Plan Review Details - Permit 17010260
Plan Review Stops For Permit 17010260
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2017-01-27 Cont ID  
Sent By rmcdouga Date 2017-01-27 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2017-01-27 Time 09:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2017-01-12 Cont ID  
Sent By rmcdouga Date 2017-01-12 Time 09:25 Rev Time 0.00
Received By rmcdouga Date 2017-01-12 Time 07:12 Sent To  
Notes
2017-01-12 09:25:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE W-44 ROOFING SYSTEM NUMBER THAT WAS SELECTED ON
 PAGE 11 OF THE PRODUCT APPROVAL ( FL5293-R23) HAS A
 MAXIMUM DESIGN PRESSURE OF -52.5 PSF. ROOF ZONES 2 AND
 3 ARE REQUIRED TO HAVE ENHANCED FASTENING CALCULATED BY
 A QUALIFIED DESIGN PROFESSIONAL. SUBMIT TWO SETS OF
 SIGNED AND SEALED ENHANCED FASTENING CALCULATIONS. SEE
 NOTE 9 ON SHEET 3 OF THE EVALUATION REPORT. NOTE: THE
 CALCULATIONS THAT WERE SUBMITTED WITH THE ORIGINAL
 APPLICATION IS SPECIFIC TO NOA NO. 15-0729.18 (PAGES
 14, 15 OF 27).

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2017-01-27 Cont ID  
Sent By rmcdouga Date 2017-01-27 Time 09:29 Rev Time 0.00
Received By rmcdouga Date 2017-01-26 Time 17:17 Sent To  
Notes
2017-01-26 17:17:47RMCDOUGAL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2017-01-12 Cont ID  
Sent By rmcdouga Date 2017-01-12 Time 09:25 Rev Time 0.00
Received By rmcdouga Date 2017-01-10 Time 14:36 Sent To  
Notes
2017-01-10 14:36:58REVISION ROUTED TO RMCDOUGAL