WALL TO EXISTING 8" CMU WALL. |
| |
| FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: |
| |
| TABLE R402.1.1 INSULATION AND FENESTRATION REQUIREMENTS |
| BY COMPONENT |
| |
| FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY |
| FAC RULE 9N-3 REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. SPECIFICALLY, PROVIDE WINDOW |
| SUBMITTALS. |
| |
| |
| |
| |